background image

WSHP-SVX02C-EN

29 

Wiring

Figure 10.

Deluxe 24V - single circuit - single phase

Summary of Contents for Axiom EXW

Page 1: ...installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equi...

Page 2: ...ted or unsaturated HFCs and HCFCs Important Responsible Refrigerant Practices Trane believes that responsible refrigerant practices are important to the environment our customers and the air condition...

Page 3: ...put on all PPE in accordance with OSHA NFPA 70E or other country specific requirements for arc flash protection PRIOR to servicing the unit NEVER PERFORM ANY SWITCHING DISCONNECTING OR VOLTAGE TESTING...

Page 4: ...ning and Flushing the Water Loop 13 Using Antifreeze 14 Field Installed Power Wiring 14 Main Unit Power Wiring 14 Control Power Transformer 15 Electrical 16 Pre Start 17 Pre Start up Checklist 17 Unit...

Page 5: ...s not possible the following provisions for outdoor storage must be met Place the unit s on a dry surface or raise above the ground to assure adequate air circulation beneath the unit Cover the unit s...

Page 6: ...essary terminals for field connection The deluxe board is equipped with a random start relay anti short cycle timer brown out protection compressor disable unit safety control diagnostics and a generi...

Page 7: ...0 1 3 208 60 3 4 460 60 3 8 230 60 3 Digit 9 Heat Exchanger Source Side 1 Copper Water Coil 2 Cupro Nickel Water Coil Note Heat Exchanger for the Load Side is Copper Water Coil ONLY Digit 10 Current D...

Page 8: ...3 EXWE240 1222 1156 Unit Location and Clearances Locate the unit in an indoor area The ambient temperature surrounding the unit must not be less than 45 F Do not locate the unit in areas subject to fr...

Page 9: ...Figure 2 EXWE060 Dimensions and Clearances WSHP SVX02C EN 9...

Page 10: ...Figure 3 EXWE120 Dimensions and Clearances 10 WSHP SVX02C EN...

Page 11: ...Figure 4 EXWE240 Dimensions and Clearances WSHP SVX02C EN 11...

Page 12: ...local codes Low Voltage Wiring Requirements 9 Connect properly sized control wiring to the proper termination points between the field supplied thermostat and the terminal strip located in the equipm...

Page 13: ...ormerly occupied by the air that is bled off 3 With the air vented and the water circulating the entire system should be checked for leaks with repairs made as required 4 Operate the supplementary hea...

Page 14: ...s Pipe Gallons per 100 Ft Minimum Flush GPM PE 3 02 3 8 1 PE 4 73 6 0 1 PE 7 55 9 5 1 PE 9 93 13 0 2 PE 15 36 21 0 Field Installed Power Wiring WARNING Hazardous Voltage Disconnect all electric power...

Page 15: ...ductors Distance from unit to control Recommended wire size 000 460 feet 18 gauge 461 732 feet 16 gauge 733 1000 feet 14 gauge Table 5 Deluxe controller diagnostic LEDs Color Green Color Red LED1 LED2...

Page 16: ...60 1 207 254 27 6 27 6 158 0 1 34 5 60 208 60 3 187 229 18 1 18 1 137 0 1 22 6 40 460 60 3 414 506 9 0 9 0 62 0 1 11 3 20 230 60 3 207 254 18 1 18 1 137 0 1 22 6 40 EXWE120 208 60 1 197 229 55 2 27 6...

Page 17: ...rigerantheatexchanger along with air purging from the water to refrigerant heat exchanger be done in accordance with the Closed Loop Ground Source Heat Pump Systems Installation Guide Is vibration iso...

Page 18: ...ircuit 4 Check the cooling refrigerant pressures against values in Operating Data p 19 5 Turn the system control switch to the OFF position Unit should stop running and the reversing valve should de e...

Page 19: ...13 15 0 11 1 9 11 117 135 232 296 10 0 4 1 16 20 80 10 0 5 3 14 18 127 147 251 320 15 0 8 3 11 14 10 0 5 3 14 18 127 146 236 300 10 0 4 1 17 22 15 0 10 8 10 13 139 159 256 326 15 0 8 3 11 15 15 0 10 8...

Page 20: ...0 5 2 8 10 110 10 0 5 0 11 14 91 105 408 520 15 0 10 5 6 7 10 0 5 0 11 15 97 111 410 522 10 0 5 2 8 10 15 0 10 2 7 9 91 105 403 513 15 0 10 5 6 7 15 0 10 2 8 10 97 111 404 515 75 10 0 4 7 13 16 70 10...

Page 21: ...0 0 6 4 30 39 80 10 0 7 5 28 36 131 151 254 323 15 0 13 2 20 26 10 0 7 5 29 37 131 150 236 300 10 0 6 4 33 41 15 0 15 1 20 26 143 164 259 329 15 0 13 2 22 28 15 0 15 1 21 26 142 164 240 305 90 10 0 6...

Page 22: ...7 7 18 23 110 10 0 6 1 21 27 90 104 420 534 15 0 15 6 13 16 10 0 6 1 22 28 96 110 421 536 10 0 7 7 18 23 15 0 12 5 14 18 90 104 406 517 15 0 15 6 13 16 15 0 12 5 15 19 95 110 407 518 75 10 0 7 0 26 33...

Page 23: ...293 10 0 4 6 61 77 80 40 0 4 7 13 17 127 146 252 321 15 0 9 4 41 52 40 0 4 7 13 17 126 146 235 299 10 0 4 6 65 82 60 0 9 5 9 12 137 158 256 326 15 0 9 3 43 55 60 0 9 5 10 12 136 157 238 302 90 10 0 4...

Page 24: ...54 90 40 0 4 1 13 16 118 135 335 426 15 0 9 8 30 38 40 0 4 1 14 17 126 145 339 431 10 0 4 8 43 54 60 0 8 5 9 11 117 135 321 408 15 0 9 8 30 39 60 0 8 5 9 12 126 145 324 412 10 0 4 8 37 47 110 40 0 3 9...

Page 25: ...y check out the system and units before and during start up This form need not be returned to the factory unless requested during technical service support MODE Heat Cool Source Load Source Load Enter...

Page 26: ...ale This service should be performed by an experienced service person WARNING Hazardous Chemicals Coil cleaning agents can be either acidic or highly alkaline and can burn severely if contact with ski...

Page 27: ...conditioned space the unit may not start in cool weather approximately 45 F It may then be necessary to startthe unit in the cooling mode for three to five minutes The unit may then be shut off there...

Page 28: ...M X Water too cold Increase temperature X X Undercharged with refrigerant Increase charge X X Defective pressure switch Replace X X Heat transfer fluid too cold Raise water temperature Freezestat open...

Page 29: ...WSHP SVX02C EN 29 Wiring Figure 10 Deluxe 24V single circuit single phase...

Page 30: ...Figure 11 Deluxe 24V dual circuit three phase Wiring 30 WSHP SVX02C EN...

Page 31: ...startup not to exceed 18 months from shipment Extended Warranty The optional extended warranty is a second through fifth yearwarranty The time startsatthe endofstandard1 year coverage through the fift...

Page 32: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Reviews: