Trane 4TTB3-D Installer'S Manual Download Page 6

 

18-AC80D1-2

Installer’s Guide

3.5 Ton Subcooling Charging Table

1.5 Ton Subcooling Charging Table

4 Ton Subcooling Charging Table

2 and 3 Ton Subcooling Charging Table

5 Ton Subcooling Charging Table

2.5 Ton Subcooling Charging Table

SUBCOOlInG ChArGInG In COOlInG ABOVe 55°F OD AMBIenT

The Trane company has always recommended installing 

Trane approved matched indoor and outdoor systems.
All Trane split systems are AHRI rated with only TXV 

indoor systems.
The benefits of installing approved indoor and outdoor split 

systems are maximum efficiency, optimum performance and 

the best overall system reliability.
The following charging methods are therefore prescribed for 

systems with indoor TXVs.
  1.  Subcooling (in the cooling mode) is the only recommend-

ed method of charging above 55°F ambient tempera-

tures.

  2.  For best results - the indoor temperature should be 

kept between 70°F to 80°F. Add system heat if needed. 

  3.  At start-up, or whenever charge is removed or added, 

the system must be operated for a minimum twenty 

(20) minutes to stabilize before accurate measurements 

can be made.

  4.  Measure Liquid Line Temperature and Refrigerant 

Pressure at service valves.

  5.  Determine total refrigerant line length, and height 

(lift) if indoor section is above the condenser. 

  6.  Determine the Design Subcool Charging Temperature 

from the unit nameplate. 

  7.  Locate this value in the appropriate  column of the 

Subcooling Charging Table.  Locate your liquid line 

 temperature in the left column of the table, and the 

 intersecting liquid line pressure under your nameplate 

8

9

10

11

12

13

14

55

179

182

185

188

191

195

198

60

195

198

201

204

208

211

215

65

211

215

218

222

225

229

232

70

229

232

236

240

243

247

251

75

247

251

255

259

263

267

271

80

267

271

275

279

283

287

291

85

287

291

296

300

304

309

313

90

309

313

318

322

327

331

336

95

331

336

341

346

351

355

360

100

355

360

365

370

376

381

386

105

381

386

391

396

402

407

413

110

407

413

418

424

429

435

441

115

435

441

446

452

458

464

470

120

464

470

476

482

488

495

501

125

495

501

507

514

520

527

533

r­410A reFrIGerAnT ChArGInG ChArT

Refer to Service Facts or 

Installer's Guide for charging method. 

LIQUID

TEMP

(

˚

F) 

DESIGN SUBCOOLING (

˚

F)

LIQUID GAGE PRESSURE (PSI)

From Dwg. D154557P01 Rev. 2

 subcool value column. Add refrigerant to raise the 

pressure to match the table, or remove refrigerant to 

lower the pressure. Again, wait twenty (20) minutes 

for the system  conditions to stabilize before adjusting 

charge again.

  8.  When system is correctly charged, you can refer to 

System Pressure Curves (in Service Facts) to verify 

typical performance.

60
50
40
30
25
20
15
10

0

10

20

25

30

40

60

80

SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)

REFRIGERANT LINE LIFT (FEET)

TOTAL REFRIGERANT LINE LENGTH (FEET)

Use Design Subcool Value (8º)

Add 2º

Add 2º

Add 1º

Add 3º

Add 4º

Add 5º

60
50
40
30
25
20
15
10

0

10

20

25

30

40

60

80

SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)

REFRIGERANT LINE LIFT (FEET

)

TOTAL REFRIGERANT LINE LENGTH (FEET)

Use Design Subcool Value (10º)

Add 1º

Add 1º

Add 2º

Add 2º

Add 3º

Add 3º

Add 4º

60
50
40
30
25
20
15
10

0

10

20

25

30

40

60

80

SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)

REFRIGERANT LINE LIFT (FEET

)

TOTAL REFRIGERANT LINE LENGTH (FEET)

Use Design Subcool Value (10º)

Add 1º

Add 5º

Add 5º

Add 2º

Add 6º

Add 3º

Add 3º

Add 6º

Add 7º

Add 4º

60
50
40
30
25
20
15
10

0

10

20

25

30

40

60

80

SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)

REFRIGERANT LINE LIFT (FEET

)

TOTAL REFRIGERANT LINE LENGTH (FEET)

Use Design Subcool Value (10º)

Add 3º

Add 2º

Add 2º

Add 2º

Add 1º

Add 1º

Add 1º

Add 3º

Add 4º

Add 4º

Add 5º

Add 5º

Add 6º

60
50
40
30
25
20
15
10

0

10

20

25

30

40

60

80

SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)

REFRIGERANT LINE LIFT (FEET

)

TOTAL REFRIGERANT LINE LENGTH (FEET)

Use Design Subcool Value (10º)

Add 1º

Add 2º

Add 3º

60
50
40
30
25
20
15
10

0

10

20

25

30

40

60

80

SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)

REFRIGERANT LINE LIFT (FEET

)

TOTAL REFRIGERANT LINE LENGTH (FEET)

Use Design Subcool Value (10º)

Add 1º

Add 2º

Add 3º

Summary of Contents for 4TTB3-D

Page 1: ...dip tube to allow for charging of liquid refrigerant into the system All R 410A systems use a POE oil that readily absorbs moisture from the atmosphere To limit this hygroscopic action the system should remain sealed whenever possible If a system has been open to the atmosphere for more than 4 hours the compressor oil must be replaced Never break a vacuum with air and always change the driers when...

Page 2: ... most practical way to run the lines 2 Consider types of bends to be made and space limitations NOTE Large diameter tubing will be very difficult to rebend once it has been shaped 3 Determine the best starting point for routing the refrigerant tubing INSIDE OR OUTSIDE THE STRUCTURE 4 Provide a pull thru hole of sufficient size to allow both liquid and gas lines 5 Be sure the tubing is of sufficien...

Page 3: ...e to vacuum pump and observe the micron gauge If gauge pressure rises above 500 microns in one 1 minute then evacuation is incomplete or system has a leak 6 If vacuum gauge does not rise above 500 microns in one 1 minute the evacuation should be complete 7 Blank off vacuum pump and micron gauge close valves on manifold gauge set NOTE DO NOT VENT REFRIGERANT INTO THE ATMOSPHERE NOTE A 3 16 Allen wr...

Page 4: ...orm a final unit inspection to be sure that factory tubing has not shifted during shipment Adjust tubing if necessary so tubes do not rub against each other when the unit runs Also be sure that wiring connections are tight and wire routing is secure H Seacoast Shield If installed within one mile of salt water including seacoasts and inland waterways models without factory supplied Seacoast Salt Sh...

Page 5: ...ounding of equipment must comply with local codes 3 Low voltage wiring to be No 18 AWG minimum conductor 4 ODT B must be set lower than ODT A 5 If outdoor thermostats ODT are not used connect W1 to W2 and W3 leGenD FACTORY WIRING FIELD WIRING PRINTED FROM B152901 P02 PRINTED FROM B152903 P02 NOTE W2 present only on 2 stage thermostat and furnace ...

Page 6: ...15 435 441 446 452 458 464 470 120 464 470 476 482 488 495 501 125 495 501 507 514 520 527 533 r 410A reFrIGerAnT ChArGInG ChArT Refer to Service Facts or Installer s Guide for charging method LIQUID TEMP F DESIGN SUBCOOLING F LIQUID GAGE PRESSURE PSI From Dwg D154557P01 Rev 2 subcool value column Add refrigerant to raise the pressure to match the table or remove refrigerant to lower the pressure ...

Page 7: ...5 8 210 8 1 4 79 3 1 8 508 20 4TTB3030D 3 1 730 28 3 4 829 32 5 8 756 29 3 4 3 4 3 8 143 5 5 8 92 3 5 8 210 8 1 4 79 3 1 8 508 20 4TTB3036D 3 1 832 32 3 4 829 32 5 8 756 29 3 4 3 4 3 8 143 5 5 8 92 3 5 8 210 8 1 4 79 3 1 8 508 20 4TTB3042D 4 1 741 29 1 8 946 37 1 4 870 34 1 4 3 4 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 4TTB3048D 4 1 741 29 1 8 946 37 1 4 870 34 1 4 7 8 3 8 152 6 98 3 7 8 219 ...

Page 8: ...efrigerant Lines been secured and isolated properly 4 Have passages through masonry been sealed If mortar is used prevent mortar from coming into direct contact with copper tubing 5 Verify tightness of all electrical connects 6 Observe outdoor fan during on cycle for clearance and smooth operation 7 Indoor coil drain line drains freely Pour water into drain pan 8 Supply registers and return grille...

Reviews: