background image

9

4. Assembly and

Installation

4.1 Break Point and General

Unit Assembly

Instructions

Ensure that all the air-handling unit

sections are positioned in the correct

order. 
Each section will display a unit drawing

with its position OUTLINED.  
1.Each of the unit sections should be

placed on a level foundation and within

200 mm of its adjoining section.

2.Remove any supports and bracing

which are supplied with the unit for

transport. All such supports will be

clearly marked:

“FOR TRANSPORT ONLY – 

REMOVE BEFORE ASSEMBLY”

3.Remove 4 M6 fixing 

bolts (A)

from the

protruding portion of the 4 framework

joining bars (see Figure 9), then loosen

the remaining 4 bolts  that are located

on the fixed side of the break point

joining bars.

Pull together the sections of the unit,

ensuring that the joiner bar in each of

the 4 corners is fitted into its adjoining

section and the plastic “T” section

sealing strip locates over the adjoining

panel.

The 52-mm diameter holes provided in

the unit base frame should be used to

manoeuvre the sections together. 

Greased skid plates will greatly assist

the whole assembly operation.

4. Secure the break point joint externally

by replacing the 4 M6 bolts and

washers, which were previously

removed in step (3). Retighten the 8

bolts located on both sides of the break

point joint. 

Where applicable, complete the

assembly of the unit as follows:

4.1.3. Fan sections

Bolt the outlet of the fan to the flexible

connection using the M8 bolts provided.

4.1.4. Damper sections

Pop-rivet through the damper spigot and

the adjoining plastic “J” section into the

adjacent fixed panel using 5-mm-

diameter rivets.

4.1.5. Coil sections (with drip pans)

Fix through the top of the drip pan into the

box section using the self-drilling screws,

which are provided.  Then seal along all

joints with a waterproof “silicone” based

sealant. We recommend “Siloflex.”

4.1.6. Weatherproof roofs

Slide on the “Doby” cleats, which are

provided, and then fix in position at the

ends with the cleat clips on the roof return

edge using 5mm diameter rivets.

2

1

2

1

CLCH-SVX05A-GB

Figure 9

Figure Notes:

1. Part 1
2.Part 2
3. Break Point
4. Bolts “A”
5. Fixed bolts
6. 52 mm diameter holes
7. 8 x M6 bolts (2 per join)

1

2

5

4

7

6

1

2

3

Summary of Contents for CLCH

Page 1: ...Installation Operation Maintenance CLCH QuantumClimate Changer Air Handling Units CLCH SVX05A GB...

Page 2: ...l inspect the unit before signing the delivery note Specify any damage on the delivery note and send a registered letter of protest to the last carrier of the goods within 72 hours of delivery Notify...

Page 3: ...18 23 1 Introduction 2 Delivery Check On Arrival Off Loading and Movement To The Site 3 Foundations and Erection 4 Assembly and Installation 5 Commissioning Procedure 6 Maintenance 7 Troubleshooting...

Page 4: ...CLCH SVX05A GB 4 1 Introduction Please pay particular attention to the instructions on the unit in accordance with the identification label assembly drawings and special warnings or advice labels...

Page 5: ...ff Loading A specific lifting method for offloading the units is recommended as follows see Figure 3 1 52 mm diameter lifting holes or certified lifting lugs are provided on the unit base frame 2 ALL...

Page 6: ...ainst the unit base frame The lift point should be as near as possible to the centre of gravity see Figures 4 and 4a In the case of larger units the use of several forklift trucks may be required 2 4...

Page 7: ...d the unit to ensure that correct operation and effective maintenance can be carried out Figure 6 gives recommended space allowances On the designated access side of the unit working areas must be equ...

Page 8: ...O PROVIDE A LEVEL PLINTH OR SUPPORT WILL RESULT IN DOORS JAMMING AND AIR LEAKS FROM THE CASING 3 2 Erection To minimize noise transmission insulation material such as cork slabbing TICO pads may be pl...

Page 9: ...to manoeuvre the sections together Greased skid plates will greatly assist the whole assembly operation 4 Secure the break point joint externally by replacing the 4 M6 bolts and washers which were pr...

Page 10: ...e the units together Also fix into position any base frame unit end and roof joining brackets that are provided Fix into position any internal joining strips and or brackets that are provided and then...

Page 11: ...reak by means of a tun dish must be fitted immediately after the trap Figure 12 Typical Air Conditioning Plant Drain Figure 12 Notes 1 Cooling coil humidifier or chilled battery 2 Vented drainage stac...

Page 12: ...ns 1 2 pipe diameter insulation Figure Notes 1 Minimum of 12 mm 2 12 mm maximum total static pressure Figure 15 Drip Pans 1 1 2 2 3 4 5 Drip Pans A UPVC elbow and 1 1 2 38 mm diameter internal dimensi...

Page 13: ...ntrol system used All pipework must be supported independently from the coils All connections must be made in such a way that the expansion and contraction of pipes do not impose forces on the coil he...

Page 14: ...the casing must be made with a gland or grommet All wiring to other accessories must be carried out in the same manner PLEASE REFER TO THE UNIT MOUNTED CONTROLS IOM Motor connection details are conta...

Page 15: ...0 70 0 85 5 108 0 127 0 146 0 162 0 177 5 Approximate Mass kg 0 1 0 1 0 2 0 3 0 7 1 5 2 7 3 8 5 6 7 5 11 1 Fenner is a registered trademark of J H Fenner Co Ltd Taper Lock and P B Precision Built are...

Page 16: ...device will fade 16 5 Commissioning Procedure 5 4 Unit Connections All electrical water and ductwork connections of the unit must be completed by a qualified person To avoid damaging the coil connect...

Page 17: ...ork the unit is started up for a test run To conduct a test run that involves the measurement of motor and fan performance the unit must be connected to the complete installation All access doors must...

Page 18: ...A GREASE 3 SHELL MOBILUX 3 MOBIL BEACON 3 ESSO SKF 28 BALL BEARING GREASE Do not overlubricate bearings Excessive pressure caused by overlubrication can displace bearing grease seals or cause grease t...

Page 19: ...80 140 112 236 224 375 56 80 125 200 to to to to to to to to to to to to 95 130 132 200 224 315 355 560 100 140 200 400 Newton N 13 20 25 35 45 65 85 115 5 10 20 40 to to to to to to to to to to to to...

Page 20: ...end of bush using a block of sleeve to prevent damage This will ensure that the bush is seated squarely in the bore Screws will now turn a little more Repeat this alternate hammering and screw tighten...

Page 21: ...n the unit is at rest and check the function of the fan overrun in this context 6 8 5 Direct expansion coils Never use hot water or steam to clean these coils During normal operation the fin block mus...

Page 22: ...6 1 For Corrosion Yes 6 1 Flexible Connection Yes 6 1 Anti Vibration Mounts Yes 6 1 Inlet Guide Vane Controller Yes Drainage Yes 6 1 Fan Bearing Yes 6 2 Motors In General Yes 6 3 Motor Bearing Yes 6 3...

Page 23: ...r grease on belts Clean belts and pulleys check for grease leaks Belts rubbing Remove obstruction Odd belts being fitted Replace with full set Filters collapsing Blocked with dirt Change at advised di...

Page 24: ...vement it reserves the right to change design and specifications without notice Only qualified technicians should perform the installation and servicing of equipment referred to in this publication So...

Reviews: