6. E5 malfunction
7. E6 malfunction (Only for 30K, 36K & 48K with 1 phase)
E5 display
Voltage protection of compressor
Check the voltage of outdoor unit power supply, whether the voltage
between L(1) and N is about 172-265V
No
Replace the power board, then check whether the system can run normally
Check the power supply
Yes
Replace outdoor main board
Yes
Trouble is solved
No
E6 display
PFC module protection
Check whether the connecting line between main
board and the PFC module is connected tightly
No
Connect it tightly, check normal or not
Yes
Check whether the voltage between P
and N of IPM module is 380-390V
No
Yes
Replace the outdoor main board
No
Replace the PFC module
Summary of Contents for CCT 100 INV-Ri
Page 6: ...TLC I 2011 1 4 2 External Appearance 2 1 Indoor units Ceiling Floor...
Page 8: ...TLC I 2011 1 6 3 Nomenclature...
Page 10: ...TLC I 2011 1 8 Part 2 Indoor Units 1 Ceiling and Floor Type 9...
Page 21: ...TLC I 2011 1 20 3 Dimensions...
Page 23: ...TLC I 2011 1 22 5 Wiring Diagrams CFT 35 INV Ri...
Page 26: ...TLC I 2011 1 25 Discharge angle 60e e e e FLOOR Airflow velocity Temperature...
Page 37: ...TLC I 2011 1 124 2 Service Space...
Page 39: ...TLC I 2011 1 126 4 Wiring Diagrams CCT 301 INVo CFT 35 INV Ro DCT 35 INV So...
Page 43: ...TLC I 2011 1 132 For 36000 60000Btu h with 3 phase outdoor unit...
Page 46: ...TLC I 2011 1 146 9 Operation Limits...
Page 65: ...TLC I 2011 1 219 Wiring 1 Control 220 2 Wiring 221 3 Test operation 222...
Page 70: ...TLC I 2011 1 225...
Page 71: ...TLC I 2011 1 227 For model 36 60 with 3 Phase outdoor unit...
Page 72: ...TLC I 2011 1 228...
Page 73: ...TLC I 2011 1 231 Part 5 Control 1 Standard Controller...