background image

About Trane and American Standard Heating and Air Conditioning

Trane and American Standard create comfortable, energy efficient indoor environments for residential applications.

For more information, please visit www.trane.com or www.americanstandardair.com

The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are 

committed to using environmentally conscious print practices.

© 2022

18-AD42D1-1B-EN   26 Aug 2022  
Supersedes   18-AD42D1-1A-EN   (November 2021)

Summary of Contents for 4TXCB004DS3HCC

Page 1: ...an expose you to chemicals including lead which are known to the State of California to case cancer and birth defects or other reproductive harm For more information go to www P65Warnings ca gov A GEN...

Page 2: ...out of the coil enclosure b Optional for maximum efficiency Remove the horizontal drain pan from the coil and discard 2 DOWNFLOW GASKET INSTALLATION OPTIONAL For unusually humid applications that expe...

Page 3: ...out of the coil enclosure b When present remove the 2 outer water diverter baffles See Figure 2 2 Attach the coil and furnace in the orientation shown in Figure 6 For S Series furnaces bend flanges t...

Page 4: ...l and slide back into the coil cabinet c Bend rear tab on top baffle inward towards the coil to avoid interference with splash guard See Figure 12 d Wedge flange of Splash Guard between Channel for Sp...

Page 5: ...K CHECK 1 Using a manifold gauge connect an external supply of dry nitrogen to the gauge port on the liquid line 2 Pressurize the connecting lines and indoor coil to 150 PSIG maximum 3 Leak check braz...

Page 6: ...refrigerant or condensate lines Once the outer doors are removed the inner coil panels can be easily removed The inside and outside of the coil can be easily cleaned withabrushandvacuumwiththepanelsr...

Page 7: ...18 AD42D1 1B EN 7 Installer s Guide Outline Drawing for model 4TXCB004DS3HCC 4TXCD010DS3HCC From Dwg D346710 Rev A...

Page 8: ...NO Is superheat 25F YES NO Is indoor temperature more than 85F NO Is sub cooling less than 8F YES Confirm that charge is correct and look for dirty or restricted outdoor coil Confirm that charge is co...

Page 9: ...18 AD42D1 1B EN 9 Installer s Guide...

Page 10: ...ications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and spec...

Reviews: