WX9 ASD Installation and Operation Manual
Acceleration/Deceleration Switching Frequency 1
Program
Special
Acc/Dec Special
This parameter sets the frequency at which the acceleration control is switched
from the
Acceleration (Acc) 1
Profile
to the
Acceleration (Acc) 2
Profile
during a multiple-profile configuration.
Direct Access Number — F505
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
S-Pattern Acceleration Lower-Limit Adjustment
Program
Special
Acc/Dec Special
During an
S-Pattern 1
or
2
sequence, this parameter settings modifies the
acceleration rate for the lower part of the acceleration curve by the percentage
set here.
This function is commonly used with transportation and lifting applications.
See
S-Curve Acc/Dec Pattern 1
Acc/Dec Pattern 1-4 Selection
) for additional information on this setting.
Direct Access Number — F506
Parameter Type —
Numerical
Factory Default —
25.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 50.00
Units — %
S-Pattern Acceleration Upper-Limit Adjustment
Program
Special
Acc/Dec Special
During an
S-Pattern 1
or
2
sequence, this parameter setting modifies the
acceleration rate for the upper part of the acceleration curve by the percentage
set here.
This function is commonly used with transportation and lifting applications.
See
S-Curve Acc/Dec Pattern 1
Acc/Dec Pattern 1-4 Selection
) for additional information on this setting.
Direct Access Number — F507
Parameter Type —
Numerical
Factory Default —
25.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 50.00
Units — %
Acceleration/Deceleration Time Lower Limit
Program
Special
Acc/Dec Special
This parameter sets the lower-limit of the
Acceleration/Deceleration (Acc/
Dec)
time.
See
Acc/Dec Pattern 1-4 Selection
(
) for additional information on this
setting.
Direct Access Number — F508
Parameter Type —
Numerical
Factory Default —
0.10
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 10.00
Units — Seconds
Acceleration Time 3
Program
Special
Acc/Dec (1 - 4) Settings
This parameter specifies the time for the drive to go from 0.0 Hz to the
Maximum Frequency
for the
Acceleration (Acc) 3 Profile
.
The
Acceleration/Deceleration (Acc/Dec)
pattern may be set using
.
The minimum
Acceleration/Deceleration (Acc/Dec)
time may be set using
Note:
An acceleration time that is shorter than the load will allow may
cause nuisance tripping and mechanical stress to loads.
Automatic Acceleration/Deceleration
,
Stall
, and
Ridethrough
settings
may lengthen the acceleration time.
Direct Access Number — F510
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum —
Maximum — 6000
Units — Seconds