7.9.12 Lower limit switch / Upper limit switch
Availability
PNO CLASS1 16 + 32
PNO CLASS2 16 + 32
TR-Mode Position
X TR-Mode Po Rpm. X
not supported!
not supported!
If the status switched on (see Teach-In function page 113) the measuring system can
inform the master via a bit whether the actual value is within the limits.
Limit switch bit = 0
actual value
lower limit or actual value
upper limit
Limit switch bit = 1
actual value < lower limit or actual value > upper limit
lower limit
0
upper limit
programmed total measuring length in increments
– 1,
within
33 554 432
default
Lower limit switch = 0, Upper limit switch = 4096
7.9.13 Data bits SSI-Interface
Availability
PNO CLASS1 16 + 32
PNO CLASS2 16 + 32
TR-Mode Position
X TR-Mode Po Rpm. X
not supported!
not supported!
Defines the number of data bits on the SSI interface.
Output format: MSB left-justified
lower limit
8
upper limit
32
default
24
7.9.14 Velocity [1/x rpm]
Availability
PNO CLASS1 16 + 32
PNO CLASS2 16 + 32
TR-Mode Position
TR-Mode Po Rpm. X
not supported!
not supported!
not supported!
With this parameter, the specified rotational speed can be scaled in arbitrary steps
between 1/1 and 1/100 revs./min.