Toshiba TCB-PSMT1E Installation Manual Download Page 2

CB14800701(EN)

Wiring method

1. Remove the four screws from the electrical parts box of Multi Tenant Kit and then remove the cover.
2. Attach 3-mm round terminals to the 24 V AC power supply cable and then connect the cable to the TB1 terminal.
3. Insert the power supply cable of Multi Tenant Kit CN3 into the tab of the indoor unit power supply terminal and 

then secure it in place with the cord clamp. Also connect the earth wire and secure it with the cord clamp at the same time.

For a model that has a lead wire protruding from the tab of the power supply terminal such as 
Concealed Duct High Static Pressure Type, cut the end of the lead wire and secure it with the supplied Wire joint.

4. Insert the indoor unit connection cable (A) (6-pin) of Multi Tenant Kit CN2 into CN61 on the indoor unit PC board.
5. Insert the indoor unit connection cable (B) (5-pin) of Multi Tenant Kit CN1 into CN50 on the indoor unit PC board.
6. Reattach the cover to the electrical parts box of Multi Tenant Kit and then use the four screws to secure it in place.

CODE No. (DN) setting

Wired remote controller setting 

(RBC-AMT32E)

Change the settings while the air conditioner is not working. 

(Stop the air conditioner before making settings.)

CAUTION

Set only the CODE No. shown in the following table: Do not set any other CODE No.
If a CODE No. not listed is set, it may not be possible to operate the air conditioner or other trouble with the product may result.

1

Push and hold the “

” + “

” + “

” buttons for over 4 

seconds and then after a short time the display flashes as 
shown in the diagram.
Check that the CODE No. displayed is [10].

• If the CODE No. is anything except [10], push the “

” button, clear the 

display, and redo the procedure from the beginning.
(Remote control operations cannot be received for about 1 minute after 
pushing the “

” button)

(When doing group control, the first indoor unit number displayed is the header 
unit.)

The indoor unit numbers under group control are displayed in order each time the 

” button is pushed, so you can select the indoor unit whose settings you 

want to change.
When this is done, the fan and horizontal louvers of the selected indoor unit 
operate, so you can confirm the position of the indoor unit whose settings you want 
to change.

2

Specify the CODE No. [d8] with the temperature setting “

” 

and “

” buttons.

3

Use the timer setting “

” and “

” buttons to set [0000] 

 

[0001]

4

Push the “

” button (settings are fixed).

Pushing the “

” button turns off the display, and it goes into normal stop mode.

(“

” flashes and remote control operations cannot be received for about 1 

minute after pushing the “

” button)

• If remote control operations cannot be received after more than 1 minute after 

pushing the “

” button, the address settings may be wrong. If this is the case, 

start at step 1 to change the settings again and redo the automatic address 
settings.

Earth screw

24 V AC power cable

(to step-down transformer)

Cord clamp

Power cable (from indoor unit)

Indoor unit connection cable (A)

Indoor unit connection cable (B)

CN1

CN3

CN2

TB1

(*The display varies for different models of indoor unit)

Lite-Vision plus remote controller 

(RBC-AMS51E*)

Perform the advanced settings for the air conditioner.
Carry out the setting operation while the indoor unit is stopped. 
(Turn off the air conditioning unit before starting the setting operation.)

1

Push the [

 

MENU] button to display the menu screen.

2

Push and hold the [

 

MENU] button and the [

 

button at the same time to display the “Field setting menu”.

Push and hold the buttons for more than 4 seconds.

3

Push the [

 

 ] / [

 

 ] button to select “5. DN setting” 

on the “Field setting menu” screen, then push the 

 

Set”  [

 

F2] button.

The fan and louver of the indoor unit operate. When the group control is used, the 
fan and louver of the selected indoor unit operate.
Move the cursor to select “DN code” with the “

 

<

” [

 F1] button, 

then set “

d8

” with the [ 

 

 

] / [ 

 

 ] button.

Move the cursor to select “data” with the “

 

>

” [

 F2] button, then 

set “0001” with the [ 

 

 

] / [ 

 

 ] button.

4

Push the [

 MENU] button to set the other DN codes. After 

“Continue?” is displayed on the screen, push the 

 

Yes”  [

 

F1] button.

5

Push the “

 

No” [

 F2] button to finish the 

setting operation. “ ” appears on the screen for a while, then 
the screen returns to the “Field setting menu” screen.

Pushing the “

 

No” [

 F2] button displays the unit selection screen 

when the group control is used. Push the [

 CANCEL] button on the unit 

selection screen to finish the setting operation. “ ” appears on the screen for a 
while, then the screen returns to the “Field setting menu” screen.

6

Push the [

 

 CANCEL] button to return.

NOTE

• The CODE No. setting cannot be set with a wireless remote controller, simple remote controller, or central control remote controller.
• When installing another option at the same time, use CN4 on the Multi Tenant Kit board.

CN4 is for use instead of the indoor unit option connector CN61, but when Multi Tenant Kit is installed, pin 3 of CN61 is changed from the unit remote controller operation disable 
function to the Multi Tenant signal so the unit remote control operation disable function of the other option cannot be used.

• A wired remote controller cannot be operated in multi tenant mode. Operation is also not accepted from another central control remote controller.
• In the case of group operation, install a Multi Tenant Kit and step-down transformer for all indoor units and enable simultaneous operation.

(Communication among the group stops and a check code is displayed.)

• Before configuring the address setting and performing test run, turn on the main power of the indoor unit.
• Be sure to install a step-down transformer for each Multi Tenant Kit. If a step-down transformer is shared by two or more kits, noise will be generated and communication will stop.
• Operation stops when multi tenant mode is cancelled (tenant power is turned on) even if auto restart is set.
• The louver of the indoor unit may open in multi tenant mode but this is not abnormal.

* Multi tenant mode: When tenant power is off

1.Test mode

2.Register service info.
3.Alarm history
4.Monitor function
5.DN setting

Field setting menu

Return

Set

DN setting

Code

(DN)

Data

Return

d8

0000

Fix

<

>

DN setting

Code

(DN)

Data

Return

d8

0001

Fix

<

>

Set

<

>

Return

Continue?

No

Yes

DN setting

Yes

No

No

Indoor unit

Indoor unit

Multi Tenant 

Kit

Multi Tenant 

Kit

Step-down 

Transformer

Step-down 

Transformer

Wired remote controller

+DB14800701_01EN.fm  Page 2  Thursday, November 5, 2015  2:12 PM

Summary of Contents for TCB-PSMT1E

Page 1: ...e will reach within approximately 2 m The Multi Tenant Kit cannot be mounted to the indoor unit Install the Multi Tenant Kit in a location where service space can be provided Installation in the following locations is not possible Location where combustible gas may leak Location subject to direct sunlight Location that becomes very hot and humid Use at an ambient temperature of 40 C or less Very d...

Page 2: ...n plus remote controller RBC AMS51E Perform the advanced settings for the air conditioner Carry out the setting operation while the indoor unit is stopped Turn off the air conditioning unit before starting the setting operation 1 Push the MENU button to display the menu screen 2 Push and hold the MENU button and the button at the same time to display the Field setting menu Push and hold the button...

Page 3: ...e pour qu il soit accessible avec le câble de connexion environ 2 m Le kit multi locataire ne peut pas être monté sur l unité intérieure Installez le kit multi locataire dans un endroit avec suffisamment d espace L installation dans les endroits suivants n est pas possible Endroit où il existe un risque de fuite de gaz combustible Endroit soumis à la lumière directe du soleil Endroit qui devient t...

Page 4: ...E Effectuez les réglages avancés pour le climatiseur Réalisez les opérations de réglage pendant que l unité intérieure est à l arrêt Mettez le climatiseur hors tension avant de démarrer les opération de réglage 1 Appuyez sur la touche MENU pour afficher l écran de menu 2 Maintenez pressée la touche MENU et la touche en même temps pour afficher le Menu réglages Service Maintenez pressées les touche...

Page 5: ...del cavo dell unità interna Il kit non può essere montato sull unità interna Deve essere installato in modo da garantire lo spazio necessario per le manutenzioni Non lo si deve installare In un ambiente ove si possano verificare perdite di gas infiammabili In un luogo esposto direttamente al sole In un ambiente molto caldo e umido la temperatura non deve superare 40 C In un ambiente molto polveros...

Page 6: ...legamento unità interna B CN1 CN3 CN2 TB1 La visualizzazione varia secondo il modello di unità interna Telecomando Lite Vision plus RBC AMS51E Con questa funzione si eseguono le impostazioni avanzate del condizionatore Prima di eseguirle è necessario spegnere l unità interna cioè il condizionatore Prima di effettuare l impostazione spegnere il condizionatore 1 Premere MENU per visualizzare la pagi...

Reviews: