18
88-A4AC5001-1A-EN
STEP 2
- Determine the final subcooling value using total Line Length and Lift measured in STEP 1 and the charts below.
STEP 3
- Stabilize the system by operating for a
minimum of 20 minutes.
At startup, or whenever charge is removed or
added, the system must be operated for a mini-
mum of 20 minutes to stabilize before accurate
measurements can be made.
20 MIN.
Design Subcooling Value = __________º F
(from nameplate or Service Facts)
Subcooling Correction = __________º F
Final Subcooling Value = __________º F
3 Ton
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET
)
10
20
25
30
40
60
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
Add 5°
Add 4°
Add 2°
Add 3° of Subcooling
Add 1° of Subcooling
3 1/2 Ton
Add 6°
Add 5°
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
10
20
25
30
40
60
Add 3° of Subcooling
Add 2° of Subcooling
Add 1° of Subcooling
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
4 Ton
Add 6°
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
10
20
25
30
40
60
Add 4° of Subcooling
Add 3° of Subcooling
Add 2° of Subcooling
Add 1° of Subcooling
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
Add 6°
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
10
20
25
30
40
60
Add 5° of Subcooling
Add 4° of Subcooling
Add 3° of Subcooling
Add 2° of Subcooling
Add 1° of Subcooling
Design
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
5 Ton
2 1/2 Ton
Add 4°
Add 3°
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
10
20
25
30
40
60
Add 2° of Subcooling
Add 1° of Subcooling
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
1 1/2 Ton
Add 3°
Add 2°
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
10
20
25
30
40
60
Add 1° of Subcooling
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
2 Ton
Add 4°
Add 2°
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
10
20
25
30
40
60
Add 1° of Subcooling
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
Summary of Contents for A4AC5018D1000A
Page 24: ...24 88 A4AC5001 1A EN 3 1 2 4 Ton Units PRINTED FROM D158514P01 2 1 2 Ton Units Accumulator...
Page 25: ...88 A4AC5001 1A EN 25 5 Ton Units PRINTED FROM D158515P01...
Page 26: ...26 88 A4AC5001 1A EN Section 17 Wiring Diagrams A4AC5018 060 Models...
Page 27: ...88 A4AC5001 1A EN 27 A4AC5018 060 Models...
Page 31: ...Notes...