background image

32

 WSHP-SVX11E-EN

Troubleshooting

WARNING

Hazardous Service Procedures!

Failure to follow all precautions in this manual and on 
the tags, stickers, and labels could result in death or 
serious injury.

Technicians, in order to protect themselves from 
potential electrical, mechanical, and chemical hazards, 
MUST follow precautions in this manual and on the 
tags, stickers, and labels, as well as the following 
instructions: Unless specified otherwise, disconnect all 
electrical power including remote disconnect and 
discharge all energy storing devices such as capacitors 
before servicing. Follow proper lockout/tagout 
procedures to ensure the power can not be 
inadvertently energized. When necessary to work with 
live electrical components, have a qualified licensed 
electrician or other individual who has been trained in 
handling live electrical components perform these 
tasks.

Deluxe 24V Controls

Troubleshooting units which contain the deluxe 24V 
control option may be made easy by using the three LEDs 
(light emitting diodes). These LEDs are provided for 
indicating the operating mode of the controller. The LEDs 
are intended to aid in troubleshooting. The LEDs are 
labeled on the circuit board with numbers as referenced in 

Table 10, p. 32

.

Table 10. Diagnostic LEDs

Color: Green

Color: Red

Controller Mode

LED1

LED2

LED3

OFF

OFF

OFF

Control OFF

ON

OFF

OFF

Normal/Compressor OFF

ON

OFF

FLASH

Anti-short cycle

ON

OFF

ON

Normal/Compressor ON

FLASH

ON

OFF

Brownout Condition

ON

FLASH

ON

Soft Lockout (low pressure)

ON

FLASH

FLASH

Soft Lockout (high pressure)

ON

ON

ON

Manual Lockout (low pressure)

ON

ON

FLASH

Manual Lockout (high pressure)

ON

FLASH

OFF

Manual Lockout (condensate overflow)

ON

ON

OFF

Compressor Disable

Table 11. Troubleshooting table  

Problem

Heating Cooling

Cause

Correction

No response to any

thermostat setting

X

X

Main power off

Check fuses

X

X

Defective control transformer

Replace

X

X

Broken or loose connection

Repair

X

X

Defective thermostat

Replace

X

X

Transformer

Reset Transformer

Unit short cycles

X

X

Thermostat or sensor improperly located

Relocate

Blower runs, but compressor does not

X

X

Defective compressor overload

Replace (if external)

X

X

Defective compressor contactor

Replace

X

X

Supply Voltage too low

Correct

X

X

Defective compressor capacitor

Replace

X

X

Defective windings

Replace

X

X

Limit switches open

Check cause/Replace or repair

Summary of Contents for Axiom GECE 006

Page 1: ...ould install and service the equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Im...

Page 2: ...ent that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the...

Page 3: ...ede these policies Non Trane personnel should always follow local regulations Introduction WSHP SVX11E EN 3 Copyright This document and the information in it are the property of Trane and may not be u...

Page 4: ...cal Data 23 Pre Start Checklist 25 Start Up 26 Initial Unit Start up 26 Start Up Checklist and Log 26 Operating Pressures 26 Water Pressure Drop 29 Water Volume 30 Maintenance 31 Preventive Maintenanc...

Page 5: ...rflow Sensor 3 Condensate Overflow and Filter Maintenance Timer 6 Condensate Overflow and Fan Status J Condensate Overflow Sensor Fan Status and Filter Maintenance Timer Digit 20 Temperature Sensor 0...

Page 6: ...terior insulation it should be removed and replaced prior to operating the system NOTICE Microbial Growth Failure to follow instructions below could result in odors and damage to the equipment and bui...

Page 7: ...tons 60 Hz 0 5 to 1 25 tons 50 Hz cabinet RH piping connection 48 12 CONTROL ACCESS PANEL 2 1 2 6 LONG 5 8 I D PLASTIC HOSE PROVIDED FOR CONDENSATE CONNECTION 3 3 8 2 3 4 5 5 8 33 6 3 3 4 4 7 8 1 3 4...

Page 8: ...OLES FILTER ACCESS 33 3 3 4 FOR CONDENSATE 2 1 2 CONNECTION 2 3 4 3 3 8 PLASTIC HOSE 6 LONG 6 1 3 4 UNIT CONTROLLER 4 3 8 21 7 8 11 1 4 DRAIN CONN 625 I D 10 7 3 8 23 3 4 22 3 8 25 625 ODS WATER IN CO...

Page 9: ...Figure 5 GEC 0 5 to 1 5 tons 60 Hz 0 5 to 1 25 tons 50 Hz subbase RH 4 3 4 48 9 1 4 33 6 15 9 5 8 3 4 11 1 4 3 3 4 3 4 TOP VIEW ISO VIEW Unit Dimensions WSHP SVX11E EN 9...

Page 10: ...Figure 6 GEC 0 5 to 1 5 tons 60 Hz 0 5 to 1 25 tons 50 Hz subbase LH 4 3 4 48 13 1 4 33 6 15 9 5 8 3 4 11 1 4 3 3 4 3 4 TOP VIEW ISO VIEW Unit Dimensions 10 WSHP SVX11E EN...

Page 11: ...3 4 22 3 8 11 1 4 25 PLASTIC DRAIN CONN 625 I D WATER IN CONN 625 O D S WATER OUT CONN 625 O D S 16 3 8 6 3 8 RECEPTACLE BOX UNIT CONTROLLER 33 3 3 4 FILTER ACCESS 2 1 2 6 LONG PLASTIC HOSE FOR CONDEN...

Page 12: ...4 3 8 21 7 8 11 1 4 PLASTIC DRAIN CONN 625 I D 7 3 8 23 3 4 22 3 8 25 WATER OUT 625 ODS WATER IN CONN 625 ODS 7 8 6 LONG PLASTIC HOSE FOR CONDENSATE CONN 33 3 3 4 2 1 2 18 1 2 17 3 4 FILTER ACCESS 6 1...

Page 13: ...Figure 9 GEC 0 5 to 1 5 tons 60 Hz 0 5 to 1 25 tons 50 Hz subbase RH extended length 19 3 4 63 9 1 4 33 6 15 9 5 8 3 4 11 1 4 3 3 4 3 4 TOP VIEW ISO VIEW Unit Dimensions WSHP SVX11E EN 13...

Page 14: ...Figure 10 GEC 0 5 to 1 5 tons 60 Hz 0 5 to 1 25 tons 50 Hz subbase LH extended length 19 3 4 63 28 33 6 15 9 5 8 3 4 11 1 4 3 3 4 3 4 TOP VIEW ISO VIEW Unit Dimensions 14 WSHP SVX11E EN...

Page 15: ...7 8 6 1 4 RECEPTACLE BOX PIPE ELECTRICAL FIELD HOOK UP 47 1 4 5 15 3 4 4 25 WALL SLEEVE MOUNTING HOLES 4 7 8 34 3 4 1 3 4 RETURN AIR OPENING 1 1 4 6 LONG PLASTIC HOSE PROVIDED FOR CONDENSATE CONNECTI...

Page 16: ...BI DIRECTIONAL GRILLES 12 34 3 4 1 3 4 1 1 4 6 LONG PLASTIC HOSE PROVIDED FOR CONDENSATE CONNECTION 1 1 2 4 7 8 2 3 4 3 3 8 CONTROL ACCESS PANEL 4 3 8 19 3 8 11 1 4 10 3 8 4 7 8 21 1 4 19 7 8 22 1 2 6...

Page 17: ...E TERMINAL STRIP 6 1 4 10 1 2 AIR SIDE SERVICE PANEL 20 1 4 REFRIGERATION SERVICE PANEL 625ODS WATER IN 2 1 8 1 1 2 6 LONG 625 I D PLASTIC HOSE PROVIDE FOR CONDENSATE CONNECTION WATER OUT 625 ODS 42 1...

Page 18: ...4 5 8 2 10 3 8 7 5 8 WATER OUT 625 ODS 2 3 8 1 3 8 2 1 8 CONDENSATE CONNECTION PLASTIC HOSE PROVIDE FOR 6 0 LONG 625 I D 625 ODS WATER IN AIR SIDE SERVICE PANEL REFRIGERATION SERVICE PANEL HIGH VOLTAG...

Page 19: ...to 1 5 tons Unit Size Shipping Weight with Pallet Shipping Weight without Pallet GEC Unit Weight lbs Chassis Weight lbs Unit Weight lbs Chassis Weight lbs 006 218 170 188 140 009 219 171 189 141 012 2...

Page 20: ...outside air cut out Level the unit per plan requirements Mark the four mounting locations for wall sleeve mounting to the wall The dimensions should fall in line with Step 5 4 Removethechassisfromthe...

Page 21: ...o condensate trapping is necessary However it is necessary for the condensate to run in a downward motion to allow gravity to properly drain the system The unit drain connection is 5 8 in I D or 7 8 i...

Page 22: ...Installation 22 WSHP SVX11E EN 19 For units with the factory provided receptacle box options the receptacle plug may now be connected to the electrical outlet...

Page 23: ...0 GEC009 220 240 50 1 13 2 5 3 23 0 1 7 4 0 70 1 12 1 16 5 20 3 0 12 5 GEC009 220 240 50 1 17 4 5 3 23 0 1 7 4 0 70 1 12 1 21 7 25 4 0 16 67 GEC009 265 60 1 3 5 2 8 13 0 1 3 7 0 70 1 30 1 4 2 15 0 0...

Page 24: ...rols Deluxe with Reheat 75 VA Deluxe with Electric Heat 75 VA UC400 B 75 VA ZN524 75 VA x ON a Controller 6 0 6 0 12 5 19 5 1K1 Compressor Contactor 5 5 5 5 5 5 5 5 X 1K2 Fan Relay 9 5 9 5 9 5 9 5 2L1...

Page 25: ...Guide Is vibration isolation provided i e unit isolation pad hose kits Is unit serviceable Allow a 12 inch clearance at the unit front for serviceability Are the low high side pressure temperature cap...

Page 26: ...mooth with no frost observed in the refrigeration circuit 10 Check the heating refrigerant pressures against values in Table 4 p 27 11 Set the thermostat to maintain the desired space temperature 12 I...

Page 27: ...12 15 19 24 GEC 006 60 Hz 95 1 8 148 170 379 483 9 12 19 25 GEC 009 60 Hz GEC 006 50 Hz 35 1 7 93 107 258 328 10 12 21 26 GEC 009 60 Hz GEC 006 50 Hz 35 2 1 93 107 258 329 8 10 21 27 GEC 009 60 Hz GE...

Page 28: ...45 2 8 144 165 178 227 11 14 23 29 105 121 277 353 11 14 24 30 GEC 015 60 Hz GEC 012 50 Hz 45 3 5 144 165 172 219 9 12 23 29 108 124 279 355 9 11 24 31 GEC 015 60 Hz GEC 012 50 Hz 55 2 8 145 167 206 2...

Page 29: ...2 172 219 9 11 23 29 110 127 289 368 8 11 24 31 GEC 018 60 Hz GEC 015 50 Hz 55 3 4 141 163 206 262 11 14 23 29 126 145 302 385 11 14 27 34 GEC 018 60 Hz GEC 015 50 Hz 55 4 2 141 162 200 254 9 11 23 29...

Page 30: ...in calculating glycol requirements for the unit Table 7 Water volume for GEC units Unit Size 60 Hz Unit Size 50 Hz WaterSide Volume in3 Water Side Volume ft3 WaterSide Volume gallons 006 009 006 13 6...

Page 31: ...ring the unit heat exchanger and to ensure a clean system For units on well water it is important to check the cleanliness of the water to refrigerant heat exchanger Should it become contaminated with...

Page 32: ...of the controller The LEDs are intended to aid in troubleshooting The LEDs are labeled on the circuit board with numbers as referenced in Table 10 p 32 Table 10 Diagnostic LEDs Color Green Color Red C...

Page 33: ...se temperature X Inadequate air flow Check clean blower and coil X Dirty filter Clean replace X X Overcharged with refrigerant Decrease charge X X Defective pressure switch Check or replace High head...

Page 34: ...34 WSHP SVX11E EN Wiring Diagrams Figure 15 Deluxe 24V controls...

Page 35: ...Figure 16 Tracer ZN524 Wiring Diagrams WSHP SVX11E EN 35...

Page 36: ...Figure 17 Tracer UC400 B 208V 60 Hz 1pH Wiring Diagrams 36 WSHP SVX11E EN...

Page 37: ...Figure 18 Tracer UC400 B 208V 60 Hz 1pH with hot gas reheat Wiring Diagrams WSHP SVX11E EN 37...

Page 38: ...ment There is a standard five year compressor parts warranty Extended Warranty The optional extended warranty is a second through fifth yearwarranty The time startsatthe endofstandard1 year coverage t...

Page 39: ......

Page 40: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Reviews: