Trane BAYENTH001A Installer'S Manual Download Page 5

INSTALLER'S GUIDE

page 5

Installation for BAYECON086A,
BAYECON088A
Horizontal Discharge
Single Enthalpy Sensor (Outdoor Air
Only)

1. 

Units with economizers already installed:

When installing the enthalpy sensor after the
economizer has been installed remove the econo-
mizer/filter access panel located on the front side of
the unit. Remove the mist eliminator and retaining
angle from the economizer.

2. Remove the two screws securing the disk type

thermostat to the rear panel.

3. Disconnect the wires 182A(YL) and 183A(YL) from

the thermostat.

4. Locate bushing supplied with kit and pull wires

182A and 183A) through bushing. Snap bushing
into the hole where the thermostat was removed.

5. Connect wire 182A to S and 183A to + terminals on

the Enthalpy Sensor.

6. Using the two screws removed in step 2, mount the

Enthalpy sensor ajacent to thermostat’s previous
location, Engagement holes are provided.

7. On the Control Module (Solid State Economizer

Logic Module) attached to the Economizer Motor,
remove the red resistor from terminals SR and +

and discard.

8. Remove the white resistor from between the SO

terminal and wire 182A. Then install the white
resistor across the SR and + terminals

9. Install the terminal adapter provided with the sensor

on terminal SO of the Control Module and connect
wire 182a to it.

10. Replace the economizer/filter access panel and mist

eliminator.

Installation for Differential Enthalpy
Sensing (Two Sensors)

1. Complete the procedures for installing a single

enthalpy sensor.

2. Mount the second enthalpy sensor on the side of the

return air hood

3. Remove the knock-out located near the front side of

the Return Air Bolckoff  and insert a snap bushing.

4. Install field supplied wires through the snap bushing

from terminals S and + on the return enthalpy sensor
to the SR and + terminals on the Control Module.

5. On the Control Module attached to the Economizer

Motor, remove the white resistor from between the
SR terminal and the + terminal and discard. Then
connect the wire from S on the sensor to SR on the
Control Module and + on the sensor to + on the
Control Module.

 9

Summary of Contents for BAYENTH001A

Page 1: ... Literature Type Sequence Date File No Supersedes Service Literature Unitary Unitary Accessories Econ Dmprs Motors Low Ambient Installer s Guide January 2008 ACC SVN85B EN 01 08 ACC SVN85A EN 11 06 Single Enthalpy Sensor Outdoor Air Only 1 Units with economizers already installed When installing the enthalpy sensor after the economizer has beeninstalledremovetheeconomizer filteraccesspanel located...

Page 2: ...singleenthalpy sensor 2 Mount the second enthalpy sensor on the bottom side of the motor deck see figure 3 3 Remove the knockout located below the Economizer Motor and insert a snap bushing 4 Install field supplied wires through the snap bushing DIFFERENTIAL ENTHALPY SENSOR SCREWS 3 4 5 6 1 M9097_1_ ENTHALPY CHANGEOVER SETPOINT LED LIGHTS WHEN OUTDOOR AIR IS SUITABLE FOR FREE COOLING JUMPER USED F...

Page 3: ...igure 4 7 RemovethewhiteresistorfrombetweentheSO terminal and wire 56A Than install the white resistor across the SR and terminals 665184 8 Installtheterminaladaptorprovidedwiththesensoron terminal SO of the Control Module and connect wire 56A to it 9 Reinstall the rain hood and filter access panel Installation for Differential Enthalpy Sensing 1 Completetheproceduresforinstallingasingleenthalpy s...

Page 4: ...le attached to the Economizer Motor remove the red resistor from terminals SR and and discard See figure 4 8 Remove the white resistor from between the SO terminal and wire 182A YL Then install the white resistor across the SR and terminals 9 Install the terminal adaptor provided with the sensor on terminal SO of the Control Module and connect wire 182A YL to it 10 Replace the economizer filter ac...

Page 5: ...Logic Module attached to the Economizer Motor remove the red resistor from terminals SR and and discard 8 Remove the white resistor from between the SO terminal and wire 182A Then install the white resistor across the SR and terminals 9 Install the terminal adapter provided with the sensor on terminal SO of the Control Module and connect wire 182a to it 10 Replace the economizer filter access pane...

Page 6: ... and discard the OAS removed in steps 2 3 5 Using the two screws removed in step 2 mount the ESC adjacent to the previous location of the OAS Engagement holes are provided 6 Connect the YL BK wire to S and the YL wire to termi nal on enthalpy sensor 7 Reinstall the mist eliminator 8 On the Control Module Solid State Economizer Logic Mod ule attached to the Economizer Motor remove the red resistor ...

Page 7: ...OSA removed in steps 2 3 5 Install ESC on mounting bracket located in the upper corner of the hood using the screws removed in step 2 6 Re install hood on economizer 7 Remove top mist eliminator in hood and connect the YL BK wire to S and the YL wire to terminal on ESC 8 Re install mist eliminator into hood 9 On the Control Module attached to the Economizer Motor remove the red resister from termi...

Page 8: ...you must turn the control set point past D fully clockwise Differential enthalpy is not available for 101 102 103 104 Economizers If the outdoor air enthalpy is lower than the return air enthalpy the outdoor air damper will proportion open on a call for cooling If the outdoor air enthalpy is higher than the return air enthalpy the outdoor air damper will close to minimum position If the outdoor ai...

Page 9: ...t of sensor to simulate low enthalpy conditions See figure 12 2 Terminals 2 3 closed Terminals 1 2 open B Disconnect power at TR and TR1 Terminals 2 3 open Terminals 1 2 closed A 1 Turn enthalpy set point on Economizer Logic Module past D full clockwise 1 LED turns off 2 With power connected spray a small amount of environmentally safe coolant into upper left vent of sensor connected to SO and to ...

Page 10: ...y Sensor Wiring When Used With BAYECON054 055 73 BAYECON086A 088A ECONOMIZER W OPTIONAL OUTDOOR ENTHALPY SENSOR ECONOMIZER W OPTIONAL DIFFERENTIAL ENTHALPY SENSORS 182A 183A 182A 183A GREEN Installer Note Please Check Installed Option ...

Page 11: ...hen Used With BAYECON0101 102 103 104 200 201 203 204 ECONOMIZER W OPTIONAL OUTDOOR ENTHALPY SENSOR GREEN YL BK The manufacturer has a policy of continuous product improvement and it reserves the right to change specifications and design without notice ...

Reviews: