THERMAL CUTOUT 

(480 volt models)

If for any reason temperatures increase beyond normal
limits, safety thermal limit will open de-energizing heat-
ing element and fan motor.  Check entire installation to
determine cause of overheating and take corrective
measures.  The limit control is the automatic reset type
and after cooling will reset, allowing heater to resume
operation.

CAUTION: 

To avoid the risk of fire, shock or personal

injury; do not insert or allow any foreign objects or
hands to enter any ventilation or exhaust openings.

THERMAL CUTOUT OPERATION
(WITH ZERO-VOLT RESET)

To reset thermal cutout disconnect all power for 5
minutes then energize unit.  If fault continues discon-
nect power and check for causes.

THERMAL CUTOUT OPERATION
(WITH CAPILLARY MANUAL RESET)

To reset thermal cutout, first disconnect power from
the unit allowing time to cool, locate the two 1/4” dia.
openings in the front grille.Using a small screwdriver
or pencil press the reset button (with minimal amount
of force) through the 1/4” opening, then restore power
to the unit. If fault continues disconnect power and
check for causes.

THERMAL CUTOUT IDENTIFICATION

All 480V Models employ a automatic limit control.
208, 240 and 277V models may employ zero-volt or
capillary manual reset limit control.
Models with capillary type manual reset limit control.
This device is located on the heater venturi (bottom of
unit as installed) with the capillary routed around the
outside of the element assembly.

2

3480 / RCH SERIES CEILING HEATER

WIRING DIAGRAMS: 

Shown on pages 4, 5, 6 and 7

WD-1, -3, -5, -7, -9, -11, -13, -15, -17 and -19 are dia-
grams of units that employ (zero-volt) manual reset limit
control devices.
WD-2, -4, -6, -8, -10, -12, -14, -16, -18 and -20 are dia-
grams of units that employ (capillary) manual reset limit
control devices.

OPTIONAL LOUVERED DIFFUSER

             

The factory installed louvered diffuser  can be

            adjusted to direct air flow as desired. If necessary the
            louvered diffuser can be rotated 90 degrees by
            removing the four mounting scews and turning the
            louvered diffuser to the desired position and attaching
           to the grille. Care must be taken to align the notched
           corners of the diffuser frame with the reset holes in the
            grille. The louvered diffuser cannot be used in
            conjunction with the standard circular outlet.

Summary of Contents for 3480 Series

Page 1: ...uld be installed so the flanges of the can are even with the interior finish or ceiling line 3 For plaster or other similar finish ceilings attach the PT3480 accessory plaster frame to the recessed ca...

Page 2: ...wer to the unit If fault continues disconnect power and check for causes THERMAL CUTOUT IDENTIFICATION All 480V Models employ a automatic limit control 208 240 and 277V models may employ zero volt or...

Page 3: ...J3485 K3485 P3482 P3483 P3484 P3485 Y3484 Y3485 208 1 240 1 277 1 208 1 240 1 277 1 208 1 240 1 277 1 208 1 240 1 277 1 208 3 240 3 208 3 240 3 480 1 480 1 480 1 480 1 480 3 480 3 2000 2000 2000 3000...

Page 4: ...08 240 OR 277V HEATERS WD 1 WD 2 WD 3 WD 4 WD 5 WD 6 WIRING DIAGRAM FOR SINGLE PHASE 208 240 OR 277V HEATERS WITH DISCONNECT SWITCH WIRING DIAGRAM FOR SINGLE PHASE 208 240 OR 277V HEATERS WITH DISCONN...

Page 5: ...R R1 OR R2 option NOTE CONTROL VOLTAGE R LINE VOLTAGE R1 24 VAC R2 120 VAC WIRING DIAGRAM FOR SINGLE PHASE 208 240 OR 277V HEATERS WITH CONTROL RELAY FAN DELAY AND DISCONNECT SWITCH R R1 OR R2 option...

Page 6: ...VOLTAGE CONTROL COIL AND FAN DELAY WIRING DIAGRAM FOR THREE PHASE 208 240V HEATERS WITH DISCONNECT SWITCH RELAY WITH LINE VOLTAGE CONTROL COIL AND FAN DELAY WD 17 WD 18 WIRING DIAGRAM FOR THREE PHASE...

Page 7: ...K WHITE 277V ONLY REMOTE MTD RELAY BLACK BLUE YELLOW HEATER SUPPLY 1 208 240V TO LOW VOLTAGE ROOM THERMOSTAT 57912 002 F 208V 57912 003 H 240V CRIMP NUT WD 19 WD 20 RELAY CONNECTION CONNECT THE YELLOW...

Reviews: