BAS-SVX44C-EN
49
Other Functional Components
There is a minimum 5°F (2.5°C) deadband between compressor and auxiliary heat lockout temperatures.
Configuration option #220 sets the compressor lockout point; #221 sets the auxiliary lockout point. Refer
to the following illustrations.
Aux Lockout
T em perature
IPN 0221=
0
C om pr Lockout
T em perature
IPN0220
≠0
A ux iliary H eat O nly
B oth C om pres s or H P
and A ux iliary H eat
O
u
td
o
o
r
T
e
m
p
e
ra
tu
re
15 to 45F (-9.5 to 7.0C)
IP N0210 = 2 (H eat P um p O peration
w ith only C om pr Loc k out )
Aux Lockout
T em perature
IPN0221
≠0
C om pr Lockout
T em perature
IPN 0220=
0
B oth C om pres s or H P
and A ux iliary H eat
C om pres s or H P O nly
O
u
td
o
o
r
T
e
m
p
e
ra
tu
re
40 to 60F (4.5 to 15.5C )
IP N0210 = 2 (H eat P um p O peration
w ith only A ux Loc k out)
Aux Lockout
T em perature
IPN0221
≠0
C om pr Lockout
T em perature
IPN0220
≠0
A ux iliary H eat O nly
B oth C om pres s or H P
and A ux iliary H eat
C om pres s or H P O nly
O
u
td
o
o
r
T
e
m
p
e
ra
tu
re
40 to 60F (4.5 to 15.5C )
15 to 45F (-9.5 to 7.0C)
IP N0210 = 2 (H eat P um p O peration
w ith C om pr and A ux Loc k out )
Both Compressor and Auxiliary
Lockout Enabled
Compressor Lockout Disabled and
Auxiliary Lockout Enabled
Compressor Lockout Enabled and
Auxiliary Lockout Disabled