11
Default = ON. Manual override of chilled water
pump off delay
AUTO = activates the “Chilled water pump off
delay”
Chilled water pump
[ON, AUTO]
“Press (+) (-) to change setting”
Next
Chilled water pump off delay
[MINUTES]
“Press (+) (-) to change setting”
Next
Front panel current limit setpoint
XXX %
“Press (+) (-) to change setting”
Next
External current limit setpoint
[Disable/Enable]
“Press (+) (-) to change setting”
Next
Low ambient lockout
[Disable/Enable]
“Press (+) (-) to change setting
Next
Low ambient lockout
(Operator settings menu)
Enable
Disable
Low ambient lockout setpoint
XXX C
“Press (+) (-) to change setting
Next
[MINUTES]
Default = 10 minutes
Select = 1 minute to 30 minutes
The time period that the chilled water pump will
run, once the stop signal is given to the chiller.
Default = 120%
Select = 40% to 120%
Default = Disable
Default = Disable
Default = -6.6°C
Select: -28°C to 16°C