WSHP-SVX015C-EN
41
3. Do not run the electrical wires transporting DC
signals in or around conduit housing high voltage
wires.
Table 6. DC conductors zone sensor module wiring
Distance from Unit to
Control
Recommended Wire
Size
0 - 150 feet (0 - 45.7 m)
22 gauge (0.33 mm2)
151 - 240 feet (46 - 73.1 m)
20 gauge (0.50 mm2)
241 -385 feet (73.5 - 117.3 m)
18 gauge (0.75 mm2)
386 - 610 feet (117.7 - 185.9 m)
16 gauge (1.3 mm2)
611 - 970 feet (186.2 - 295.7 m)
14 gauge (2.0 mm2)
Figure 44.
Reliatel
™
™
conventional thermostat field
wiring diagram
RTRM