DESIGNATED TEMP.
(super low)
10min.
6min.
(super low)
(super low)
(super low) (super low)
INDOOR FAN
COMPRESSOR
0.7
2.0
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
10min.
6min.
3min.
DRY MODE OPERATION
1. When the room temperature is +2
°
C (or more) higher than designated temperature, compressor and indoor
fan operate.
2. When the room temperature has been cooled to the tempe2
°
C higher than the designated, the
compressor and indoor fan start intermittent operation, ON (for 10 min.) and OFF (for 6 min.) by turns.
The air flow speed of indoor fan is super low.
3. When the room temperature is cooled to designated temperature, compressor and indoor fan stop.
The indoor fan restarts at the air flow speed of super low, after 3 minutes the compressor stops.
4. When the room temperature is raised to +0.7
°
C higher than the designated temperature, the intermittent
operation above #2 starts.
5. When operating in #2 above, if the room temperature b2.7
°
C higher than the designated, the
operation #1 above starts.
OPERATION DETAILS