![Trane BAYECON353 Series Installation Instructions Manual Download Page 12](http://html1.mh-extra.com/html/trane/bayecon353-series/bayecon353-series_installation-instructions-manual_1149331012.webp)
12
ACC-SVN203C-EN
Economizer Controller
NOTICE
Equipment Damage!
Electrostatic discharge can short equipment circuitry.
Ensure that you are properly grounded before handling
the sensor.
Notes:
•
Upon power up or after a power outage or brownout
(or if power goes below 18 Vac), the controller begins
a
5 minute
power up delay before enabling
mechanical cooling. Power must be above 18 VAC for
the delay to become functional.
•
The controller will be in “Setup” mode for the first
60
minutes
after powered. If a sensor for outside air or
one of the Sylk Bus devices (sensor or actuator) is
disconnected during the set up mode, the controller
will not alarm that failure. The mixed air temperature
sensor is a system “critical sensor”; if it is removed
during the set up mode the controller will alarm. After
60 minutes the controller will change to “Operation”
mode and all components removed or failed will alarm
in the operation mode.
•
The terminals on MAT, OAT and S-BUS sensors are
polarity insensitive.
Controller User Interface and
Keypad
The user interface consists of an LCD display and a 4-
button keypad on the front of the economizer module. The
LCD is a 16 character by 2 line dot matrix display.
Figure 16.
Controller user interface and keypad
Table 2.
Economizer module - left hand terminal blocks
Label
Type
Description
Top Left Terminal Block
MAT
MAT
20k NTC and
COM
Mixed Air Temperature Sensor (polarity
insensitive connection)
OAT
OAT
20k NTC and
COM
Outdoor Air Temperature Sensor (polarity
insensitive connection)
S-BUS
S-BUS
SYLK Bus
Sylk Bus Sensor (polarity insensitive
connection)
Bottom Left Terminal Block
IAQ 2-10
2-10 Vdc
Air Quality Sensor Input (e.g. CO
2
sensor)
IAQ COM
COM
Air Quality Sensor Common
IAQ 24V
24 Vac
Air Quality Sensor 24 Vac Source
ACT 2-10
2-10 Vdc
Damper Actuator Output (2-10 Vdc)
ACT COM
COM
Damper Actuator Output Common
ACT 24V
24 Vac
Damper Actuator 24 Vac Source
n/a
The last pin is not used
Table 3.
Economizer module - right hand terminal
blocks
Label
Type
Description
Top Right Terminal Block
n/a
The first pin is not used
AUX2 I
24 Vac IN
Shut Down (SD) or Heat (W)
Conventional only or Heat Pump
Changeover (O/B) in Heat Pump mode
OCC
24 Vac IN
Occupied / Unoccupied Input
E-GND
EGND
Earth Ground - System Required
EXH1
24 Vac OUT Exhaust Fan 1 Output
AUX1 O
24 Vac OUT
Programmable:
Exhaust fan 2 Output or ERV or System
Alarm output
Bottom Right Terminal Block
Y2-I
24 Vac IN
Y2 in - Cooling Stage 2 Input from Space
Thermostat
Y2-O
24 Vac OUT
Y2 out - Cooling Stage 2 Output to Stage
2 Mechanical Cooling
Y1-I
24 Vac IN
Y1 in - Cooling Stage 1 Input from Space
Thermostat
Y1-O
24 Vac OUT
Y1 out - Cooling Stage 1 Output to Stage
1 Mechanical Cooling
C
COM
24 Vac Common
R
24 Vac
24 Vac Power (Hot)
Scroll
(up/down)
Buttons
Select (Enter)
Button
Menu Up
(Exit)
Button
2 Line LCD