WX9 ASD Installation and Operation Manual
117
Jump Frequency 1
Program
Special
Jump Frequencies
In conjunction with
, this parameter establishes a user-defined frequency
range: the
Jump Frequency
and a plus-or-minus value.
During acceleration, the output frequency of the drive will hold at the frequency
of the lower level of the
Jump Frequency
range until the programmed
acceleration ramp reaches the upper level of the
Jump Frequency
range. Then,
the output frequency of the drive will accelerate to the upper level of the
Jump
Frequency
range and continue upward as programmed.
During deceleration, the output frequency of the drive will hold at the
frequency of the upper level of the
Jump Frequency
range until the
programmed deceleration ramp reaches the lower level of the
Jump Frequency
range. Then, the output frequency of the drive will decelerate to the lower level
of the
Jump Frequency
range and continue downward as programmed.
Once set up and enabled, it is on in all control modes.
User-selected frequencies may be jumped to avoid the negative effects of
mechanical resonance.
Direct Access Number — F270
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
Jump Frequency 1 Bandwidth
Program
Special
Jump Frequencies
This parameter establishes a plus-or-minus value for
Jump Frequency 1
).
Direct Access Number — F271
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 30.00
Units — Hz
Jump Frequency 2
Program
Special
Jump Frequencies
This parameter is the same as
Jump Frequency 1
) and is used when
multiple frequencies are to be jumped (see the plus-or-minus value setting at
Jump Frequency 2 Bandwidth
(
). When multiple jump frequencies
overlap, the system will recognize the lowest and the highest frequencies as one
jump range.
Direct Access Number — F272
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
Jump Frequency 2 Bandwidth
Program
Special
Jump Frequencies
This parameter establishes a plus-or-minus value for
Jump Frequency 2
Direct Access Number — F273
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Jump Frequency 3
Program
Special
Jump Frequencies
This parameter is the same as
Jump Frequency 1
) and is used when
multiple frequencies are to be jumped (see the plus-or-minus value setting at
Jump Frequency 3 Bandwidth
(
). When multiple jump frequencies
overlap, the system will recognize the lowest and the highest frequencies as one
jump range.
Direct Access Number — F274
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
Summary of Contents for WX9 ASD
Page 2: ......
Page 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv WX9 ASD Installation and Operation Manual ...
Page 225: ......