Mounting: 

 

 
OPERATION: 

 

 

The power and movement detection indication

: The LED will flash once every  4 seconds after 

power ON of the unit, and will flash every 2 seconds when the units detects the movement.  

 

Detection field

: The detection field is made up of up and down, left and right service field. (See 

the following diagram). But it has the relation ship between the sensitivity and the orientation of 

moving. Detection distance may vary according to the installation position and detection field. 

 

Time-delay adjustment

:  The timer knob can be set according to the customer needs. The 

minimum is 30 sec. and the maximum is 450 sec delay OFF.

 

 

 

Identifies day and night automatically

: When the trimmer knob is turned towards SUN Position 

(max), it will switch ON  lights both in  day and night. When turned towards MOON position (min), 

the sensor will operate only at night (less than 10LUX ambient light) 

 

Correct Moving Orientation

Incorrect Moving Orientation

At a distance closer to sensor the detection motion speed can 

be minimum and vice versa

 

 

 

 

Summary of Contents for T 76 251

Page 1: ...ilt timer to switch OFF the load when there is no human movement The device is also incorporated with Lux detector Applications Movement sensors can be installed in Office Hotel corridors Stair cases Passage Stores Classrooms Common fresh rooms SPECIFICATIONS Supply voltage 110 250V AC Supply frequency 50 60 Hz Rated load 1200W resistive Detection angle 360 Detection distance 10 feet radius with n...

Page 2: ...epute If required connect 2 2uF 440V AC Fan Capacitor across CFL with electronic ballasts to avoid blinking of lamps when it is OFF Connect upto specified wattage of load only For higher loads suitable rated contactor of reputed make can be used Hindrance moving object should not hide the detection window Avoid installing in Bathrooms Make sure air conditioners central heating etc do not cloud IR ...

Page 3: ...ion distance may vary according to the installation position and detection field Time delay adjustment The timer knob can be set according to the customer needs The minimum is 30 sec and the maximum is 450 sec delay OFF Identifies day and night automatically When the trimmer knob is turned towards SUN Position max it will switch ON lights both in day and night When turned towards MOON position min...

Page 4: ...t the connections Turn the lux level adjuster photo fully clockwise Sensitivity is poor Installation height may be high The sensitivity level adjuster may be low side Incorrect moving orientation Obstruction in front of sensor window Install at recommended height Turn the sensitivity level adjuster to high side Correct moving orientation Remove the obstruction in front of the window DIMENSIONS 33 ...