Wire connection
REQUIREMENT
• Pass the wires through the grommet of wiring connection holes of the Air to Air Heat Exchanger.
• Keep a margin (Approx. 100 mm) on a wire.
• The low-voltage circuit is provided for the remote controller.
• Rotate the electrical control base to open.
• Connect the power supply wire (R (L), S (N)) and the remote control wire (A, B).
• Connect the central control wire (U1/U3, U2/U4) or the external output terminal block (1 to 5) if necessary.
• Tighten the screws on the terminal board firmly, then fix the wiring on the electrical control box using the
accessory cord clamp.
• Perform earthing work.
S
R
B
A
U1
U3
U2
U4
30
30
S(N)
R(L)
Communication wire
terminal block
Wiring for the central
control (U3, U4)
Wiring for the remote
controller (A, B)
Power supply terminal
block (R(L), S(N))
External output terminal
block (1, 2, 3, 4, 5)
Operation output
Common
External damper output (3-4)
Abnormal/Bypass mode
output (3-5)
Remote
controller wire
Central control
wire
Earth screw
Grommet
Power supply
wire
Electrical control
box
15
10
40
15
10
Power supply wire
Central control wire
Remote controller wire
Earth line
In a central control system, connect
the copper braid shield of central
control wire (2-core shielded wire).
Switching between Extra High and High
WARNING
• Turn off the circuit breaker before switching between Extra High and High.
When switching to Extra High, connect the black lead wire
(Extra High) to the connector.
* The blue lead wire (High) is connected as factory default.
* Connect the black lead wire both to the supplying air motor
(white connector) and the exhausting air motor (red
connector).
* Refer to “Connection diagram” for the connection method.
Remote Controller Wiring
• As the remote controller wire has non-polarity, there is no problem if connections to Air to Air Heat Exchanger
terminal blocks A and B are reversed.
Wiring diagram
* For details of wiring/installation of the remote controller, refer to the Installation Manual enclosed to in the remote
controller.
Exhaust air
(red connector)
Supply air
(white connector)
Blue lead wire
(High)
*Factory default
Cord clip
REQUIREMENT
• After connecting the black lead wire to the connectors, fix the
lead wires using the cord clip.
A
B
A
B
Terminal block
Remote
controller
unit
Terminal block for remote
controller wiring of Air to Air
Heat Exchanger
Remote controller wire
(locally procured)