13
CG-SVX06F-GB
Minimal installation water
content
The water volume is an important
parameter because it allows a
stable chilled water temperature and
avoids short cycle operation of the
compressors.
Parameters which influence
the water temperature
stability
• Water loop volume
• Load fluctuation
• Number of capacity steps
• Compressors rotation
• Dead band (adjusted on chiller
controller)
• Minimum time between 2 starts of
a compressor
Minimum water volume for
a comfort application
For comfort application we can
allow water temperature fluctuation
at part load. The parameter to
take into account is the minimum
operating time of the compressor.
In order to avoid lubrication problem
on a scroll compressor it must run
at least 2 minutes (120 seconds)
before it stops.
The following table gives the
minimal installation water content
recommended according to all these
parameters.
Installation
Table 2 - Minimal water content
Notes
(1) Minimum water loop volume in order to obtain m/- 1°C chilled water temperature fluctuation vs. Chilled
water set-point
(2) Minimum water loop volume in order to obtain m/- 1.5°C chilled water temperature fluctuation vs.
Chilled water set-point
(3) Minimum water loop volume in order to obtain m/- 2°C chilled water temperature fluctuation vs. Chilled
water set-point
This table is estimated with
- Condenser : Water 30°/35°C
- Evaporator : Water 12°/7°C
Confort Application
Process cooling Application
2°C Dead
band (1)
3°C Dead
band (2)
4°C Dead
band (3)
2°C Dead
band (1)
3°C Dead
band (2)
4°C Dead
band (3)
CGWN - CCUN 205
660 l
440 l
330 l
1160 l
730 l
530 l
CGWN - CCUN 206
670 l
450 l
340 l
1160 l
740 l
540 l
CGWN - CCUN 207
650 l
440 l
330 l
1100 l
710 l
520 l
CGWN - CCUN 208
880 l
580 l
440 l
1520 l
960 l
710 l
CGWN - CCUN 209
1060 l
700 l
530 l
1860 l
1170 l
860 l
CGWN - CCUN 210
1080 l
720 l
540 l
1870 l
1190 l
870 l
CGWN - CCUN 211
1260 l
840 l
630 l
2220 l
1400 l
1020 l
CGWN - CCUN 212
1260 l
840 l
630 l
2170 l
1380 l
1010 l
CGWN - CCUN 213
1050 l
700 l
530 l
1760 l
1130 l
830 l
CGWN - CCUN 214
1270 l
850 l
640 l
2150 l
1370 l
1010 l
CGWN - CCUN 215
1240 l
820 l
620 l
2060 l
1330 l
980 l