Trane 4TEE3F31B1000B Installer'S Manual Download Page 9

18-GE04D2-15

9

Installer’s Guide

2" MINIMUM 

2" MINIMUM 

Manufactured traps

EZT-105

Figure 15

Field fabricated trap

2" MIN.

2" MIN.

CAP OR PLUG

Trap must be within 4' 
of air handler condensate
drain connection.

Close as possible

Figure 16

The manufactured trap shown in Figure 15 allows
for a float switch option to be added.
Refer to the manufacturers data and instructions
for details.

2. The trap must be located within 4 feet of the air

handler drain outlet connection.

3. It 

 

is recommended that a clean-out tee or cross be

installed in the primary drain line for future main-
tenance  (See Figure 15 & 16).

4. Do not use reducing fittings in the condensate drain

lines.

5. Slope the drain lines downward a minimum of 1/4"

per foot.

6. Insulate the primary drain to prevent sweating

where pipe temperature could meet or fall below
dewpoint temperatures.

7.

Provide means for drainage to prevent winter
freeze-up of condensate line

.

8. Do not connect the drain line to a closed drain sys-

tem.

9. Use Teflon

®

 tape on the air handler drain line con-

nections!  Do Not Use pipe joint compound or PVC/
CPVC cement!

It is always recommended that an auxiliary drain pan
be installed under a horizontally installed air handler.

Connect the auxiliary drain line to a separate drain line
(no trap is needed in this line) and terminate according
to local codes.

NOTE: DO NOT use a torch or flame near the plastic
drain pan coupling.

NOTE: DO NOT tighten the drain pipe excessively. Sup-
port the condensate piping and traps outside the unit
to prevent strain on the drain coupling.

H. ELECTRICAL — POWER WIRING

WARNING

!

ELECTRICAL SHOCK HAZARD
LOCK UNIT DISCONNECT SWITCH IN OPEN POSITION
BEFORE SERVICING UNIT.  FAILURE TO FOLLOW THIS
WARNING COULD RESULT IN PROPERTY DAMAGE,
PERSONAL INJURY, OR DEATH.

1. These Air Handlers are shipped from the factory

wired for 230 volts. The units may be wired for 208
volts. Follow instructions on unit wiring diagram lo-
cated on blower housing and in the Service Facts
document included with the unit.

2. The selection of wire and fuse sizes should be made

according to the Minimum Branch Circuit Ampacity
and the Maximum Overcurrent Device listed on the
unit nameplate.

3. Field wiring diagrams for electric heaters and unit

accessories are shipped with the accessory.

4. Wiring must conform to National and Local codes.
5. Ground unit per local codes with good safety proce-

dures.

If an electric heater is not installed, the Knockout Plate pro-
vided in the Accessory Kit MUST be installed on the air han-
dler and the conduit terminated to it.  The electrical connec-
tions are made using the two power leads and ground wire
connections which are located near the discharge of the
blower. 

  Openings where the field wiring enters the

cabinet must be completely sealed.  Location of power
entry is shown on the outline drawing.  Use 2.5" clear
stickers to seal all unused electrical knockouts.

NOTE: If air handler is used with or without a heater,
the electrical entry hole as well as any other cabinet
penetrations  must be sealed air-tight.

Summary of Contents for 4TEE3F31B1000B

Page 1: ...ct your local distributor or the manufacturer as listed on the air handler nameplate These air handlers are shipped from the factory in the upflow or horizontal right configuration and are fully convertible to downflow or horizontal left Refer to Sec tion C beginning on page 4 for additional information INSPECTION Check carefully for any shipping damage This must be reported to and claims made aga...

Page 2: ...the air handler must be made to allow access for refrigerant lines or attach refrigerant lines to air handler when installing This area may also be used for other purposes includ ing an electric hot water heater but in no case shall a fossil fuel device be installed and or operated in the same closet alcove or utility room In addition these air handlers are suitable for installa tion in an attic g...

Page 3: ...structions These should only be installed on the supply air side of the system Atomizing style humidifiers are not recommended with the use of this unit C UNIT INSTALLATION UPFLOW a For maximum efficiency the horizontal drip tray should be removed See Figures 5 6 and 7 B Two Piece Cabinet Disassembly OPTIONAL NOTE For easier installation into tight areas the 4 and 5 ton air handlers can be disasse...

Page 4: ...to support the total weight must be pro vided Provide a minimum height of 14 inches for proper unrestricted airflow d If a return air duct is connected to the air han dler it must be the same dimensions as shown in the outline drawing on page 13 e Pedestal and unit should be isolated from the foundation using a suitable isolating material f Openings where field wiring enters the cabinet must be co...

Page 5: ...and isolated carefully to pre vent sound transmission Vibration isolators pur chased locally must be placed under the unit e It is always recommended that an auxiliary drain pan be installed under a horizontal air handler See Condensate Piping to prevent possible dam age to ceilings f Isolate the auxiliary drain pan from the unit or from the structure g Connect the auxiliary drain line to a separa...

Page 6: ...nly needs to be suspended at both ends See Figure 11 d If the unit is not suspended it must be supported as mentioned above and isolated carefully to pre vent sound transmission Vibration isolators pur chased locally must be placed under the unit e It is always recommended that an auxiliary drain pan be installed under a horizontal air handler See Condensate Drain Piping to prevent pos sible damag...

Page 7: ...ns Return ple num should be flanged Sheetmetal screws must be 1 2 in length or shorter See Figure 12 NOTE Any duct board return connection can be made to the sides of the unit using tape or mastic Rail Figure 11 Mounting Installation Options g Connect the auxiliary drain line to a separate drain line no trap is needed in this line and ter minate according to national and local codes h If a return ...

Page 8: ...he tubing Overheating of the sensing bulb will affect the func tional characteristics and performance of the air han dler IMPORTANT Do NOT unseal refrigerant tubing until ready to cut and fit refrigerant lines 1 Remove both sealing caps from indoor coil 2 Field supplied tubing should be cut squared off en suring the tube is still round and free of burrs at the connecting end Clean the tubing to pr...

Page 9: ...ighten the drain pipe excessively Sup port the condensate piping and traps outside the unit to prevent strain on the drain coupling H ELECTRICAL POWER WIRING WARNING ELECTRICAL SHOCK HAZARD LOCK UNIT DISCONNECT SWITCH IN OPEN POSITION BEFORE SERVICING UNIT FAILURE TO FOLLOW THIS WARNING COULD RESULT IN PROPERTY DAMAGE PERSONAL INJURY OR DEATH 1 These Air Handlers are shipped from the factory wired...

Page 10: ...TION Disconnect power to the air handler before changing dip switch positions Failure to follow this procedure may result in equip ment damage Blower speed changes are made on the ECM Fan Con trol mounted on the control box The ECM Fan Control controls the variable speed motor There is a bank of 8 dip switches See Figure 17 The dip switches work in pairs to match the airflow for the outdoor unit s...

Page 11: ...NECT 1 PF TO MATING PLUG IN THE HEATER CONTROL BOX AS SHOWN 3 TERMINAL W2 WILL HAVE INTERNAL CONNECTIONS ONLY IF 2ND CONTACTOR IS USED BY THE HEATER FOR CONTROLLING POWER TO ELECTRIC HEAT ELEMENTS IF 2ND BH CONTACTOR IS NOT USED THEN FIELD CONNECTIONS TO W2 CAN BE OMITTED AS APPROPRIATE 4 CONNECTIONS TO R BK O AND Y MUST BE MADE AS SHOWN FOR PROPER OPERATION OF BLOWER WITH HUMIDISTAT IN COOLING 4T...

Page 12: ...E HEATER CONTROL BOX AS SHOWN 3 TERMINAL W2 WILL HAVE INTERNAL CONNECTIONS ONLY IF 2ND CONTACTOR IS USED BY THE HEATER FOR CONTROLLING POWER TO ELECTRIC HEAT ELEMENTS IF 2ND BH CONTACTOR IS NOT USED THEN FIELD CONNECTIONS TO W2 CAN BE OMITTED AS APPROPRIATE 4 IF ODT IS NOT USED THEN CONNECT APPROPRIATE JUMPER FROM W1 TO W2 TO W3 ON LVTB 5 CONNECTIONS TO R BK O AND Y MUST BE MADE AS SHOWN FOR PROPE...

Page 13: ...low during the defrost cycle 5 Connect only if used with applicable indoor thermostat 6 When heaters are used discard power leads with polarized plug PM A and connect 1 PF to mating plug in the heater control box as shown REQUIRED WIRING Refer to Field Hook up Diagrams 4TTX6 4TWX6 4A7A6 4A6H6 units require 80 airflow with Y1 firststage 100 airflow with Y2 second stage Note A The installer must jum...

Page 14: ...14 18 GE04D2 15 Installer s Guide 4TEE 3 F OUTLINE DRAWING ...

Page 15: ...E04D2 15 15 Installer s Guide 4TEE3F AIR HANDLERS DIMENSIONAL DATA Model No H W 4TEE3F31B 43 00 21 50 4TEE3F37B 45 00 23 50 4TEE3F40B 51 75 26 00 4TEE3F49B 4TEE3F49C 57 90 4TEE3F65B 4TEE3F66A 62 75 H W 21 0 ...

Page 16: ... RECOMMENDATIONS 1 Be sure the disconnect switch is OFF and safety label if any is attached 2 Check on field wiring for tight connections and grounding according to codes 3 Check circuit protection for proper size per nameplate specifications 4 Check control box panel in place and secured NOTE OPERATION OF HEATERS MUST BE CHECKED DURING THE OPERATION CHECK OF THE TOTAL SYSTEM J CHECKOUT PROCEDURES...

Reviews: