174
WX9 ASD Installation and Operation Manual
Point 1 Setting
Program
Communications
Communication Adjustments
When enabled at
Frequency Point Selection
, this parameter is used to
allow the user to set the gain and bias of the speed control input to the drive
when the speed control signal is received via the source selected at
Frequency
Point Selectio
n (
.
Gain and Bias Settings
When operating in the
Speed Control
mode and using one of the control
sources from
Settings
above, the settings that determine the gain and bias
properties of the input signal are:
•
Communications Point 1 Frequency
•
the communications
input signal value that represents
Communications
Point 1 Setting
•
Communications Point 2 Frequency
•
the communications
input signal value that represents
Communications Point 2 Setting
).
Once set, as the input signal value changes, the output frequency of the drive
will vary in accordance with the above settings.
This parameter sets the
Communications Reference
input value that represents
Communications Point 1 Setting
. This value is entered as 0 to 100% of the
Communications Reference
input value range.
Note:
Changes made to this parameter require that the power be cycled
(off then on) for the changes to take effect.
Direct Access Number — F811
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 100.0
Units — %
Point 1 Frequency
Program
Communications
Communication Adjustments
This parameter is used to set the gain and bias of the
Communications
Reference
speed control input.
See
Point 1 Setting
for additional information on this setting.
This parameter sets
Point 1 Frequency.
Note:
Changes made to this parameter require that the power be cycled
(off then on) for the changes to take effect.
Direct Access Number — F812
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
Point 2 Setting
Program
Communications
Communication Adjustments
This parameter is used to set the gain and bias of the
Communications
Reference
speed control input.
See
Point 1 Setting
for additional information on this setting.
This parameter sets the
Communications Reference
input value that represents
Point 2 Setting
. This value is entered as 0 to 100% of the
Communications
Reference
input value range.
Note:
Changes made to this parameter require that the power be cycled
(off then on) for the changes to take effect.
Direct Access Number — F813
Parameter Type —
Numerical
Factory Default —
100.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 100.0
Units — %