background image

18-CD29D1-11  

15

Installer’s Guide

Furnace

Vent

Air

Inlet

(See Note)

For 

DIRECT VENT APPLICATION: The Furnaces must 

be vented to the exterior of the house and combustion air 

MUST come through the inlet air pipe FROM OUTSIDE 

AIR.

NOTE:

 

BAYVENT200* accessories can be used for inlet 

and outlet terminals when the pipes do not exit the 

structure together.   

For Canadian applications, venting systems must meet 

ULC-S636 requirements.

For 

NONDIRECT VENT APPLICATION: The Furnace 

shall be vented to the exterior of the house, but combustion 

air may enter from the surrounding area as long as 

combustion air requirements are met. (See AIR FOR 

COMBUSTION AND VENTILATION)

FURNACE VENT / INLET PIPE INSTALLATION

There are many different variations of the vent / inlet air 

pipe combination. The vent / inlet air combination used for 

installation of these Furnaces depends on the needs of the 

location. However, these guidelines must be followed:

  1.  The Furnace must vent outside the structure.

  2.  Furnace combustion air requirements must be met for 

non-direct, single pipe applications.

  3.  For direct vent application of these Furnaces, the vent 

pipe and air inlet pipe do not have to exit in the same 

air space. 

However, the longest individual pipe will 

decide the value for the longest allowable equivalent 

vent/ inlet air length as shown in the vent length tables 

on page 17 and 18.

NOTE:  For single pressure zone applications, see Figure 

27. 

EX. 2 —
The inlet air does not have to come from outside the 

structure. Example 2 shows the inlet air, may come from 

the attic if the requirements for combustion air are met as 

shown in the section AIR FOR COMBUSTION AND VENTI-

LATION.

NOTE: If only the flue gas pipe is to the outside of the 

structure, a straight section of pipe (long enough to exit 

the Furnace cabinet) must be attached to the inlet air side 

with an elbow (which is 5 to 10 equiv. ft.) installed on the 

end to prevent dust and debris from falling directly into 

the Furnace.

Example 1

Example 2

Furnace

Air

Inlet

Vent

Attic

Vent

(See Note)

The following are 

EXAMPLES ONLY:

EX. 1  —
Example 1 shows the vent pipe exhausting through the roof 

and the inlet air coming from the interior of the house. The 

inlet air coming from the interior of the house must meet 

combustion requirements for area, etc., as shown in the sec-

tion AIR FOR COMBUSTION AND VENTILATION in this 

Installer’s Guide.

Summary of Contents for ADH1B040A9241A

Page 1: ...operty and is to remain with this unit Please return to service information pack upon completion of work Installer s Guide __First letter may be A or T UPFLOW UH1 UPFLOW HORIZONTAL A341624P13 UH1 UH1B040A9241A UH1B060A9361A UH1B080A9421B UH1C080A9601A UH1C100A9481A UH1D100A9601A UH1D120A9601A DH1B040A9241A DH1B065A9421A DH1C085A9481A DH1D110A9601A DH1 DOWNFLOW DOWNFLOW HORIZONTAL DH1 18 CD29D1 11 ...

Page 2: ... izontal pitch as required in the National Fuel Gas Code ANSI Z223 1 NFPA 54 or the CAN CGA B149 Installation Codes and these instructions Deter mine that there is no blockage or restriction leak age corrosion and other deficiencies which could cause an unsafe condition 3 As far as practical close all building doors and windows and all doors between the space in which the appliance s connected to ...

Page 3: ...e connections must be adhered to In the absence of local codes the installation must conform with latest edition of the National Fuel Gas Code ANSI Z223 1 National Installation Code CAN CGA B149 1 The latest code may be obtained from the American Gas Association Laboratories 400 N Capitol St NW Washington D C 20001 1 800 699 9277 or www aga org These furnaces have been classified as CATEGORY IV fu...

Page 4: ...nstallations This is necessary for proper condensate drainage NOTE On upflow 5 or 6 ton airflow models where the airflow re quirement exceeds 1800 CFM Models will require return air openings and filters on 1 both sides or 2 one side and the bottom or 3 just the bottom WARNING EXPLOSION HAZARD PROPANE GAS IS HEAVIER THAN AIR AND MAY COLLECT IN ANY LOW AREAS OR CONFINED SPAC ES IN ADDITION ODORANT F...

Page 5: ...UPFLOW HORIZONTAL ALL DIMENSIONS ARE IN INCHES 1 UH1D120A9601 UH1C080A9601 UH1C100A9481 AND UH1D100A9601 REQUIRE 3 DIAMETER VENT PIPE 2 DIAMETER OF VENT PIPE MAY BE LIMITED TO 2 1 2 OR 3 ON SOME MODELS AT DIFFERENT ALTITUDES REFER TO THE VENT LENGTH TABLE FOR PROPER APPLICATION ...

Page 6: ... OUTLINE DRAWING DOWNFLOW HORIZONTAL ALL DIMENSIONS ARE IN INCHES MODEL DIM A DIM B DIM C DIM D DH1B040A9241 DH1B065A9421 17 1 2 2 1 4 16 1 4 16 DH1C085A9481 21 2 1 2 19 3 4 19 1 2 DH1D110A9601 24 1 2 2 15 16 23 1 4 23 May be A or T Part numbers can end in A Z ...

Page 7: ...front of the furnace See Figure 3 Clearance Table 1 Line contact is only permissible between lines formed by intersections of the top and two sides of the furnace casing and building joists studs or framing The furnace may be placed horizontally in a crawl space on a pad or other noncombustible material which will raise the unit for sufficient protection from moisture The furnace must be supported...

Page 8: ...as described for confined space Confined spaces are installations with less than 50 cu ft of space per 1000 BTU hr input from all equipment installed as in Figure 7 Air for combustion and ventilation require ments can be supplied from inside the building as in Figure 8 or from the outdoors as in Figure 9 Table 2 MINIMUM AREA IN SQUARE FEET FOR UNCONFINED SPACE INSTALLATIONS FURNACE MAXI MUM BTUH I...

Page 9: ...e installation of air return remote from the living area i e central hall When the furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space con taining the furnace the return air shall also be handled by a duct s sealed to the furnace and terminating outside the space containing the furnace RETURN AIR DUCT CONNECTION NOTE On upflow 5 or 6 ton air...

Page 10: ...ocity type air filters The optional filters may be located within the furnace blower compartment for UPFLOW furnaces in either a BOTTOM or SIDE left side or right side return air inlet Some optional filters may need to be trimmed for side or bottom filter use The furnace and the blower filter rack installation can be seen in Figure 12 The optional furnace filter in the bottom or side configura tio...

Page 11: ...ch side inserts into engage ment holes at the bottom of the furnace cabinet side See Figure 15 e Reinstall the furnace filter in the bottom position by inserting the chamfer end first into the filter rack NOTE Remove the bottom front channel to install the filter rack in the 14 1 2 width cabinet furnaces Filter Rack Furnace Cabinet Side Filter Rack Retaining Screw Pin Engagement Hole For Bottom Re...

Page 12: ...he engagement hole in the blower deck and the lower pin screw rests against the side of the bottom panel See Figures 14 18 20 e Reinstall the furnace filter in the side position by inserting the chamfer end first into the filter rack Airflow p Typical Horizontal Filter Installation TABLE 6 Cabinet Width Left Side Bottom Right Side 14 5 X1 X2 Use Alternate Filter Clips Only 17 5 X X X 21 X X X 24 5...

Page 13: ...ure21 a UNIT SIZE RETURN AIR BOTTOM SIDE 14 1 2 CUT ON LINE DO NOT CUT 17 1 2 DO NOT CUT DO NOT CUT 21 DO NOT CUT CUT ON LINE 24 1 2 DO NOT CUT CUT ON LINE TABLE 7 INSTALLING THE OPTIONAL FILTER The filter may need to be cut to fit the unit depending on the location of the return air filter A score line and the words CUT HERE are located on the end of the filter If your application requires cuttin...

Page 14: ...d lateral of the ex isting venting system as well as quantity and type of bends c Use the appropriate tables in the latest edition of the National Fuel Gas Code ANSI Z223 1 CAN CGA B149 1 Installation Codes or Exhibit J of ANSI Z21 47 CAN CGA 2 3 Standards Exhibit J includes examples and drawings of typical venting systems CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below...

Page 15: ...ent application of these Furnaces the vent pipe and air inlet pipe do not have to exit in the same air space However the longest individual pipe will decide the value for the longest allowable equivalent vent inlet air length as shown in the vent length tables on page 17 and 18 NOTE For single pressure zone applications see Figure 27 EX 2 The inlet air does not have to come from outside the struct...

Page 16: ...lypropelene venting pipes BONDING OF PVC NOTE It is recommended that the first joints from the furnace be connected and sealed with high temperature RTV This will enable the pipes to be removed later without cutting Be sure to properly support these joints Commercially available solvent cement must be used to join the pipe and fittings Follow instructions on the container carefully Procedure for C...

Page 17: ...EXCEEDED THE LENGTH SHOWN IS NOT A COMBINED TOTAL IT IS THE MAXIMUM LENGTH OF EACH Vent or Inlet air pipes 5 One SHORT radius 90 elbow is equivalent to 10 of 4 pipe 10 of 3 pipe or 8 of 2 pipe One LONG radius elbow is equivalent to 6 of 4 pipe 7 of 3 pipe 6 of 2 5 pipe or 5 of 2 pipe Two 45 elbows equal one 90 LONG elbow 6 The termination tee or bend must be included in the total number of elbows ...

Page 18: ...TEM MANUFACTURER S INSTALLATION INSTRUCTIONS FOR APPROPRIATE VENTING DIAMETERS AND EQUIVALENT LENGTHS 2 Minimum vent length for all models 3 horizontal or 3 vertical 3 DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET Except adapters at the top of the furnace If different inlet and vent pipe sizes are used the vent pipe must adhere to the maximum length limit shown i...

Page 19: ...ny is fully open on a minimum of two sides beneath the floor Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer s Installation Instructions Table 14 See Figure 22 Non Direct Vent Terminal Clearances Canadian Installations US Installations A Clearance above grade veranda porch deck or balcony 12 inches 30 cm 12 inches 30 cm B Clearanc...

Page 20: ...exhaust pipe to end of inlet pipe 6 Min 24 Max 6 Min 24 Max ELBOW AND TEE MUST BE AS CLOSE TOGETHER AS POSSIBLE j DO NOT Install return air through the side of furnace cabi net on horizontal applications HORIZONTAL VENTING THROUGH WALL These furnaces may be installed as direct vent as shipped or as nondirect vent Installation must con form to national state and local codes The vent inlet terminals...

Page 21: ...eel vent ing See Figure 30 BAYAIR30AVENTA Sidewall l Shield material to be a minimum of 24 gauge stainless or aluminized sheet metal Minimum dimensions are 12 x12 Shield must be fastened to both inside and outside of wall Use screws or anchor type fasteners suited to the outside or inside wall surfaces NONCOMBUSTIBLE MATERIAL WALL The hole through the wall must be large enough to main tain pitch o...

Page 22: ...P COMBUSTION AIR STRAP FIELD SUPPLIED COMBUSTION AIR VENT ELBOW FIELD SUPPLIED VENT 1 1 2 BAYAIR30AVENTA 3 PIPING 2 2 1 2 or 3 PIPING REDUCING COUPLING FIELD SUPPLIED IF NEEDED SEAL ALL WALL CAVITIES BAYVENT200B c CAUTION The vent for this appliance shall not terminate 1 Over public walkways or 2 Near soffit vents or crawl space vents or other areas where condensate or vapor could create a nuisanc...

Page 23: ...SNOW LEVEL MAXIMUM OF 24 IN ABOVE ROOF VENT COMBUSTION AIR n BAYAIR30AVENTA REMOVE RIBS FROM CAP COMBUSTION AIR ROOF FLASHING BOOT FIELD SUPPLIED COMBUSTION AIR VENT ELBOW FIELD SUPPLIED MAINTAIN 12 IN 18 IN FOR CANADA MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL MAXIMUM OF 24 IN ABOVE ROOF SUPPORT FIELD SUPPLIED VENT m 6 Min 40 Inch Upflow or Downflow Furnace Slope 1 4 per ft Slope 1 4 ...

Page 24: ...all flue pipe and masonry chimney is to be used for another gas appliance venting area must be sufficient to vent that appliance and that appliance must be connect ed to chimney with separate entry openings IMPORTANT The single wall flue pipe joints must be sealed The 90 elbow connection to vertical pipe must be sealed to prevent condensate leakage to base of ma sonry chimney SUPPORT THE SINGLE WA...

Page 25: ...quirements of this subdivision can not be met at the time of completion of installation the owner shall have a period of thirty 30 days to comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed 2 APPROVED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance w...

Page 26: ...models LABEL SAYS TOP STRAIGHT SIDE MUST BE ON BOTTOM FOR PROPER CONDENSATE DRAINAGE WHEN THE FACTORY SUPPLIED OFF SET 2X3 REDUCING COUPLING IS USED FOR 3 VENT PIPE INSTALLATION MAKE SURE THE MARKING TOP IS LOCATED ON THE TOP SIDE OF THE PIPE 2 TO 3 COUPLING FURNACE VENT OUTLET FACTORY SUPPLIED ONLY WITH THE FOLLOWING MODELS UH1C080A9601A ALL 100 000 BTUH UPFLOW MODELS ALL 120 000 BTUH UPFLOW MODE...

Page 27: ...duced blower and reposition into the other drain tap of the inducer which is located 90 clockwise around the inducer Move the cap from that drain tap to the unused drain tap On upflow units plug the hole in the blower deck where the tube went through On upflow units this tube may need to be extended using the tubing shipped with the furnace Connections must be made to an OPEN or VENTED DRAIN Outdo...

Page 28: ...ain connection SEE NOTE 6 From drawing B341437 Rv 1 FURNACE TWIN SEE NOTE 7 B C B C TO 115 V 1 PH 60 HZ POWER SUPPLY PER LOCAL CODES HUM SEE NOTE 5 EAC SEE NOTE 5 FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE 1 STAGE HEATING USING A 1 STAGE HEATING THERMOSTAT NO COOLING Primary drain vent stack must terminate below secondary heat exchanger condensate drain outlet To drain opening If upflow furnace is i...

Page 29: ...external electrical source is uti lized OUTDOOR UNIT NO TRANSFORMER SEE NOTE 6 From drawing B340388 Rv 2 SEE NOTE 8 FURNACE B C B C TO 115 V 1 PH 60 HZ POWER SUPPLY PER LOCAL CODES HUM SEE NOTE 5 EAC SEE NOTE 5 FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE 1 STAGE HEATING 1 STAGE COOLING USING A 1 STAGE HEATING 1 STAGE COOLING THERMOSTAT OUTDOOR SECTION WITHOUT TRANSFORMER The integrated furnace contro...

Page 30: ...TE 4 ISOLATION RELAY SEE NOTE 4 B C B C B C From Dwg 21B341422 Rev 3 TWIN TWIN R1 R1 TWINNING CONNECTION DIAGRAM FOR TWINNING 1 STAGE FURNACES WITH SINGLE WIRE TWINNING FEATURE 1 STAGE HEAT 1 STAGE COOL THERMOSTAT 1 STAGE HEATING COOLING THERMOSTAT FURNACE NO 1 FURNACE NO 2 BLOWER OPERATION OF UNIT NO 2 IS SYNCRONIZED WITH UNIT NO 1 VIA SIGNALS FROM TWIN CONNECTION SEE NOTE 4 SEE NOTE 5 ISOLATION ...

Page 31: ...ovided on the right side for an alternate gas piping arrangement See Figure 52 The installation of piping shall be in accordance with pip ing codes and the regulations of the local gas company Pipe joint compound must be resistant to the chemical reaction with liquefied petroleum gases Refer to piping Table 15 for delivery sizes Connect gas supply to the unit using a ground joint union and a manua...

Page 32: ...n be ordered through Global Parts 4 Turn on system power and energize valve HORIZONTAL FURNACE GAS PIPING MAY BE FROM EITHER SIDE UPFLOW SHOWN GROUND UNION JOINT DRIP LEG AUTOMATIC GAS VALVE WITH MANUAL SHUTOFF MAIN MANUAL SHUTOFF VALVE GROUND UNION JOINT DRIP LEG MAIN MANUAL SHUTOFF VALVE AUTOMATIC GAS VALVE WITH MANUAL SHUTOFF R ORIFICE SIZES MODEL INPUT RATING BTUH NUMBER OF BURNERS MAIN BURNER...

Page 33: ...85A9481A 3 5 W C 11 0 W C DH1D110A9601A 4 5 W C 11 0 W C 5 Adjust gas heat by removing the adjustment regulator cover screw a To increase outlet pressure turn the regulator ad just screw clockwise b To decrease outlet pressure turn the regulator ad just screw counterclockwise c Adjust regulator until pressure shown on mano meter matches the pressure specified in Table 17 1 The input of no more tha...

Page 34: ...ode ANSI Z223 1 NFPA 54 or National Standard of Canada Natu ral Gas and Propane Installation Code CSA 149 1 Instal lation of this furnace at altitudes above 2 000 ft 610m shall be made in accordance with the listed high Altitude Conversion Kit available with this furnace IMPORTANT Re install the propane orifices to the same depth as the orifices supplied with the equipment GAS FLOW IN CUBIC FEET P...

Page 35: ...tem being placed into operation could result in carbon monoxide poisoning or death START UP AND ADJUSTMENT PRELIMINARY INSPECTIONS With gas and electrical power OFF 1 Duct connections are properly sealed 2 Filters are in place 3 Venting is properly assembled 4 Blower door is in place Flip the switch on main gas valve within the unit to the OFF position Turn the external gas valve to ON Purge the a...

Page 36: ...damage Whenever your house is to be vacant arrange to have someone inspect your house for proper temper ature This is very important during freezing weath er If for any reason your furnace should fail to oper ate damage could result such as frozen water pipes SEQUENCE OF OPERATION Thermostat call for heat R and W thermostat contacts close signaling the control module to run its self check routine ...

Page 37: ...ion The unit will not op erate until the condensate drain has been cleared and the condensate flows freely 7 RESET AFTER LOCKOUT When the integrated control module has shut the sys tem down and gone into lockout the system must be manually reset before the unit will restart To reset turn the system power off then on then off and then on again within 30 seconds This may be done at the unit s power ...

Page 38: ...38 18 CD29D1 11 Installer s Guide ...

Page 39: ...es or Recycles exceeded 3 Flashes Draft Pressure Error Possible problems a Venting problem b Pressure switch problem c Inducer problem 4 Flashes Open High Limit Device 5 Flashes Flame sensed when no flame should be present 6 Flashes 115 Volt AC power reversed or Poor Grounding 7 Flashes Gas valve circuit error 8 Flashes Low flame sense signal 9 Flashes Check Ignitor circuit and Line N to 24VAC Com...

Page 40: ...vement and reserves the right to change design and specifications without notice Trane 6200 Troup Highway Tyler TX 75707 For more information contact your local dealer distributor Literature Order Number 18 CD29D1 11 File Number 18 CD29D1 11 Supersedes 18 CD29D1 10 Date 03 14 ...

Reviews: