20
WX9 ASD Installation and Operation Manual
I/O and Control
The
WX9 ASD
can be controlled by several input types and combinations thereof, as well as operate
within a wide range of output frequency and voltage levels. This section discusses the ASD control
methods and supported I/O functions.
The
Terminal Board
supports discrete and analog I/O functions and is shown in
.
lists the names and the default settings of the input and output terminals of the
Terminal
Board
. See the section titled
Terminal Descriptions on pg. 22
for an expanded description of each
terminal.
Note:
Set the
Command Mode
to
Terminal Board
to use the input control lines of the
Terminal Board
for command input (Program
Fundamental
Standard Mode
Selection
Command Mode Selection
Terminal Board). Output lines of the
Terminal Board
need not be selected to enable the output. However, output lines may
be set to a user-selected function.
shows the typical connection diagram for the
WX9 ASD
system.
Table 2. Terminal Board Terminal Names and Functions.
Default
Term.
Setting
Input/Output
Default Function
(also see
WX9 ASD Terminal Board. on pg. 21
Circuit Config.
ST
Discrete Input
Connect to CC
to activate
(Sink mode)
Switching
applies to
discrete input
terminals only.
Standby
— Multifunctional programmable discrete input. Activation required
for normal ASD operation.
RES
Reset
— Multifunctional programmable discrete input. Resets a faulted ASD.
F
Forward
— Multifunctional programmable discrete input.
R
Reverse
— Multifunctional programmable discrete input.
S1
Preset Speed 1
— Multifunctional programmable discrete input.
S2
Preset Speed 2
— Multifunctional programmable discrete input.
S3
Preset Speed 3
— Multifunctional programmable discrete input.
S4
Emergency Off
— Multifunctional programmable discrete input.
RR
Analog Input
RR
— Multifunctional programmable analog input
(0.0 to 10 volt input — 0 to 80 Hz output).
RX
RX
— Multifunctional programmable analog input
(-10 to +10 VDC input — -80 to +80 Hz output).
II
II
— Multifunctional programmable analog input (4 [0] to 20 mADC input —
0 to 80 Hz output).
VI
VI
— Multifunctional programmable analog input
(0 to 10 VDC input — 0 to 80 Hz output).
AM
Analog Output
Produces an output voltage that is proportional to the magnitude of the
function assigned to this terminal.
FM
OUT1(C-A)
Switched
Output
Low Frequency
— Programmable contact (N.O.).
OUT2(C-A)
Reach Frequency
— Programmable contact (N.O.).
FLA
Fault relay (N.O.).
FLB
Fault relay (N.C.).
FLC
Fault relay (Common).
FP
Pulsed Output
Frequency Pulse
— an output pulse train that has a frequency based on the
output frequency of the ASD.
P24
DC Output
24 VDC @ 50 mA output.
PP
PP
— 10.0 VDC voltage source for the external potentiometer.
CC
—
Return for analog and discrete input terminals.
DO NOT
connect to
Earth Gnd.