Trane 2TWZ9 Installer'S Manual Download Page 1

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

IMPORTANT — This Document is customer property and is to remain with this unit.  Please return to service information
pack upon completion of work.

Installer’s Guide

3. Avoid locating the unit where condensation and freezing

of defrost vapor may annoy the customer. For instance,
installing the unit under a bedroom, kitchen, or picture
window may be annoying to the customer since conden-
sate and fog will occur during the defrost cycle.

4. Avoid locating the unit under the eaves or other over-

head structures as sizeable icicles may form and the unit
may be damaged by these falling icicles.

B. LOCATION AND PREPARATION

OF THE UNIT

1. When removing unit from the pallet, notice the tabs on

the basepan. Remove tabs by cutting with a sharp tool as
shown on page 2, Figure 2, and slide unit off of pallet.

2. The unit should be set on a level support pad at least as

large as the unit base pan, such as a concrete slab. If this
is not the application used please refer to application
bulletin “Trane XL19i-APG**-EN”. (*denotes latest
revision)

Heat Pumps

2TWZ9

These instructions do not cover all variations in
systems nor provide for every possible contingency to
be met in connection with installation. All phases of
this installation must comply with NATIONAL, STATE
AND LOCAL CODES. 
Should further information be
desired or should particular problems arise which are not
covered sufficiently for the purchaser’s purposes, the matter
should be referred to your installing dealer or local distributor.

A. GENERAL

The following instructions cover 2TWZ9 Heat Pump Units.

NOTE:
These outdoor units must be used with indoor units
equipped with Thermostatic Expansion Valve only.

Check for transportation damage after unit is uncrated.
Report promptly, to the carrier, any damage found to the unit.

To determine the electrical power requirements of the unit,
refer to the nameplate of the unit. The electrical power
available must agree with that listed on the nameplate.

The Weathertron

® 

Heat Pump has been designed and

manufactured to withstand and operate in severe winter
conditions. However, there are precautionary steps which
should be taken at the time of installation which will help
assure the efficient operation of the unit. It is recom-
mended that these precautions be taken for units
being installed in areas where snow accumulation and
prolonged below freezing temperatures occur.

1.

Units should be elevated 3 to 12 inches above the pad or
rooftop, depending on local weather. This additional
height will allow better drainage of snow and ice (melted
during defrost cycle) prior to its refreezing. 

This should

prevent a build-up of ice around the unit which occurs
when unit is not elevated. Insure that drain holes in
unit base pan are not obstructed preventing
draining of defrost water.

2. If possible, avoid locations that are likely to accumulate

snow drifts. If not possible, a snow drift barrier should be
installed around the unit to prevent a build-up of snow
on the sides of the unit and should be of sufficient
distance from the unit to prevent restriction of airflow to
and from the unit. Also allow for proper maintenance
space. The barrier should be constructed of materials
which will blend in with the building design.

1

18-BC53D1-2

Summary of Contents for 2TWZ9

Page 1: ...istributor A GENERAL The following instructions cover 2TWZ9 Heat Pump Units NOTE These outdoor units must be used with indoor units equipped with Thermostatic Expansion Valve only Check for transporta...

Page 2: ...is the same Final refrigerant charge adjustment is necessary Use the Charging Charts in the outdoor unit Service Facts 1 Determine the most practical way to run the lines 2 Consider types of bends to...

Page 3: ...pressure taps NOTE Unnecessary switching of hoses can be avoided and com plete evacuation of all lines leading to sealed system can be accomplished with manifold center hose and connecting branch hos...

Page 4: ...rement is representative of the operating state and relative capacity of the heat pump system By measuring the change in delta T we can determine the need for defrost The coil sensor also serves to se...

Page 5: ...f this installation are the unit Operational and Checkout Procedures which are found in this instruction on page 8 To obtain proper performance all units must be operated and charge adjustments made i...

Page 6: ...46 37 1 4 870 34 1 4 7 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 933 36 3 4 2TWZ9036B 4 1267 49 7 8 946 37 1 4 870 34 1 4 7 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 933 36 3 4 2TWZ9048B 4 1267 49 7 8 946...

Page 7: ...18 BC53D1 2 7 Installer s Guide MOUNTING HOLE LOCATION NOTE ALL DIMENSIONS ARE IN MM INCHES NOTE For model base size see table on page 6 From Dwg 21D152637 Rev 1...

Page 8: ...Inadequate or No Cooling Htg ELECTRICAL Compressor O D Fan Won t Start Compressor Will Not Start But O D Fan Runs O D Fan Won t Start Compressor Hums But Won t Start Compressor Cycles on IOL I D Blow...

Reviews: