tozen PRV-CPR Instruction Manual Download Page 8

7.

Cause & Counter Measure Of Malfunction 

Condition Possible 

Cause 

Countermeasure 

Outlet side   
pressure increase 
 

The valve body have plenty of air 

Please relief the air out of the 
valve body.   
Refer to 5. Operation Manual. 

Foreign Particles stuck in the valve 
(Stick at seat ring, shield ring, Pilot valve's 
seat ring and shield ring) 

Remove the foreign particles. 

Part's Damage 
(Seat ring, shield ring, Pilot valve's seat ring 
and shield ring) 

Exchange the main body shield 
ring, and pilot valve shield ring.
PRV main body seat ring, pilot 
valve body seat ring part if 
serious damage, please exchange 
the part. 

The valve body's stem can't operate 
smoothly. 
(Stem, seat, guide bush) 

Use cloth file to filing the stem, 
make it smooth to operate. 

Pilot valve's diaphragm damaged. 

Exchange the part 

Strainer clogging 

Clean the strainer mesh 

Outlet side   
pressure does not 
rise 

The valve body's stem can't operate 
smoothly. 
(Stem, seat, guide bush) 

Use cloth file to filing the stem, 
make it smooth to operate. 

Wrong selection of the sizes   
(Nominal diameter too small) 

Reconfirm the specification and 
change the nominal diameter 
sizes. 

Piping resistance too big 

Checking the piping 

Operation Failure 
(Pulsation, 
vibration, 
pressure 
unstable) 

Air pocket in the piping 

Proceed to relief the air, or install 
the air vent 

Wrong selection of the sizes 

Reconfirm the specification and 
change the nominal diameter 
sizes. 

Pressure reduction ratio too big 

Do two steps pressure reducing 

Poor adjustment of the needle valve 

Small  opening  of  the  needle 
valve, the disc assembly of the 
PRV body easy to operate and 
also insensitivity easily.   
If opening too big, the disc 
assembly of the valve body,   
operation easily become 
 unstable and acutely. 

 
 

 

Summary of Contents for PRV-CPR

Page 1: ...20201203 PRV CPR Pressure Reducing valve Instruction Manual...

Page 2: ...on Manual 5 1 Precaution 5 2 Procedure Maintenance Manual Cause Counter Measure Of Malfunction Sizes Selection Diagram Sizes Selection Diagram Pressure Reducing Valve When Pilot Valve Fully Open Flow...

Page 3: ...of the diaphragmin the pilot valvepressure increase the discassembly of the pilot valve will rise and the pilot valve will closed Thepilotvalveclosed theupperpartofthediaphragminthePRVbodypressurewil...

Page 4: ...y the surrounding and there is a risk to get hurt Caution Remove the foreign matters in the pipe line before install the valve The valve can t have the original performance and may damage if foreign p...

Page 5: ...on failure Toavoidpipefreezing drainthepipewaterandthermalinsulationthepipe By freezing may damage the valve Pleasesecuretheinstallationspace referto4 3InstallationSpace When doing maintenance and ins...

Page 6: ...terflow makesureallthepipeworkbeenproperinstalled If the water spouting off the pipe line it may dirty the surrounding and there is a risk to get hurt Caution Remove the foreign particles in the pipe...

Page 7: ...er out from the valve body outlet side pressure become zero only can proceed If the water spouting off the pipe line it may dirty the surrounding and there is a risk to get hurt Caution To maintain th...

Page 8: ...damaged Exchange the part Strainer clogging Clean the strainer mesh Outlet side pressure does not rise The valve body s stem can t operate smoothly Stem seat guide bush Use cloth file to filing the st...