Operating Pressures
28
WSHP-SVX10H-EN
Water Pressure Drop
The following table should be used to define feet of head/
pressure drop.
Note:
To calculate feet of head, when using gauges that read
in PSIG, multiply PSI by 2.31.
Table 18. Water pressure drops (WPD) in feet of head
Unit
GPM
Cooling
Heating
EWT °F
Ft. Head
Pressure
EWT °F
Ft. Head
Pressure
GET*009
1.1
77
1.8
55
2.1
GET*009
2.1
77
5.3
55
6.1
GET*009
2.6
77
7.9
55
9.0
GET*012
1.5
77
3.9
55
5.2
GET*012
2.8
77
11.9
55
15.3
GET*012
3.5
77
17.6
55
22.5
GET*015
1.9
77
3.9
55
4.7
GET*015
3.5
77
11.8
55
13.8
GET*015
4.4
77
17.5
55
20.3
GET*018
2.3
77
3.2
55
3.9
GET*018
4.2
77
9.7
55
11.5
GET*018
5.3
77
14.3
55
17.0
GET*024
3.0
77
2.9
55
3.6
GET*024
5.6
77
8.6
55
10.5
GET*024
7.0
77
12.8
55
15.4
GET*036
4.5
77
4.7
55
5.7
GET*036
8.4
77
14.2
55
16.9
GET*036
10.5
77
21.1
55
24.9
Water Volume
Table 19. Model flow option GPM press drop (feet)
GET*009
Low
1.0
5.5
GET*009
High
1.5
6.6
GET*012
Low
1.5
6.6
GET*012
High
2.0
8.1
GET*015
Low
2.5
10.1
GET*015
High
3.5
15.4
GET*018
Low
3.0
12.6
GET*018
High
4.0
18.7
GET*024
Low
4.0
7.6
GET*024
High
6.0
11.4
GET*036
Low
6.0
11.4
GET*036
High
8.0
16.7
The following table is provided for use in calculating glycol
requirements for the unit.
Table 20. Water volume
Unit
Water Side Volume
Cubic In.
Water Side Volume
Cubic Ft.
Water Side
Volume Gallons
GET*009
18.7
0.011
0.081
GET*012
24.9
0.014
0.108
GET*015
37.2
0.022
0.161
GET*018
40.9
0.024
0.177
GET*024
62.6
0.036
0.271
GET*036
85.0
0.049
0.368
Flow Checks
For the operating temperature drop (heating) and rise
(cooling), refer to
temperature change. Depending on the unit size, entering
water temperature and water flow rate, the cooling
temperature rise is from 8°F - 16°F. Based on the same criteria
for heating, the temperature drop is from 2°F - 13°F.
Pressure
Using the P/T ports and one 0-60 psi pressure gauge with the
P/T port adapter, measure the pressure difference between
the water-in and water-out connections. Compare the
pressure differential to
to determine flow.
GET*036
95
7.10
145-167
355-452
11-14
15-19
—
—
—
—
GET*036
95
9.10
145-167
347-441
8-11
15-19
—
—
—
—
Table 17. Operating pressures (continued)
Model
Entering
Water Temp
°F
Water Flow
GPM
Operating Data
Cooling
Heating
Suction
Pressure,
PSIG
Discharge
Pressure,
PSIG
Water Temp
Rise °F
Air Temp
Drop °F DB
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Water Temp
Drop °F
Air Temp
Rise °F DB
Table 19. Model flow option GPM press drop (feet)