Start-Up
WSHP-SVX11E-EN
29
Water Pressure Drop
should be used to define
feet of head/pressure drop. Please note the feet of
pressure (ft/head) provided is at AHRI/ISO standard.
Note:
To calculate feet of head, when using gauges that
read in PSIG, multiply PSI by 2.31.
Table 5.
Cooling water pressure drops (WPD) in feet of
head for GEC* units - 0.5 to 1.5 tons
Unit Size
(60 Hz)
Unit Size
(50 Hz)
EWT °F
GPM
Ft.
Pressure
006
—
86
1.8
3.6
009
006
86
2.1
4.3
012
009
86
2.8
9.3
015
012
86
3.5
13.1
018
015
86
4.2
9.1
Table 6.
Heating water pressure drops (WPD) in feet of
head for GEC* units - 0.5 to 1.5 tons
Unit Size
(60 Hz)
Unit Size
(50 Hz)
EWT °F
GPM
Ft.
Pressure
006
—
68
1.8
4.3
009
006
68
2.1
5.0
012
009
68
2.8
10.7
015
012
68
3.5
14.9
018
015
68
4.2
10.2
GEC*018 (60 Hz)
GEC*015 (50 Hz)
35°
3.4
—
—
—
—
92-106
274-349
9-12
21-26
GEC*018 (60 Hz)
GEC*015 (50 Hz)
35°
4.2
—
—
—
—
92-106
274-349
7-9
21-27
GEC*018 (60 Hz)
GEC*015 (50 Hz)
45°
3.4
141-162
178-226
11-14
23-29
108-124
288-367
10-13
24-30
GEC*018 (60 Hz)
GEC*015 (50 Hz)
45°
4.2
141-162
172-219
9-11
23-29
110-127
289-368
8-11
24-31
GEC*018 (60 Hz)
GEC*015 (50 Hz)
55°
3.4
141-163
206-262
11-14
23-29
126-145
302-385
11-14
27-34
GEC*018 (60 Hz)
GEC*015 (50 Hz)
55°
4.2
141-162
200-254
9-11
23-29
129-148
305-388
9-12
27-35
GEC*018 (60 Hz)
GEC*015 (50 Hz)
68°
3.4
143-164
249-317
11-14
22-28
152-175
325-413
13-16
31-39
GEC*018 (60 Hz)
GEC*015 (50 Hz)
68°
4.2
143-164
242-308
9-11
22-28
156-180
326-415
10-13
32-40
GEC*018 (60 Hz)
GEC*015 (50 Hz)
75°
3.4
143-165
275-350
11-14
21-27
169-194
336-428
13-17
33-42
GEC*018 (60 Hz)
GEC*015 (50 Hz)
75°
4.2
143-165
267-340
9-11
21-27
173-199
339-432
11-14
34-43
GEC*018 (60 Hz)
GEC*015 (50 Hz)
86°
3.4
145-167
320-407
11-14
20-26
196-225
357-454
15-19
36-46
GEC*018 (60 Hz)
GEC*015 (50 Hz)
86°
4.2
145-167
312-397
9-11
20-26
202-232
360-458
12-15
37-47
GEC*018 (60 Hz)
GEC*015 (50 Hz)
95°
3.4
146-168
362-461
11-14
19-24
—
—
—
—
GEC*018 (60 Hz)
GEC*015 (50 Hz)
95°
4.2
146-168
353-450
9-11
19-25
—
—
—
—
Table 4.
Operating pressures in cooling/heating for GEC* units (continued)
Operating Data
Model GEC*
Entering
Water
Temp
(°F)
Water
Flow
(GPM)
Cooling
Heating
Suction
Pressure,
(psig)
Discharge
Pressure,
(psig)
Water
Temp
Rise
(°F)
Air Temp
Drop
(°F DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Drop
(°F)
Air Temp
Rise
(°F DB)
Summary of Contents for Axiom GECE 006
Page 34: ...34 WSHP SVX11E EN Wiring Diagrams Figure 15 Deluxe 24V controls...
Page 35: ...Figure 16 Tracer ZN524 Wiring Diagrams WSHP SVX11E EN 35...
Page 36: ...Figure 17 Tracer UC400 B 208V 60 Hz 1pH Wiring Diagrams 36 WSHP SVX11E EN...
Page 37: ...Figure 18 Tracer UC400 B 208V 60 Hz 1pH with hot gas reheat Wiring Diagrams WSHP SVX11E EN 37...
Page 39: ......