Before installing venting for this unit, the installer should read these instructions to insure that the proper vent configura-
tion has been selected. Use only Town and Country Termination kits #:TCVT.RTA - Roof Termination Kit
Vent system components approved for use with the Town and Country Fireplace are shown on page 21.
Various combinations of vent runs may be used. Refer to (Figure 29) for details. For optimum performance and flame
appearance, keep the vent length to a minimum and limit the number of elbows. Connections between each vent system
component must be tightly joined, secured with sheet metal screws and sealed with high temperature self adhesive tape.
VENT SUPPORTS: A minimum of 1 support every 4’ must be used.
CAUTION: UNDER NO CONDITION SHOULD COMBUSTIBLE MATERIAL BE CLOSER THAN 1 3/4 INCHES FROM
ANY PART OF THE VENT PIPE.
20'
10'
8'
6
40'
MAX.
4'
2'
48'
4' MAX.
'
18 MIN” BEFORE ELBOW
Figure 29: TCWS54CODE Venting chart.
MINIMUM VENT HEIGHT
Various combinations of vent runs may be used.
Refer to (Figure 29) for details. For optimum
performance and flame appearance, keep the
vent length to a minimum and limit the number of
elbows. Connections between each vent system
component must be tightly joined, secured with
sheet metal screws and sealed.
CAUTION:
Under no condition
should combustible
material be closer than
1 3/4 inches from any
part of the vent pipe.
Only 45º elbows can be
used in this vent system.
Maximum number of
elbows is 2.
18
5055.5401-A
TCWS.54CODE_041115-36
Venting
Roof Termination Venting Chart