3
6) Before the water supply is turned on, be sure all stop
valves to the flush valves are closed off tightly. The stop
valves can be opened and closed by using the adjust-
ment screw located at the center of the stop valve cap
G,
behind the adjustment screw cover if already installed.
Stop valve adjustments can only be made by using the
adjustment screw. If for any reason, it becomes necessary
to remove the stop valve cap
G
, be certain that the water
is shut off at the main supply valve.
For new installations, we recommend the following steps:
• Shut off stop valve and remove flushometer cover.
• Lift out the piston valve. Install the flushometer cover
and open the stop valve to flush the line of any debris
and sediment.
After completion, shut off the stop valve, remove the
flushometer cover and reinstall the piston valve. Reinstall
the flushometer cover securely. Open the stop valve and
activate the flushometer valve.
7) Flushometer valves are preset for fixture volume as
marked on the valve cartons. The valve does not require
adjustment for variations in water pressure within its
operating range. To set the flushometer valve for proper
operation, open the stop valve completely by turning the
adjustment screw and flush the Flushometer valve sev-
eral times. Gradually adjust the stop valve down, using
the adjustment screw, so that the rate of water flow into
the fixture is not excessive, yet is sufficient to adequately
evacuate the waste. The final setting for urinals should be
such that the fixture will not overflow when the valve is
actuated several times in succession.
8) The stop cap screw cover should be replaced and tightly
secured after final adjustments have been made.
SPECIFICATIONS
Flush volume:
TMT1NNC - 6.0 LPF (1.6 GPF)
TMW1NNC - 13.3 LPF (3.5 GPF)
TMU1NNC - 3.8 LPF (1.0 GPF)
Protect the chrome or special finish of the flushometer. DO NOT USE TOOTHED TOOLS TO INSTALL OR SERVICE THE
VALVE.
A non-hold open feature is standard on these valves