With Variable Speed UH2/DH2-V Furnace
• Units with pigtails require wirenuts for connec-
tions. Cap all unused wires.
• In systems with multiple stages of heat, jumper
W1 and W2 together if comfort control has only one
stage of heat.
** When using a BK enabled comfort control, cut BK
(W14) jumper and bypass Y and BK at the furnace.
Connect BK from comfort control to BK of the
furnace.
• Install R-O Jumper and cut BK Jumper (W14)
Furnace
Y
Y
Y
LO
Thermostat
Outdoor
Unit
R
G
B
W1
W2
B
R
G
B/C
Y1
W1
W2
24 VAC HOT
FAN
24 VAC
Common
HEATING
O
BK
BK
**
**
Y2
Y2
COOL
1st STAGE
COOL
2nd STAGE
With Variable Speed S-Series Furnace
NOTES:
1) For PWM (BK) enabled thermostats, cut the BK jumper on
the IFC and connect wiring.
2) The factory Y1-O jumper must remain in place for proper
LED read out in cooling mode.
3) Y1 and Y2 wiring from the thermostat must connect to
the IFC for proper airflow and LED readout.
4) Single compressor and two compressor airflow is auto-
matically set with the IFC Menu options in ODU section.
2-1=2 stage / 1 compressor (1st stage airflow = 75%)
2-2=2 stage / 2 compressors (1st stage airflow = 50%)