Trane 4TGB3F18A Installer'S Manual Download Page 3

18-GD06D1-5 

 

3

Installer’s Guide

 

f. It  is  always  recommended  that  an  auxiliary  drain 

pan be installed under a horizontal air handler (See 

Condensate Drain Piping) to prevent possible dam-

age to ceilings.

 

g. Isolate  the  auxiliary  drain  pan  from  the  unit  or 

from the structure.

 

h. Connect the auxiliary drain line to a separate drain 

line (no trap is needed in this line) and terminate 

according to local codes. 

 

i. If a return duct is connected to the Air Handler, it 

must  be  the  same  dimensions  as  the  return  open-

ing shown in the outline drawings. 

 C.  DUCT CONNECTIONS

The  supply  and  return  air  ducts  should  be  connected  to 
the unit with flame retardant duct connectors.

 

Convertible duct flanges are provided to make a “flush fit” 
for ¾” or 1-1/2” ductboard applications.  Three are located 
in  the  accessory  kit  shipped  with  the  unit  and  one  is  in-
stalled  on  the  discharge  opening.  If  the  duct  flanges  are 
not needed, the installed flange must be removed. See the 
Outline drawing for sizes of the discharge opening. After 
ductwork is secured, seal the ductwork per local and na-
tional codes to prevent air loss/infiltration.

D.  REFRIGERANT PIPING

IMPORTANT:

Refrigerant piping must be routed to maintain service access 

to blower compartment and provide easy removal of filter ac-

cess panel and filter.

  1.  Refrigerant connections are made outside the cabinet.

NOTE:

TXV bulb 

MUST

 be protected (wrap a wet rag around 

the  suction  line  between  the  TXV  bulb  and  the  braze 

joint) or removed, while brazing the tubing. Overheat-

ing of the sensing bulb will affect the functional char-

acteristics and performance of the air handler.

  2.  If changing the Thermostatic valve (TEV/TXV), be sure 

to  use  a  wrench  and  backup  wrench  to

  tighten  the 

mechanical fittings 1/6 turn past finger tight

 upon 

installation.

  3.  Installation of refrigerant lines is covered in the instal-

lation  instructions  packaged  with  the  outdoor  unit. 

Evacuation,  leak  testing  and  brazing  procedures  are 

included in those instructions. Read those instructions 

before starting installation of refrigerant lines.

NOTE:

TXV Equipped is Non-Bleed, and may require a start 

kit on the outdoor unit.

NOTE:

Refrigerant  line  openings  must  be  sealed  along  with 

field wiring.

E.  BRAZING TO EVAPORATOR SECTION

IMPORTANT:

Do noT unseal refrigerant tubing until ready to cut and fit 

refrigerant lines.

  1.  Remove the sealing caps from indoor coil field connec-

tions.

  2.  Field supplied tubing should be cut squared-off, ensur-

ing the tube is still round and free of burrs at the con-

necting end. Clean the tubing to prevent contaminants 

from entering the system.

  3.  Run  refrigerant  tubing  into  the  stub  sockets  of  indoor 

unit coil.  

Refrigerant line openings must be com-

pletely sealed.

  4.  Braze and evacuate according to indoor and outdoor in-

stallation instructions.

IMPORTANT:

Painted areas of unit must be shielded during brazing. 

 

F.  CONDENSATE DRAIN PIPING

NOTE:

Make certain that the unit has been installed in a level 
position to ensure proper draining.

The indoor blower is downstream of the evaporator coil 

which  creates  a  negative  pressure  at  the  condensate 

drain  connections  during  operation.  The  condensate 

drain  connections  in  front  of  the  indoor  coil  are  3/4" 

NPT.  The  lower  connection  is  the  primary  drain.  See 

Figure 3.
Two  secondary  drain  connections  are  provided  for  the 

different orientations (See Figure 3). The lower of the 

two  should  be  connected  as  a  backup  to  prevent  con-
densate overflow by a blocked primary drain. The weep 
hole in center of drain coupling area should be sealed 
with caulk or RTV.
For proper drainage of condensate, the following steps 

should be followed:

  1.  The primary drain line must be trapped with a min-

imum of 2" water seal as shown in Figures 4 & 5

.

 

  2.

  Do not use preformed 3/4" PVC running traps.

 

    The use of Field fabricated or manufactured traps 

as shown in Figures  4 & 5 is acceptable. The man-

ufactured trap shown in Figure 4 allows for a float 

switch  option  to  be  added.  Refer  to  the  manufac-

turers data and instructions for details.

  3. 

The trap must be located within 4 feet of the 

air handler drain outlet connection.

  4.  It 

 

is recommended that a clean-out tee or cross be 

installed in the primary drain line for future main-

tenance  (See Figures  4 & 5).

Figure 3

3/4" NPT  

Primary 

drain  

connection

3/4" NPT  

Secondary

drain  

connection

Seal weep 

hole

Summary of Contents for 4TGB3F18A

Page 1: ...only Refer to Section B beginning on page 2 for additional information INSPECTION Check carefully for any shipping damage This must be reported to and claims made against the transporta tion company i...

Page 2: ...s are suitable for instal lation in an attic garage or crawl space with ducted supply and return air This equipment for models 2 4TGB3F18 25 30 36A only has been evaluated in accordance with the Code...

Page 3: ...NOTE TXV Equipped is Non Bleed and may require a start kit on the outdoor unit NOTE Refrigerant line openings must be sealed along with field wiring E BRAZING TO EVAPORATOR SECTION IMPORTANT Do not un...

Page 4: ...are shipped with the accessory 4 Wiring must conform to National and Local codes Ground unit per Local codes with good safety pro cedures If an electric heater is not installed the Knockout Plate prov...

Page 5: ...18 GD06D1 5 5 Installer s Guide 2 4TGB AIR HANDLERS WITH SINGLE STAGE COOLING 1 STAGE HEAT...

Page 6: ...6 18 GD06D1 5 Installer s Guide 2 4TGB AIR HANDLERS WITH SINGLE STAGE COOLING AND TWO STAGE HEATING 2 4TGB AIR HANDLERS WITH SINGLE SPEED HEAT PUMP From Dwg B801081 Rev 2...

Page 7: ...18 GD06D1 5 7 Installer s Guide OUTLINE DRAWING FOR 2 4TGB3F18 25 30 36A From Drawing D810094P01 Rev 3...

Page 8: ...ts per unit nameplate 8 Check filters for proper size Inform owner of proper procedure for removal and reinstallation 9 Energize the system and carefully observe its opera tion make any necessary adju...

Reviews: