27
4
3
High
Low
1
Medium
1.5
8.4.2.4 Condenser temperature protection
---55 <T3<60 , the compressor frequency will decrease to the lower level until to F1 and then runs at
F1.If T3<54 , the compressor will keep running at the current frequency.
---T3<52 , the compressor will not limit the frequency and resume to the former frequency.
---T3>60 for 5 seconds, the compressor will stop until T3<52 .
8.4.2.5 Evaporator temperature protection
---T2<0 , the compressor will stop and restart when T2
>=
5 .
---0
℃≦
T2<4 , the compressor frequency will be limited and decreased to the lower level
---4
≤
T2
≤
7 , the compressor will keep the current frequency.
---T2>7 , the compressor frequency will not be limited.
8.4.3 Heating Mode
8.4.3.1 Compressor running rules
The maximum operation frequency of the compressor after starting submits to the following rule.