Tradewinds RNC15 Installation Instructions Manual Download Page 7

7

Stale Air Exhaust System

The stale air exhaust system draws air from the points in
the house where the worst air quality problems occur.
Stale air ducts should be installed in the bathroom,
kitchen, and laundry room. Applications such as green-
houses, atriums, swimming pools, saunas, etc. have
unique ventilation requirements which should be
addressed with an isolated ventilation system. Also, the air
handler return duct may be used to exhaust from. In this
method, the exhaust air is not ducted back to the HRV
with "dedicated lines" from bathrooms, kitchens, etc.
Instead, the exhaust air is drawn out of the cold air return
of the air handler.

The air handler blower must be run-

ning when the unit is operating for this system to be
effective.

Balancing Dampers and Grilles

Balancing dampers and/or adjustable grilles should be
used to balance the flow rates into and out of various
rooms.

Grilles or diffusers should be positioned high on the wall or
in the ceiling. Kitchen exhaust grilles must never be con-
nected to a range hood. They should be installed at least 4
feet (1.2m) horizontally away from the stove. A hinged
6”X10” (150 X 250mm) rectangular kitchen exhaust grille
is available as part number. This grille includes a remov-
able grease filter. Canadian building codes require that
kitchen grilles be equipped with washable filters.

Field-supplied balancing dampers should be installed
external to the unit to balance the amount of stale air
being exhausted with the amount of fresh air being
brought into the house. Refer to Air flow Balancing sec-
tion.

The Round Diffuser is available in

4" (100mm)
5” (125mm)
6" (150mm)
8" (200mm)

Drain Connection (HRV Only)

During a defrost cycle, the HRV may produce some con-
densation. This water should flow into a nearby drain, or
be taken away by a condensate pump.

The HRV cabinet has prepunched holes for the drain (see
below). Insert the drain spout through the hole in the drain
pan. Do not forget the “O ring” which seals each spout to
the pan.

REMEMBER TO HAND TIGHTEN ONLY

the

washer and lock nut which hold the drain spout in place.

Construct a P-Trap using the plastic tee connector. Cut
two lengths of hose and connect each piece to an end of
the “T” fitting, then connect the other ends to the two drain
spouts. Position the "T" fitting to point upward, andconnect
the drain line. Tape or fasten base to avoid any kinks. This
creates a “trap” which will hold some condensate and pre-
vent odors from being drawn up the hose and into the
fresh air supply of the HRV.

Round
Diffusers

Kitchen Grille

REMOVABLE

FILTER

CAUTION

DRAIN

SPOUT

ZIP  TIE

TO DRAIN

TEE

CONNECTOR

DRAIN

SPOUT

PRE-PUNCHED HOLES (2)

DRAIN PAN

DRAIN PAN

1/2 " I.D. 

DRAIN HOSE

DRAIN HOSE PLUMBING

DRAIN

SPOUT

DRAIN

SPOUT

TO DRAIN

1/2" HARD PIPE

TEE

JOINT

PRE-PUNCHED HOLES (2)

DRAIN PAN

DRAIN PAN

HARD PIPE PLUMBING

"P" Trap (HRV only)

Note: Secondary drain pan may be required to 
protect from condensate leakage.

The HRV and all condensate lines must be 
installed in a space where the temperature is 
maintained above the freezing point or freeze 
protection must be provided. 

CAUTION

Summary of Contents for RNC15

Page 1: ...ains removable grease filter Heat Recovery Ventilators HRV are designed to provide fresh air while exhausting an equal amount of stale air The HRV is equipped with an aluminum core The device uses the...

Page 2: ...min 100 length max 99 186 Weather Hoods 2 6 150mm c w 1 4 6mm screen 99 116 Dehumidistat Ventilation Control Dehumidistat with ON OFF 99 130 Dehumidistat Control Dehumidistat All units conform to CSA...

Page 3: ...e wire min 100 length max 99 186 Weather Hoods 2 6 150mm c w 1 4 6mm screen 99 116 Dehumidistat Ventilation Control Dehumidistat with ON OFF 99 130 Dehumidistat Control Dehumidistat All units conform...

Page 4: ...Weatherhood Location and Installation Weatherhood kit includes two fixed cover hoods with a 1 4 6mm mesh screen Exhaust Weatherhood Requirements At least 6 2 m from the ventilation air intake At least...

Page 5: ...e exhaust weatherhood At least 6 2 m away from dryer vents and air handler exhaust medium or high efficiency furnaces A minimum of at least 6 2 m from driveways oil fill pipes gas meters or garbage co...

Page 6: ...ated duct should be connected between the HRV and the supply exhaust duct system The main supply and return lines to from the HRV must be 6 inches 150mm minimum Branch lines to the individual rooms ma...

Page 7: ...of stale air being exhausted with the amount of fresh air being brought into the house Refer to Air flow Balancing sec tion The Round Diffuser is available in 4 100mm 5 125mm 6 150mm 8 200mm Drain Co...

Page 8: ...e grade minimum 5 Due to the differences in pressure between the HRV and the epuipment it is being connected to the HRV s airflow must be confirmed on site using the balancing procedure found in this...

Page 9: ...be made by a quali fied service technician Low voltage wires from the remote controls are connected to the HRV micro processor board In order to prevent electric shock when cleaning or servicing the H...

Page 10: ...oltage Connect one per HRV only Connects to red black and orange Part No 99 116 REMOTE DEHUMIDISTAT requires 2 wires anywhere humidity is a concern provides high speed ventilation when humidity level...

Page 11: ...he OFF position Changing the remote control from OFF to STANDBY can be achieved by Setting the DIP Switch as per Figure 2 Figure 2 DIP Switch Settings for Standby When using a Remote Control Device th...

Page 12: ...ECTOR BI DIRECTIONAL DAMPER MOTOR ORANGE RED BLACK ORANGE Model RNC5 Only 12VAC P4 N C COMMON N O TO MOTOR K1 K2 K3 K4 3 4 AMP FUSE CR1 C1 VDR1 VDR2 VDR3 AUTO TRANS T9 T8 T6 T5 T4 T3 T2 P1 SPARE FAN O...

Page 13: ...t the Interface relay contacts from initializing the condenser unit This problem can occur at the thermostat because the Y termi nal is connected to the G terminal internal to the stat When R and G ar...

Page 14: ...idity levels are in a range from 30 to 45 The dehumidistat switches the ventilator to high speed when the moisture level in the building exceeds the desired setpoint The dehumidistat switches the HRV...

Page 15: ...istances but the actual installation may limit the amount of straight duct The Pitot tube should be connected to a magnehelic gauge or digital manometer capable of reading from 0 to 0 25 in 0 62 Pa of...

Page 16: ...ng Damper Field supplied Balancing Damper optional Placement of Pitot Tube HRV MAGNEHELIC DUCT AIR FLOW Pitot tube High Pressure Side Low Pressure Side Magnehelic gauge Pitot Tube and Gauge Pitot Tube...

Page 17: ...increase the speed of the HRV have contractor balance HRV locate the grilles high on the walls or under the baseboards install ceiling mounted diffuser or grilles so as not to directly spill the supp...

Page 18: ...ops on the back of the cabinet NOTE Core will appear to stick out from cabinet approxi mately 1 8 3mm This is designed this way so that the access door will fit tight against the core 4 Motors Mainten...

Reviews: