E6581440 

 

- 8 - 

3.2.  Network Baudrate (

f831

Set the network baudrate to 

f831

. Set the same baudrate in the network. If set AUTO 

baudrate, the option unit detects network baudrate automatically. 

 

3.3.  Network error detection (

f832

,

f851

,

f852

Set the network communication loss action time to 

f832

. The network loss detection 

starts from the first receiving of the proper frame message. The action of the network 

communication loss is set by 

f851

If 

f851

 is set other than 4, `

t

' alarm appear at the inverter panel display when 

communication loss was detected. 
In addition, in the case of 

f851

= 5, the inverter output designated frequency in “Preset 

speed operation selection(

f852

)”. 

 

3.4.  Instance Number (

f833

f834

Set BACnet® Object Instance number. The instance number should not be duplicate in 
the network. The instance number is 22bit data length, and set the number of the option 
board as below. 

Instance number = 

f833

 x 1000 + 

f834 

f834 

< 1000 

Instance number < 4194304

 

 

3.5. MaxMaster (

f835

Set the maximum master number of the segment. The BACnet® option unit polls master 

station node from 0 to MaxMaster, so set MaxMaster to be small number to be a fast 

response time. 

 

3.6. MaxInfoframe (

f836

Set the max information frame number to send from this node. Not need to change. 

 

3.7.  MAC address monitor(

f853

Set the station MAC address to a switch(SW102) on the option board. This station MAC 
address should be a unique number on the MS/TP network segment. 

f853

 is the monitor parameter of MAC address that is set to the address switch on the 

option board. 

 

3.8.  Number of motor poles for communication(

f856

Set the number of motor pole pairs to calculate the motor rotational speed. 
This parameter is used only when the motor rotational speed is monitored with a 
communication.

 

Summary of Contents for TOSVERT BCN001Z

Page 1: ...uction manual is delivered to the end user of BACnet Option unit 2 Read this manual before installing or operating the BACnet Option unit Keep it in a safe place for reference 3 All information contained in this manual are subject to change without notice Please confirm the latest information on our web site ...

Page 2: ... valid range to network variables Otherwise the motor may suddenly start stop and that may result in injuries Mandatory Use an additional safety device with your system to prevent a serious accident due to the network malfunctions Usage without an additional safety device may cause an accident Caution Mandatory Set up Communication error trip function see below to stop the Inverter when the option...

Page 3: ...ter f835 8 3 6 MaxInfoframe f836 8 3 7 MAC address monitor f853 8 3 8 Number of motor poles for communication f856 8 4 FUNCTIONS 9 4 1 Object Property support Matrix 9 4 2 Drive I O Objects 10 4 2 1 Binary Input Object Instance 10 4 2 2 Binary Output Object Instance 11 4 2 3 Binary Value Objects Instance 12 4 2 4 Analog Input Object Instance 13 4 2 5 Analog Output Object Instance 13 4 2 6 Analog V...

Page 4: ...nal symbol Function Electrical specifications Internal circuits B Communication signal A Communication signal GND Signal common SCR BACnet communication signal EIA 485 Shield terminal B A GND SCR 47k 47k 4 7k 4 7k 120 SW102 TERM Don t use this connecter Connector to the inverter MS TP MAC address switches See 2 4 Don t use this switch BACnet Connector See 2 2 Terminal connector MSTB 2 5 4 STF 5 08...

Page 5: ...0 5s Invalid configuration was detected MAC address max master Note When inverter occurred in E 23 or E 24 the LED becomes this state D COM LED 3 times in 2 seconds OFF for 1 second ERR LED OFF Waiting for Auto baudrate detection E COM LED Flashing ERR LED OFF Valid message was received for this node F COM LED OFF ERR LED Flashing Invalid message was received any node G COM LED OFF ERR LED OFF No ...

Page 6: ...ON ON 12 OFF OFF OFF OFF ON ON OFF OFF 44 OFF OFF ON OFF ON ON OFF OFF 13 OFF OFF OFF OFF ON ON OFF ON 45 OFF OFF ON OFF ON ON OFF ON 14 OFF OFF OFF OFF ON ON ON OFF 46 OFF OFF ON OFF ON ON ON OFF 15 OFF OFF OFF OFF ON ON ON ON 47 OFF OFF ON OFF ON ON ON ON 16 OFF OFF OFF ON OFF OFF OFF OFF 48 OFF OFF ON ON OFF OFF OFF OFF 17 OFF OFF OFF ON OFF OFF OFF ON 49 OFF OFF ON ON OFF OFF OFF ON 18 OFF OFF...

Page 7: ... ON OFF ON ON OFF ON 78 OFF ON OFF OFF ON ON ON OFF 110 OFF ON ON OFF ON ON ON OFF 79 OFF ON OFF OFF ON ON ON ON 111 OFF ON ON OFF ON ON ON ON 80 OFF ON OFF ON OFF OFF OFF OFF 112 OFF ON ON ON OFF OFF OFF OFF 81 OFF ON OFF ON OFF OFF OFF ON 113 OFF ON ON ON OFF OFF OFF ON 82 OFF ON OFF ON OFF OFF ON OFF 114 OFF ON ON ON OFF OFF ON OFF 83 OFF ON OFF ON OFF OFF ON ON 115 OFF ON ON ON OFF OFF ON ON 8...

Page 8: ...ire breaks 0 Inverter stop communication command frequency mode open by cmod fmod 1 None continued operation 2 Deceleration stop 3 Coast stop 4 Network error err8 trip 5 Preset speed operation by f852 setting 0 f852 Preset speed operation selection 0 None 1 15 Preset speed operation by parameter setting 0 f853 MAC address 2 Read Only BCN001Z MS TP MAC address monitor Set DIP switches on the board ...

Page 9: ...e in the network The instance number is 22bit data length and set the number of the option board as below Instance number f833 x 1000 f834 f834 1000 Instance number 4194304 3 5 MaxMaster f835 Set the maximum master number of the segment The BACnet option unit polls master station node from 0 to MaxMaster so set MaxMaster to be small number to be a fast response time 3 6 MaxInfoframe f836 Set the m...

Page 10: ...ct Type System Status Vendor Name Vendor Identifier Model Name Firmware Revision Appl Software Revision Protocol Version Protocol Revision Services Supported Object Types Supported Object List Max APDU Length Segmentation Support APDU Timeout Number APDU Retries Max Master Max Info Frames Device Address Binding Database Revision Present Value Status Flags Event State Out of Service Units Priority ...

Page 11: ...N OFF R Binary input 4 RO 5 ACT Inverter OUT5 terminal monitor f136 ON OFF R Binary input 5 RO 6 ACT Inverter OUT6 terminal monitor f137 ON OFF R Binary input 6 DI 1 ACT Inverter F terminal monitor ON OFF R Binary input 7 DI 2 ACT Inverter R terminal monitor ON OFF R Binary input 9 DI 4 ACT Inverter RES terminal monitor ON OFF R Binary input 10 DI 5 ACT Inverter S1 terminal monitor ON OFF R Binary...

Page 12: ...ription Active Inactive Access Binary Output 0 RO 1 CMD FL terminal control f132 92 ON OFF C Binary Output 1 RO 2 CMD OUT1 terminal control f130 94 ON OFF C Binary Output 2 RO 3 CMD OUT2 terminal control f131 96 ON OFF C Binary Output 3 RO 4 CMD R2 terminal control f138 98 ON OFF C Binary Output 4 RO 5 CMD OUT3 terminal control f136 100 ON OFF C Binary Output 5 RO 6 CMD OUT4 terminal control f137 ...

Page 13: ... object access to parameter fc91 bit10 YES NO R 7 DRIVE READY The VSD is ready and waits a start command This object access to parameter fd01 bit14 READY NOT READY R 8 AT SETPOINT The VSD has reached the target speed REACHED NO R 10 RUN STOP CMD Commands a drive start START STOP C 11 FWD REV CMD Commands a motor direction s change REV FWD C 14 FAULT RESET Command to reset faults RESET NO C 15 MBOX...

Page 14: ...ETB004Z Expansion IO card option R Read only W Writable C Commandable 4 2 5 Analog Output Object Instance The analog output objects allow to control inverter analog AM FM output levels and also can be used priority array and relinquish default property These objects only write to inverter parameters fa51 fa54 It is necessary to set meter function selection parameters see below table to 31 Instance...

Page 15: ...from fe30 100 3 VSD rate voltage Motor rate current R 7 DRIVE TEMP Drive Thermal State fd24 OL1 will be caused if this value reaches 100 R 8 KWH R Energy counter Calculate from fd76 fd77 KWH R 10 PRC PID FBCK PID regulator feedback fe22 vl 100 00 R 14 RUN TIME Cumulate operation time fe14 hour R 16 INPUT REF 1 Speed reference fa07 vl 100 C 18 LAST FLT Current fault code fc90 R 19 PREV FLT 1 Past f...

Page 16: ...bject Name VF PS1 Object Type 8 device Vendor Name TOSHIBA Vendor Identifier 203 Model Name VFPS1 2007P depend on the VSD model Firmware Revision V1 00 depend on the option software version Application Software Version V6 20 depend on the VSD software version Protocol Version 1 Protocol Revision 2 ...

Page 17: ...d communication number is illegal MBOX READ value remains 1 It allow to check read failure Binary value 16 MBOX WRITE Write Command If MBOX WRITE command value is set to 1 the inverter parameter specified by MBOX PARAM is written the data specified by MBOX DATA and MBOX WRITE set to 0 automatically If parameter writing is denied or specified communication number is illegal MBOX WRITE value remains...

Page 18: ...array fault err6 26 1A Output current detector error err7 27 1B Option error err8 29 1D Low current operation status uc 30 1E Undervoltage main circuit up1 32 20 Over torque trip ot 33 21 Ground fault trip ef1 34 22 Ground fault trip ef2 36 24 Dynamic braking abnormal element ocr 37 25 Overcurrent during acceleration element overheat oc1p 38 26 Overcurrent during deceleration element overheat oc2p...

Page 19: ...VDC supplied from the inverter Network specification Item Specification Data link physical layer Master Slave Token Passing MS TP Node type Master node Maximum connection units Maximum 32 units within one segment Communication baudrate 9600 19200 38400 76800bps Auto adaptive is supported Bias resistor and termination Local bias resistors are mounted Termination resistor 120 ohm can be select by SW...

Reviews: