18-BC99D1-1D-EN
11
Table 13.
Isolation From Joist/Rafter
8 Feet Maximum
Side View
8 Feet Maximum
Joist/Rafter
Isolator
Line Set
6HFXUH 9DSRU /LQH IURP MRLVWV XVLQJ LVRODWRUV HYHU\ IW 6HFXUH /LTXLG /LQH GLUHFWO\ WR LQVXODWHG 9DSRU /LQH XVLQJ WDSH ZLUH RU RWKHU DSSURSULDWH
PHWKRG HYHU\ IW
Table 14.
Isolation In Wall Spaces
Side View
Isolator
Line Set
8 Feet Maximum
Wall
8 Feet Maximum
6HFXUH 9DSRU /LQH IURP MRLVWV XVLQJ LVRODWRUV HYHU\ IW 6HFXUH /LTXLG /LQH GLUHFWO\ WR LQVXODWHG 9DSRU /LQH XVLQJ WDSH ZLUH RU RWKHU DSSURSULDWH
PHWKRG HYHU\ IW
Table 15.
Isolation Through Wall
Wall
Sealant
Insulation
Vapor Line
Duct Work
Isolator
Line Set
DO NOT hang line sets from duct work