TRADEFORCE TRFSD240PE Installation And User Manual Download Page 17

15

9.        9V TERMINAL AND REMOTE TEST & HUSH

WARNING: THIS TERMINAL IS NOT ISOLATED FROM THE MAINS SUPPLY.

This first terminal (Yellow) has a 9Vdc positive output and can be used for the following

applications:  As an output to operate smoke alarm as an early warning indicator system.          

The 9V terminal in this smoke alarm is intended for use with a security/fire alarm
panel where a signal from that panel can be used to activate a single Smoke Alarm or
interconnected Smoke Alarms to alert residents/occupants that an alarm has been
activated elsewhere and there may be cause to evacuate the area. The diagram below
shows the 9V terminal and the Signal terminal, marked SW, connected to the N/O
(normally open) contacts of a suitable relay, the coil of which when energized from an
extra-low voltage signal from an alarm panel, closes the contacts thereby activating the
Smoke Alarm(s). This can be an Early Warning Indicator System.

Note: The presence of an audible sound from the smoke alarm and the absence of a

flashing RED LED in the smoke alarm(s), means the smoke alarm(s) have been
activated externally. It is an Early Warning Indicator.

However, check also for the presence of fire or smoke in the vicinity of your

dwellings. If there is fire, follow actions in Section 15.      

It is essential that the relay and associated base must be of a type providing effective

isolation between the coil and contacts (having an isolation voltage [Dielectric
Strength] of 4kV and creep/clearance distances of no less than 8mm between the coil
and contacts). 

We recommend using an OMRON Relay Type G2R-2-SN and Base

Type 17X5W which meet the necessary isolation requirements. 

9.1       

9V TERMINAL

1398-7210-01_v1.qxd:_  2013.5.15  5:25 PM  Page 15

Summary of Contents for TRFSD240PE

Page 1: ...AND OR INTERCONNECTABLE 24 UNITS PHOTOELECTRIC SMOKE ALARM 9V REPLACEABLE BATTERY BACKUP MODEL TRFSD240PE OR BUILT IN RECHARGEABLE BATTERY BACKUP MODEL TRFSD240PERL TEST AND HUSH CONTROLAND LOW BATTE...

Page 2: ...INSTALLATION REPLACEMENT AND TEST 13 9V TERMINAL AND REMOTE TEST HUSH 15 REPAIRS AND SERVICES 19 GOOD SAFETY HABITS 19 THE LIMITATIONS OF SMOKE ALARMS 19 OPERATING PRINCIPLES OF SMOKE ALARMS 21 DEVELO...

Page 3: ...an alarm not located in that room from waking the sleeper 1 7 Smoke heat and other combustion products rise to the ceiling and spread horizontally Mounting the alarm on the ceiling in the center of t...

Page 4: ...both ends of a bedroom hallway or large room if the hallway or room is more than 9m long 1 13 Do not locate smoke alarms in kitchen areas due to potential nuisance alarms from cooking fumes 1 RECOMME...

Page 5: ...alarms as recommended refer to RECOMMENDED LOCATIONS 2 2 In older mobile homes that are not well insulated compared to present stan dards extreme heat or cold can be transferred from the outside throu...

Page 6: ...etector guards unless the combination alarm and guard has been evaluated and found suitable for that purpose 3 AVOID THESE LOCATIONS 4 FALSE ALARMS 4 1 This smoke alarm is designed to minimize false a...

Page 7: ...SAA Wiring Rules AS3000 6 1 2 For model TRFSD240PERL Connecting the smoke alarm on the base plate will activate the lithium battery Please note the long absence of mains power may damage the recharge...

Page 8: ...um of 250 meters 820 feet of wire can be used in interconnect ing smoke alarms 6 1 7 All final sub circuit conductors including the signal conductor must be a mini mum size of 1mm with 250V grade insu...

Page 9: ...e SW SWITCHWIRE FORINTERCONNECTIONONLY Blue N NEUTRAL Orange LOOP DEAD TERMINAL WARNING Connecting the Switch wire terminal to any other supply conduc tor may result in damage to the alarm failure to...

Page 10: ...ge the alarm 6 1 19 PSA recommend the smoke alarms to be installed on its own subcircuit to avoid false alarms and nuisance chirping that may be caused by electromag netic interferences from other ele...

Page 11: ...lly away from the base plate to remove the smoke alarm Figure 2 To connect smoke alarm 1 Place smoke alarm in line with the base plate 2 Push smoke alarm towards connec tor A Ensure the smoke alarm sl...

Page 12: ...es into alarm indicat ing that products of combustion have been detected Red LED will latch on solid state for about 5 minutes after the alarm stop After the 5 minutes the red LED will diminish For in...

Page 13: ...will silence immediately and c h i r p every 32 seconds for approximately 5 min utes to indicate the alarm is in the temporary desensitized condition 7 2 4 The smoke alarm will automatically reactiva...

Page 14: ...s Alarm mode Red Light is OFF Smoke alarm activated Smoke alarm in full alarm Other interconnected units may have activated the alarm Check other smoke alarms or devices Hush mode Green light ON Red l...

Page 15: ...d intervals 8 1 3 Replace battery when chirping occurs To ensure proper operation the bat tery should be replaced once a year 8 1 4 To replace battery remove alarm from mounting base see section 6 2 a...

Page 16: ...should sound the alarm 8 2 3 If the battery module has a fault the alarm will chirp every 32 seconds 8 2 4 Watch the Red LED for about 32 seconds It should flash at least once 8 2 5 Switch on mains po...

Page 17: ...ergized from an extra low voltage signal from an alarm panel closes the contacts thereby activating the Smoke Alarm s This can be an Early Warning Indicator System Note The presence of an audible soun...

Page 18: ...d the relay must be installed in accordance with the relevant requirements of the SAA Wiring Rules AS3000 for low voltage 240V conductors LOOP N SW A 9V LOOP N SW A 9V LOOP N SW A 9V 1 2 24 YELLOW RED...

Page 19: ...red for the Remote Test and Hush Plate In order for this alarm to op erate properly with the LIFTHP a Remote Test Hush card LIFTHC is required for each alarm in the interconnected system See the owner...

Page 20: ...he Remote Test Hush Plate can be mounted in an easy to reach location to provide convenient access to the Test and Hush functions of your Models TRFSD240I TRFSD240PE TRFSD240PERL smoke alarm Connectio...

Page 21: ...n sensing alarm may detect invisi ble fire particles associated with fast flaming fires sooner than photoelectric alarms photoelectric sensing alarm may detect visible fire particles associ ated with...

Page 22: ...by providing early warnings of a fire they are not a substitute for an insurance policy 12 10 This smoke alarm alone will not alert the hearing impaired Use special purpose smoke alarm with lights or...

Page 23: ...ains power where appli cable or the battery would pass through the gap with ease without causing any alarm However in the event of particles arising from combustion or dust particles refer il lustrati...

Page 24: ...14 DEVELOPAND PRACTICE A PLAN OF ESCAPE 13 OPERATING PRINCIPLES OF SMOKE ALARMS BASIC OF ESCAPE PLAN 14 1 Make a floor plan indicating all doors and windows and at least two escape routes from each r...

Page 25: ...N OF ESCAPE 15 WHAT TO DO WHEN THE ALARM SOUNDS 15 1 Alert small children in the home 15 2 Leave immediately by your plan of escape Every second counts so don t waste time getting dressed or picking u...

Page 26: ...hirp until the battery is fully charged 16 4 If the alarm chirps again press the Test button to check the battery condition 16 5 If chirps persists replace smoke alarm and return to your supplier for...

Page 27: ...This smoke alarm has an expected service life of 10 years under normal conditions We recommend that you should replace the smoke alarm after 10 years from installation date to ensure normal operation...

Page 28: ...HISSMOKEALARMHASBEENTESTEDANDCOMPLIESTO AS3786 DEAR ELECTRICIAN PLEASE LEAVE THIS MANUAL FOR THE OWNER THANK YOU FOR CHOOSING THIS SMOKE ALARM 1398 7210 01 1398 7210 01_v1 qxd _ 2013 5 15 5 25 PM Page...

Reviews: