background image

18-CD19D8-18

35

Installer’s Guide

Thermostat call for heat (1-stage Thermostat)

W1/W2 (jumpered) thermostat contacts close signaling a call
for heat.  1st stage sequence of operation remains the same
as above.  2nd stage heat will energize after the stage delay
timer (field selectable at .5, 5, 10 or 15 minutes) has expired.

Thermostat satisfied:

W1/W2 (jumpered) contacts open signaling the control
module to close the gas valve. The induced draft blower is
switched to low speed and de-energized after the post purge
timer has expired.  The indoor blower motor will continue to
operate after the flames are extinguished and then is
switched to low heat speed for the FAN-OFF period.

CONTROL AND SAFETY SWITCH ADJUSTMENTS

LIMIT SWITCH CHECK OUT

The limit switch is a safety device designed to close the gas
valve should the furnace become overheated.  Since proper
operation of this switch is important to the safety of the unit, it

must be checked out on initial start up by the installer.

To check for proper operation of the limit switches, set the
thermostat to a temperature higher than the indicated
temperature to bring on the gas valve.  Restrict the airflow
by blocking the return air (disconnecting the indoor blower
may trip the inducer limit).  When the furnace reaches the
maximum outlet temperature as shown on the rating plate,
the burners must shut off.  If they do not shut off after a
reasonable time and overheating is evident, a faulty limit
switch is probable and the limit switch must be replaced.
After checking the operation of the limit control, be sure to
remove the paper or cardboard from the return air inlet. Refer
to Service Facts for additional instructions.

NOTE TO INSTALLER

Review the following warnings with the owner. Review con-
tents of USER’S INFORMATION MANUAL with the owner.

AIRFLOW ADJUSTMENT

Check inlet and outlet air temperatures to make sure they
are within the ranges specified on the furnace rating name-
plate. If the airflow needs to be increased or decreased, see
the wiring diagram for information on changing the speed of
the blower motor.

WARNING

!

Disconnect power to the unit before removing the blower
door. Allow a minimum of 10 seconds for IFC power supply
to drain to 0 volts. Failure to follow this warning could
result in property damage, personal injury or death.

This unit is equipped with a blower door switch which cuts
power to the blower and gas valve causing shutdown when
the door is removed. Operation with the door removed or ajar
can permit the escape of dangerous fumes. All panels must be
securely closed at all times for safe operation of the furnace.

INDOOR BLOWER TIMING

Heating: 

The integrated furnace control module controls the

indoor blower. The blower start is fixed at 45 seconds after
ignition. The FAN-OFF period is field selectable by dip
switches SW-2, #1 and #2 at 60, 100, 140, or 180 seconds.
The factory setting is 100 seconds.

W1-W2 stage delay (jumpered together) is field selectable by
dip switch SW-1, #1 and #2 at .5, 5, 10 or 15 minutes.  The
factory setting is 10 minutes. (See wiring diagram).

Cooling: 

The fan delay off period is factory set at 0 seconds.

The option for 80 second delay off is field selectable by dip
switch SW-2, #3 (See wiring diagram).

ROOM AIR THERMOSTAT
HEAT ANTICIPATOR ADJUSTMENT

Set the thermostat heat anticipator according to the current
flow measured, or the settings found in the notes on the
furnace wiring diagram (found in the SERVICE FACTS or
inside the furnace casing).

INSTRUCTIONS TO THE OWNERS

In the event that electrical, fuel, or mechanical failures
occur, the owner should immediately turn the gas
supply off at the manual gas valve, located in the
burner compartment. Also turn off electrical power to
the furnace and contact the service agency designated
by your dealer.

BURNER BOX TEMPERATURE LIMIT DEVICE

All models are equipped with a manual reset temperature
limit located on the burner box.  In case of excessive tempera-
ture, the limit will open and cause the circuit to open which
shuts off all flow of gas.

Summary of Contents for ADX2B060A9362A

Page 1: ...ler s Guide __First letter may be A or T Upflow Horizontal Downflow Horizontal Gas Fired Direct Vent 2 Stage Condensing Furnaces with Variable Speed Inducer A341624P03 UX2B060A9362A UX2B080A9422A UX2C...

Page 2: ...result in serious injury death or property damage Improper servicing could result in dangerous operation serious injury death or property damage CARBON MONOXIDE POISONING HAZARD Failure to follow the...

Page 3: ...cial venting systems which must be gas tight and water tight These Category IV Direct Vent furnaces are approved for installa tion in Manufactured Mobile housing when used with BAYMFGH001A LOCATION AN...

Page 4: ...B080A9422A 17 1 2 2 1 4 16 1 4 16 7 1 2 2 UX2C100A9482A 21 2 1 2 19 3 4 19 1 2 9 3 UX2D120A9602A 24 1 2 2 15 16 23 1 4 23 10 3 Prefix May Be A or T Notes 1 UX2D120A9602A Requires 3 Diameter Vent Pipe...

Page 5: ...See Note 1 DIM A DIM B DIM C DIM D DX2B060A9362A DX2B080A9422A 17 1 2 2 1 4 16 1 4 16 DX2C100A9482A 21 2 1 2 19 3 4 19 1 2 DX2D120A9602A 24 1 2 2 15 16 23 1 4 23 Prefix May Be A or T Notes 1 Diameter...

Page 6: ...1234567890121234567890123456 123456789012345678901234567890121234567890123456 123456789012345678901234567890121234567890123456 123456789012345678901234567890121234567890123456 123456789012345678901234...

Page 7: ...for combustion Permanent wave solutions Chlorinated waxes and cleaners Chlorine based swimming pool chemicals Water softening chemicals Deicing salts or chemicals Carbon Tetrachloride Halogen type re...

Page 8: ...turn air grille Although these furnaces are designed with large blowers operating at moderate speeds any blower moving a high volume of air will produce audible noise which could be objectionable when...

Page 9: ...of the furnace is accessible it is recommended that both supply and return air plenums are removable 8 When replacing a furnace old duct work should be cleaned out Thin cloths should be placed over t...

Page 10: ...inserted into the bottom of the furnace The retaining screw pin on each side inserts into engagement holes at the bottom of the furnace cabinet side See Figures 13 14 16 NOTE Remove the bottom front c...

Page 11: ...side of the furnace Confirm that the upper retaining pin screw locks into the engagement hole in the blower deck and the lower pin screw rests against the side of the bottom panel See Figures 14 15 17...

Page 12: ...e cut to fit the unit depending on the location of the return air filter A score line and the words CUT HERE are located on the end of the filter If your application requires cutting the filter do so...

Page 13: ...m 2 Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion or other deficiencies which could cause an unsafe condi...

Page 14: ...the building NOTE It is recommended that the first joints from the furnace be connected and sealed with high temperature RTV This will enable the pipes to be removed later without cutting Be sure to p...

Page 15: ...assifications covered in ASTM D1784 Deflection Temps Under Load 264 PSI Allowable temperatures based on classifications covered in ASTM D3965 Deflection Temps Under Load 264 PSI NOTE Follow venting in...

Page 16: ...ote 6 below for exception The inlet pipe can be of a larger diameter but never smaller than the vent pipe 3 MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED THE LENGTH SHOWN IS NOT A COMBINED TOTAL IT IS THE...

Page 17: ...MUM j ELBOW AND TEE MUST BE AS CLOSE TOGETHER AS POSSIBLE NOTE VENT AND INLET MUST BE SUPPORTED AT A MAXIMUM OF 3 INTERVALS BAYAIR30AVENTA TEE BAYVENT200B k 40 UPFLOW OR DOWNFLOW MODELS SEE VENTING TA...

Page 18: ...osen to meet the requirements of Figure 39 for either direct or nondirect vent applications PITCH Venting through the wall must maintain 1 4 per foot pitched upward to insure that condensate drains ba...

Page 19: ...RT FIELD SUPPLIED VENT BAYAIR30AVENTA VERTICAL v b n GALVANIZED FIRESTOP SHOULD BE FABRICATED WITH 3 7 8 DIA HOLE FOR SUPPORT FLANGE 12 x 12 PANEL OR 12 DIA MIN VENTING THROUGH CEILING CEILING SUPPORT...

Page 20: ...ed for another gas appliance venting area must be sufficient to vent that appliance and that appliance must be connected to chimney with separate entry openings IMPORTANT The single wall flue pipe joi...

Page 21: ...ight 15 feet 4 5 m above the meter regulator assembly I Clearance to service regulator vent outlet 3 feet 91 cm J Clearance to nonmechanical air supply inlet to building or the combustion air inlet to...

Page 22: ...o permanently closed window D Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet 61 cm from the center line of the terminal E Clearance to unvent...

Page 23: ...th the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed 2 APPROVED CARBON MONOXIDE DETECTORS Each...

Page 24: ...all excess tubing to avoid kinks Downflow furnace The furnace is shipped with the left side drainage setup To change the right side drain remove the drain lines from the trap rotate the trap 180 so it...

Page 25: ...causing slippery conditions that could lead to personal injury Excessive draining of condensate may cause saturated ground conditions that may result in damage to plants NOTE Use 1 2 or larger PVC or...

Page 26: ...JUMPER W1 TO W2 2ND STAGE WILL FIRE 10 MINUTES AFTER 1ST SEE NOTE 8 B C B C TO 115 V 1 PH 60 HZ POWER SUPPLY PER LOCAL CODES HUM SEE NOTE 5 EAC SEE NOTE 5 FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE 1 ST...

Page 27: ...STAGE COOLING USING A 2 STAGE HEATING 1 STAGE COOLING THERMOSTAT OUTDOOR SECTION WITHOUT TRANSFORMER OUTDOOR UNIT NO TRANSFORMER SEE NOTE 6 From Dwg B342019 Rev 0 SEE NOTE 8 FIELD ADDED JUMPER NOTE 9...

Page 28: ...SEE NOTE 4 ISOLATION RELAY SEE NOTE 4 JUMPER W1 TO W2 ON BOTH UNITS 2ND STAGE WILL FIRE 10 MINUTES AFTER 1ST B C B C B C From Dwg 21B341336 Rev 2 TWIN TWIN TWINNING CONNECTION DIAGRAM FOR TWINNING UX...

Page 29: ...ould result in carbon monoxide poisoning or death ELECTRICAL CONNECTIONS Make wiring connections to the unit as indicated on enclosed wiring diagram As with all gas appliances using electrical power t...

Page 30: ...FROM EITHER SIDE Typical UPFLOW Furnace in horizontal configuration shown AUTOMATIC GAS VALVE WITH MANUAL SHUT OFF Q UPFLOW MAY BE LEFT OR RIGHT HAND GAS PIPING AUTOMATIC GAS VALVE WITH MANUAL SHUT OF...

Page 31: ...ressure to the gas valve for natural gas is 13 8 W C Minimum pressure is 5 0 W C Maximum pressure to the gas valve for propane is 13 8 W C Minimum pressure is 11 0 W C All gas fittings must be checked...

Page 32: ...regulator cover screw securely 6 Adjust 2nd stage gas heat by removing the high HI adjustment regulator cover screw a To increase outlet pressure turn the regulator adjust screw clockwise b To decrea...

Page 33: ...t be changed LP installations will require an orifice change IMPORTANT Reinstall the propane orifices to the same depth as the orifices supplied with the equipment Installation of this furnace at alti...

Page 34: ...nt freeze up of all water pipes and water receptacles Whenever your house is to be vacant arrange to have someone inspect your house for proper temperature This is very important during freezing weath...

Page 35: ...ified on the furnace rating name plate If the airflow needs to be increased or decreased see the wiring diagram for information on changing the speed of the blower motor WARNING Disconnect power to th...

Page 36: ...flame control module will then recycle the ignition sequence then if ignition is not achieved it will shut off the gas valve and lock out the system 3 POWER FAILURE If there is a power failure during...

Page 37: ...VERY On power up last 4 faults if any will be flashed on the red LED The newest fault detected will flash first and the oldest last There will be a 2 second delay between fault code flashes Solid red...

Page 38: ...improvement it reserves the right to change design and specifications without notice Trane 6200TroupHighway Tyler TX75707 Formoreinformationcontact yourlocaldealer distributor Literature Order Number...

Reviews: