background image

 

18-AC74D1-4

Min. 12” to 

Shrubbery

Avoid Install 

Near Bedrooms

Min 5’ Unrestricted

Access Panel

Min 3’ 

Unrestricted 

2.3 Suggested Locations for Best Reliability

Ensure the top discharge area is unrestricted for 
at least five (5) feet above the unit.

Three (3) feet clearance must be provided in 
front of the control box (access panels) and any 
other side requiring service. 

Do not locate close to bedrooms as operational 
sounds may be objectionable.

Min. 12” to 

Shrubbery

Min. 12” 

to Wall

Position the outdoor unit a minimum of 12” from 
any wall or surrounding shrubbery to ensure 
adequate airflow.

Outdoor unit location must be far enough away 
from any structure to prevent excess roof runoff 
water from pouring directly on the unit.

2.4 Coastal Considerations

If installed within one mile of salt water, including seacoasts and inland waterways, models without factory 
supplied Seacoast Salt Shields require the addition of BAYSEAC001 (Seacoast Kit) at installation time.  Please 
refer to Application Guide SS-APB006-EN: Trane - Sea Coast Applications and Seascoast Corrosion Protection 
Bulletin
 UN-SVB11A-EN.

Summary of Contents for 4TTX5018A1000A

Page 1: ...matched indoor and outdoor systems All of the manufacture s split systems are A H R I rated only with TXV EEV indoor systems Some of the benefits of installing approved matched indoor and outdoor spl...

Page 2: ...for component replacement For specific handling concerns with R 410A and POE oil reference Retrofit Bulletins SS APG006 EN and APP APG011 EN Extreme caution should be exercised when opening the Liquid...

Page 3: ...SS APG006 EN or Refrigerant Piping Software Program 32 3312 03 or latest revi sion Table 2 1 Unit Dimensions and Weight Models H x D x W in Weight lb 4TTX5018A1000A 41 x 34 x 37 227 4TTX5024A1000A 41...

Page 4: ...12 to Shrubbery Min 12 to Wall Position the outdoor unit a minimum of 12 from any wall or surrounding shrubbery to ensure adequate airflow Outdoor unit location must be far enough away from any struc...

Page 5: ...ion 4 Setting the Unit 4 1 Pad Installation When installing the unit on a support pad such as a concrete slab consider the following The pad should be at least 1 larger than the unit on all sides The...

Page 6: ...ge Line Length 5 4 Refrigerant Line Insulation Important The Vapor Line must always be insulated DO NOT allow the Liquid Line and Vapor Line to come in direct metal to metal contact Vapor Line Liquid...

Page 7: ...structure due to vibration transmission from the refrigerant lines For Example When the refrigerant lines have to be fastened to floor joists or other framing in a structure use isolation type hanger...

Page 8: ...or other appropriate method every 8 ft 8 Feet Maximum Isolation Through Wall DO NOT hang line sets from ductwork Sealant Insulation Vapor Line Wall Ductwork Isolator Line Set Section 7 Refrigerant Lin...

Page 9: ...avoid heat damage and continue the dry nitrogen purge Braze the refrigerant lines to the service valves Continue the dry nitrogen purge Do not re move the wet rag until all brazing is completed Import...

Page 10: ...2 Check for leaks by using a soapy solu tion or bubbles at each brazed location Remove nitrogren pressure and repair any leaks before continuing Section 8 Refrigerant Line Leak Check 8 1 Check For Lea...

Page 11: ...e blank off the vacuum pump and micron gauge and close the valves on the manifold gauge set 1 MIN Section 10 Service Valves 10 1 Open the Gas Service Valve 0350 Microns ON OFF CAP 1 4 TURN ONLY COUNTE...

Page 12: ...System Service Port 3 16 Hex Wrench Unit Side of Service Valve Extreme caution should be exercised when opening the Liquid Line Service Valve Turn counterclockwise until the valve stem just touches t...

Page 13: ...umper wire from W3 to W2 If electric heat does not have 2nd contactor BH connect a jumper wire from W2 to W1 2 Ylo and BK may not be present on unit Air Handler Hook up Diagram Notes 1 If single stage...

Page 14: ...Y2 B O BK D Y1 R Neatly bundle all low voltage wires behind the service valve cover as shown Yellow Yellow Blue Blue Yellow Yellow Blue Blue Notes 1 See User Interface setup menu for cooling CFM opti...

Page 15: ...flow circuits to work properly Internally mounted con 4 densate switch is optional and must be ordered separately If 3rd party condensate 5 overflow switches are installed they should be wired in seri...

Page 16: ...Voltage Ground Ground the outdoor unit per national state and local code requirements LIVE ELECTRICAL COMPONENTS During installation testing servicing and troubleshooting of this product it may be ne...

Page 17: ...to apply power to the indoor and outdoor units STEP 5 Set system thermostat to ON OFF DONE CANCEL ON OFF STEP 4 Wait one 1 hour before starting the unit if compressor crankcase heater acces sory is u...

Page 18: ...to return in the spring or summer to accurately charge the system in the cooling mode when outdoor ambient tempera ture is above 55 F STEP 1 Use the refrigerant line total length and lift measurements...

Page 19: ...60 Use Design Subcooling Add 1 REFRIGERANT LINE LIFT FT SUBCOOL CHARGING CHART CORRECTIONS TABLE TOTAL REFRIGERANT LINE LENGTH FT 042 Units 60 Add 5 50 Add 4 40 30 25 20 15 10 0 10 20 25 30 40 60 Add...

Page 20: ...sure should be ap proximately 327 PSI This is the shown as the intersection of the Final Subcooling column and the Liquid Temperature row Table 14 2 8 9 10 11 12 13 14 179 182 185 188 191 195 198 195...

Page 21: ...S FOR 4TTX5049E1000A 4TXCD010CC3 Cooling 1400 CFM LIQUID PRESSURE PSIG OUTDOOR TEMPERATURE Degree F SUCTION PRESSURE PSIG OUTDOOR TEMPERATURE Degree F COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDO...

Page 22: ...eckout Procedures and Troubleshooting 15 1 Operational And Checkout Procedures Checkout Procedure After installation has been completed it is recommended that the entire system be checked against the...

Page 23: ...C T O R C O I L L O W V O L T A G E F U S E S T U C K C O M P R E S S O R I N E F F I C I E N T C O M P R E F U N D E R C H A R G E R E F O V E R C H A R G E E X C E S S I V E E V A P L O A D N O N C...

Page 24: ...www trane com The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Representative only illustra...

Reviews: