6

TEE3C49A-SF-1B

AIR HANDLER FLASH CODES

Fault LED

COMM LED 

User Interface 

Display

Comfort 

Control 
Display

Solid ON ‡

N/A

CNTRL FAULT †

ERR 18

18

Control Failure

Internal Control Error

Solid ON ‡

N/A

CHECK FUSE †

N/A +

92

Fuse Failure

24V Fuse Open Error

1 Flash *

N/A

EXT SW OPEN *

ERR 106 *

106

External 

Shutdown Fault

External Shutdown Input Open Error

PM MEM ERR

PM Data Corrupt Error

PM MISSING

PM Missing Error

ID MTR ERR

Motor Mismatch Error

PM UNIT ERR

PM Unit Data Error

CAP MISMATCH

Compressor Capacity Mismatch 

Error

PM DATA ERR

PM Data Section Error

NO SYS CLK

COMM Bit Master Clock Error

SYS COMM ERR

COMM Heat/Cool Demand Error

3 Flash

N/A

BLW COMM ERR

Serial Motor Communication 

Inactive Error ¹

3 Flash **

Fast Flash

SYS COMM CRC

COMM System Busy Error

3 Flash

N/A

BLW COMM CRC

Serial Motor Communication Busy 

Error

HT+LK ON ERR

Both Interlock Relay & Heater Relay 

Stuck Closed Error

INTLK ON ERR

Interlock Relay Stuck Closed 

Error

NTLK OFF ERR

Interlock Relay Stuck Open Error

HT ON ERR

Heater Relay Stuck Closed Error

HT OFF ERR

Heater Relay Stuck Open Error

DAS RNG ERR *

Discharge Air Temperature Range 

Error

DAS UL ERR *

Discharge Air Temperature Upper 

Limit Error

DAS LL ERR *

Discharge Air Temperature Lower 

Limit Error

DAS SHORT *

Discharge Air Sensor Short Error

DAS OPEN *

Discharge Air Sensor Open Error

6 Flash *

N/A

RAS RNG ERR *

N/A

117

Return Air 

Temperature 

Fault

Return Air Temperature Range 

Error

RAS SHORT *

Return Air Sensor Short Error

RAS OPEN *

Return Air Sensor Open Error

Y1 ON ERR

Y1 Relay Stuck Closed Error

Y1 OFF ERR

Y1 Relay Stuck Open Error

8 Flash

N/A

TWIN ERROR

N/A

19

Twinning Fault

Air Handler Twinning Error

DEMAND ERR *

Heat/Cool Demand Conflict Error

HT CFG ERR

Electric Heat Configuration Error

ERR 118 *

N/A

N/A

4 Flash

5 Flash *

5 Flash *

6 Flash *

N/A

N/A

   +     Fuse alert notification level would show on Comfort Control, but when fuse is open the COMM bus has no power

9 Flash

N/A

123

Demand 

Configuration 

   †     If Air Handler processor is reset or fuse is open, COMM Alert cannot be reported; if the processor is reset
             the User Interface will not be updated

   *      Alert flash code will not be implemented for initial release

   ‡     LitePort™ transmissions will be allowed during ON flash codes

Notes:

  ¹    Comfort Control will switch system to "OFF" until this fault condition clears

Discharge Air 

Sensor Fault

52

Discharge Air 

Temperature 

Fault

118

7 Flash

N/A

Y1 Relay Fault

110

101

ERR 101

Return Air 

Sensor Fault

N/A

Communication 

Busy Fault

90

N/A

Heater Interlock 

Relay Fault

105

N/A

Heater Relay 

Fault

104

ERR 104

ERR 114

Alert Description

2 Flash

N/A

PM Bad or 

Missing Fault

114

Alert Notification

Alert 

Code

Alert Group

N/A

Fast Flash

3 Flash **

   **    COMM communication errors may also be flashed on Fault LED

91

N/A

ERR 91

ERR 105

N/A

Communication 

Inactive Fault

4 Flash

Summary of Contents for 4TEE3C49A1000A

Page 1: ...ts of this product that are capable of conducting electrical current are grounded If grounding wires screws straps clips nuts or washers used to com plete a path to ground are removed for service they must be returned to their original position and prop erly fastened HAZARDOUS VOLTAGE DISCONNECT POWER BEFORE SERVICING WARNING IMPORTANT This document contains a wiring diagram and service informatio...

Page 2: ...389 High 450 CFM 1326 1334 1335 1337 1326 Watts 235 292 347 402 464 Low 290 CFM 1013 1012 1007 993 966 Watts 144 188 232 275 315 Med Lo 350 CFM 1204 1213 1214 1218 1206 3 5 Watts 190 239 292 349 392 tons Med Hi 400 CFM 1375 1381 1382 1386 1373 Watts 257 314 370 430 488 High 450 CFM 1541 1546 1545 1544 1545 Watts 340 405 468 534 595 Low 290 CFM 1211 1220 1227 1225 1212 Watts 195 249 304 357 408 Med...

Page 3: ...C circuit 1 BAYHTR1419 BRKC circuit 2 BAYHTR1415 BRKC with single circuit power source kit BAYSPEK140B circuit 1 BAYHTR1415 BRKC circuit 2 TOTAL HEATER BAYHTR1425BRKC UNIT TEST MODE Unit Test Mode Air Handler The system must be idle or thermostat switched to OFF before the Unit Test will run the air handler The unitwillworkthesamewayineithertheCommunicating Mode or 24 volt AC mode To access the Un...

Page 4: ...4 TEE3C49A SF 1B 2 4TEE3C49A USER INTERFACE MENU ...

Page 5: ...FACE MENU 24V MODE USER INTERFACE ENTER Push left right to scroll through menu options Push up down to scroll through setup menu Push ENTER to make selection Viewing Window User Interface pictured above adjusts variable speed airflow options ...

Page 6: ...rge Air Sensor Open Error 6 Flash N A RAS RNG ERR N A 117 Return Air Temperature Fault Return Air Temperature Range Error RAS SHORT Return Air Sensor Short Error RAS OPEN Return Air Sensor Open Error Y1 ON ERR Y1 Relay Stuck Closed Error Y1 OFF ERR Y1 Relay Stuck Open Error 8 Flash N A TWIN ERROR N A 19 Twinning Fault Air Handler Twinning Error DEMAND ERR Heat Cool Demand Conflict Error HT CFG ERR...

Page 7: ...TEE3C49A SF 1B 7 WIRING DIAGRAM FOR 2 4TEE3C49A ...

Page 8: ...product data improvement it reserves the right to change design and specifications without notice Trane 6200 Troup Highway Tyler TX 75707 For more information contact your local dealer distributor 1 08 OUTLINE DRAWING FOR 2 4TEE3C49A Printed from Dwg D802101 Rev 3 ...

Reviews: