5. [Fundamental operation] How to use parameters
5-42
4
5
9
• <F405: Motor rated capacity>
• <F415: Motor rated current>
• <F417: Motor rated speed>
Two parameter setting methods are provided.
1) Setting with <F400: Offline auto-tuning>
Set <F400: Offline auto-tuning> to "5".
For details, refer to [6. 23. 1].
* If an auto-tuning error occurs, set motor parameters individually by referring to [6. 23. 1]
"
Setting method 4: Manually setting motor parameter".
2) Manual setting
Set each motor constant.
For details, refer to [6. 23. 1].
6: PM motor control
Permanent magnet motors (PM motors) that are highly efficient can be operated in sensor-less
operation.
Setting of parameters for PM motor is required. For details, refer to [6. 23. 2].
7: V/f 5-point setting
V/f control characteristics can be created according to machinery. Set frequency and voltage in five
points and run the inverter with V/f control characteristics derived by connecting these points.
Set five points from VF1 to VF5 with the following parameters <F190> to <F199>.
Title
Parameter name
Adjustment range
Unit
Default setting
F190
V/f 5-point VF1 frequency
0.0 - FH
Hz
0.0
F191
V/f 5-point VF1 voltage
0.0 - 125.0
%
*1
*1 100% with 200 V for 240 V class and 400 V for 480 V class.
0.0
F192
V/f 5-point VF2 frequency
0.0 - FH
Hz
0.0
F193
V/f 5-point VF2 voltage
0.0 - 125.0
%
0.0
F194
V/f 5-point VF3 frequency
0.0 - FH
Hz
0.0
F195
V/f 5-point VF3 voltage
0.0 - 125.0
%
0.0
F196
V/f 5-point VF4 frequency
0.0 - FH
Hz
0.0
F197
V/f 5-point VF4 voltage
0.0 - 125.0
%
0.0
F198
V/f 5-point VF5 frequency
0.0 - FH
Hz
0.0
F199
V/f 5-point VF5 voltage
0.0 - 125.0
%
0.0
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...