E6582062
6. [Advanced] How to use parameters
6-86
4
4
6
9
5) Motor parameter setting method (Basic)
<F401: Slip frequency gain>
This parameter sets the compensation gain for motor slip.
Increasing the value will reduce motor slip.
Set <F417: Motor rated speed> and then make fine adjustments to <F401>.
Keep in mind that setting a higher value than necessary will cause unstable operation such as
hunting.
<F402: Automatic torque boost>
This parameter adjusts the primary resistive component of the motor.
Increasing this value will prevent torque reduction due to voltage drop during low speed.
Adjust the value according to the actual operation.
Keep in mind that setting a higher value than necessary will increase current at low speed and
may cause tripping.
If there is a motor test report, check the stator resistance value per phase.
<F402> (%) = (
√
3 x Rs x <F415> x 0.9) / (Vtype x 100)
where Rs is the stator resistance value per phase (
Ω
), Vtype is 200, 400 V (depends on voltage
class).
<F405: Motor rated capacity>
This parameter sets the motor rated capacity.
Check the motor name plate or test report while setting.
<F412: Leakage inductance>
This parameter sets the leakage inductance component of the motor.
Increasing this value will improve torque in the high-speed region.
<F415: Motor rated current>
This parameter sets the motor rated current.
Check the motor name plate or test report while setting.
<F416: Motor no load current>
This parameter sets the ratio of the motor no-load current to the rated current.
This is equivalent to the exciting inductance of the motor.
Check the no-load current value in the motor test report and divide it by the rated current value.
Set the calculated value in %.
F463
Speed control response
2
0.0 - 25.0
-
0.0
F464
Speed control
stabilization coefficient 2
0.50 - 2.50
-
1.00
F465
Speed reference filter
coefficient 2
0 - 100
-
35
F466
Speed control response
switching frequency
0.0 - FH
Hz
0.0
*1 Depending on capacity. For details, refer to [11. 6].
*2 Depending on the setup menu. Refer to [5. 3. 10], [11. 10].
Title
Parameter name
Adjustment range
Unit
Default setting
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...