GENERAL MAINTENANCE 

Housing: 

The SP670 can be wiped down with a damp lint free cloth. Do not use any cleaning agents 

including solvent or soap. 

 

Battery Replacement: 

When the LED indicator blinks Red the batteries need to be replaced. 

1.

 

Turn the SP670 off. Loosen the battery cover screw and open the cover. 

2.

 

Remove the three AAA batteries from the battery holder. 

3.

 

Install three new AAA alkaline batteries into the holder observing correct polarity. Note: 

Battery level is displayed in the Smart Probe app. 

 

Schrader Depressor and Gasket: 

The white gasket that seals the SP670 probe to a service port can 

wear over time causing leaks. In addition the Schrader depressor can also wear or be damaged. 

Overtightening or connection to damaged ports can also cause this. 
 

Follow these steps to replace the Schrader depressor and/or the gasket. 

 

1.

 

Using needle nose pliers, grasp the Schrader 

depressor and turn valve counter clockwise. 

 

 

 

 

 

 
 

 

 

 

 

2 Remove and replace the Schrader depressor 

and/or the worn gasket. 

 

 

 

 
 

 

 

 

 

3 Install the gasket and screw in the Schrader depressor. (New Schrader depressor and gasket are 
part number A670) 

 

Summary of Contents for SP670

Page 1: ...SP670 Smart Pressure Probe Instruction Manual Scan to download the TPI View app ...

Page 2: ...P323 smart temperature clamps allow superheat and sub cooling to be calculated 1 Turn on each SP670 and SP323 open the app and allow the smart probes to connect 2 Connect the probes to the Suction low side and Liquid high side lines 3 Tap on Refrigeration in the app For the Suction Line tap on Pressure Select to assign the SP670 connected to the suction line from the available devices Repeat this ...

Page 3: ...ower off When connected to a smart device the auto power off is disabled SCHRADER VALVE DEPRESSOR ADJUSTMENT The SP670 uses an adjustable Schrader valve depressor This is useful for use on worn Schrader valves If the depressor is unable to engage the valve enough to open it the SP670 depressor can be adjusted outward to make better contact 1 Using needle nose pliers carefully turn the Schrader val...

Page 4: ...ote Battery level is displayed in the Smart Probe app Schrader Depressor and Gasket The white gasket that seals the SP670 probe to a service port can wear over time causing leaks In addition the Schrader depressor can also wear or be damaged Overtightening or connection to damaged ports can also cause this Follow these steps to replace the Schrader depressor and or the gasket 1 Using needle nose p...

Page 5: ... scale Battery Life Approximately 160 hours Battery Type AAA x 3 alkaline Operating Temperature 32 F to 122 F 0 C to 50 C Storage Temperature 4 F to 140 F 20 C to 60 C Humidity 0 to 80 RH Weight 5 64oz 160g Bluetooth 5 0 350 foot range depending on obstacles See www tpieurope com for CE and UKCA Certificate of Conformity FCC ID QOQBGM113 IC Industry Canada ID 5123A BGM113 209 J00204 ...

Page 6: ...expenses to the company are not covered Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitations or exclusions may not apply to you To Obtain Warranty Performance Include with the product your name address phone number written description of the problem and proof of purchase date Carefully package and return to TPI Inc TPI Canada TPI Euro...

Page 7: ...applicable This warranty gives you specific legal rights and you may also have other rights which vary from state to state NOTES ...

Page 8: ...www testproductsintl com Test Products International Ltd 342 Bronte Road South Unit 6 Milton Ontario Canada L9T 5B7 Tel 905 693 8558 www tpicanada com Test Products International Europe Ltd Rutherford Way Industrial Estate Rutherford Way Manor Royal Crawley West Sussex RH10 9LN www tpieurope com ...

Reviews: