WX9 ASD Installation and Operation Manual
Motor Rated Capacity (nameplate)
Program
Motor
Vector Motor Model
This parameter identifies the wattage rating of the motor.
Direct Access Number — F412
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
No
Minimum — 0.10
Maximum — (ASD-Dependent)
Units — kW
Motor Type
Program
Motor
Vector Motor Model
This parameter identifies the type of motor being used.
Settings:
0 — Toshiba EQP III TEFC
1 — Toshiba EQP III ODP
2 — Toshiba EPACT TEFC
3 — Toshiba EPACT ODP
4 — Other Motor
Direct Access Number — F413
Parameter Type —
Selection List
Factory Default —
Toshiba EQP III
TEFC
Changeable During Run —
No
Autotune of Motor Constant 3
Program
Motor
Vector Motor Model
This parameter Enables/Disables tuning of
Motor Constant 3
during an
Autotune
.
Settings:
0 — Prohibited
1 — Valid for Sensorless Vector
2 — Valid for Vector with PG
Direct Access Number — F414
Parameter Type —
Selection List
Factory Default —
Valid for Sensorless
Vector
Changeable During Run —
No
Torque Command Selection
Program
Torque
Torque Control
When operating in the
Torque Control
mode, this parameter allows the user to
select the source of the torque command signal.
Settings:
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — CN8 Option
6 — Binary/BCD Input
7 — Common Serial (TTL)
8 — RS232/RS485
9 — Communication Card
Direct Access Number — F420
Parameter Type —
Selection List
Factory Default —
RX
Changeable During Run —
Yes
Torque Command Filter
Program
Torque
Torque Control
This parameter reduces the motor vibration caused by large-inertia loads. A
small value will have a great effect while an increased value will have a lesser
effect.
Direct Access Number — F421
Parameter Type —
Numerical
Factory Default —
200.0
Changeable During Run —
Yes
Minimum — 10.0
Maximum — 200.0