a t o t a l v i e w o f f i r e
1.11.1
Convection grilles
The convection grilles of the heat chamber, which are
compulsory, shall be fitted as high as possible but less
than 30cm from the ceiling (to be positioned at the level
of the false ceiling).
Concerning the parameters of the convection grilles:
Convection circuit:
- effective cross-section of the convection air inlets: 600
cm² minimum
- effective cross-section of the convection air outlets:
600 cm² minimum
N.B:
It is possible to replace the ventilation grille by a slot with section equal or greater.
The air vents are to be installed above the false ceiling.
Note
:
The convection hot air outlet grilles must open into the room where the fireplace is located.
Air vent
Convection
air intlet grille
Convection air
outlet grille
The air vents allow
ventilation of the false
ceiling. They must be 20
cm² minimum each. They
must be staggered to allow
effective ventilation. One
close to the ceiling and the
other close to the false
ceiling.