Attaching bracket F

„

 Attaching the Super Long Life Filter

1

Turn the hanging hook of the Super Long Life Filter to the side of the electrical control box.

2

Fit the opposite side of the hanging hook onto brackets C and D, then slide the Super Long Life 
Filter to the right.

3

When the hanging hooks have been fitted onto brackets A, B, and F, fix the Super Long Life Filter 
using the decorative screws (12).

In addition, attach the closing plate (7) to bracket F using the decorative screws (12).

„

 Attaching the center panel

Attach the center panel referring to the Installation Manual of the center panel.

Fix bracket F (6) onto bracket E (5) using 2 screws (13). 
(Figure 10)

NOTE

• You need not attach bracket F for TCB-LF283UW.

5 Bracket E

13 Screws

6 Bracket F

Figure 10

12 Decorative 
screws

Figure 11

7 Closing plate

12 Decorative screws

Super Long Life Filter

The decorative screws (12) are used to prevent 
the filter from falling off. Tighten them firmly.

Fit this onto 
bracket A (1).

Super Long Life Filter

3 Bracket C

12 Decorative 
screw

1 Bracket A

Hanging 
hook

NOTE

• You need not attach the closing plate for 

TCB-LF283UW.

• Attach the Super Long Life Filter after the 

panel has been installed.

Hanging 
hook

5

Changing the SET DATA (Wired remote 
controller)

„

How to change the setting data

For details, refer to the Installation Manual of the 2-way cassette type (indoor unit).

• Change the SET DATA when using the Super Long Life 

Filter 

• Before you change the SET DATA, be sure to stop the air 

conditioner.

Step

Operation

1

Push and hold the 

 button and theTEMP. 

 button simultaneously 

for about 4 seconds. The display will start flashing. Make sure that [01] 
is displayed.
• If any code other than [01] is displayed, push the 

 button to cancel 

the procedure and start again. (Operation from the remote controller 
is invalid for a while after you push the 

 button.)

(During group control, [ALL] is displayed first. The unit number 
displayed next is that of the header unit.)

2

Each time you push the 

 button, the unit numbers of the indoor 

units in the group are displayed one by one. Select a unit to change its 
SET DATA.
When you select a unit, the fan and the louver of the selected unit start 
operating to show which unit is selected.

3

Use the TEMP. buttons 

 / 

 to select [5d].

4

Use the TIME 

 / 

 buttons to select [0001].

5

Push the 

 button. The setting procedure is completed when the display stops flashing and stays lit.

• Repeat the procedure from step 

2

 to change the SET DATA of another unit.

If you push the

 button, all changes made to the SET DATA are cleared. Redo the procedure from step 

2

.

6

When the setting is completed, push the 

 button. (Setting is fixed.)

When you push the 

 button, the [SETTING] indicator flashes, then it 

goes off and the unit returns to normal operation.
(Operation from the remote controller is invalid while the [SETTING] 
indicator is flashing.)

1

6

1

3

2

5

4

 

UNIT  LOUVER

SET DATA

0000

0001

Filter

Normal filter 
(Factory default)

Super Long Life Filter

9-EN

10-EN

+00EH99876601_00Ta.book  Page 5  Wednesday, November 24, 2010  5:06 PM

Summary of Contents for TCB-LF283UW-E

Page 1: ...er FC1403UW E getrennt erhältlich Die Luftfilter an der Deckenblende können nicht mit dem Super Long Life Filter verwendet werden Per usare il filtro di durata super lunga è innanzi tutto necessario installare la camera del filtro TCB FC283UW E FC803UW E o FC1403UW E da acquistare a parte I filtri dell aria del pannello a soffitto non possono essere usati insieme al filtro di durata super lunga Pa...

Page 2: ...with the plastic bag suffocation and death may result CAUTION Install the center panel on the ceiling panel securely Incorrect installation may result in the center panel falling and causing an injury Indication Meaning of Indication WARNING Text set off in this manner indicates that failure to adhere to the directions in the warning could result in serious bodily harm 1 or loss of life if the pro...

Page 3: ...uum cleaner then wash the filter in water Do not remove the filter from the filter frame Do not scrub the surface of the filter when washing it If the filter is badly clogged wash the filter in water with a neutral detergent standard density then wash it in clean water until the lather is gone Use the filter after it has completely dried Super Long Life Filter Dust collection efficiency 50 Gravime...

Page 4: ... not use for TCB LF283UW E 2 Attach the sealing materials 8 and 9 to cover the gap according to Figure 3 Remove the release paper of the sealing material 10 to attach it to the side 3 Attach all the sealing materials to the upper frame of the Filter Chamber NOTE Attach bracket F after installing the panel If you attach bracket F during this step you cannot install the panel Installing the Filter C...

Page 5: ...ging hook Push in the direction of the arrow when detaching the ceiling panel Hanger on the indoor unit equipped on both sides Ceiling panel Filter Chamber Figure 7 Frame cover CAUTION 3 Confirm that the screw holes on the ceiling panel and the indoor unit are aligned and fix the panel to the indoor unit with the supplied screws M5 x 40mm 4 screws for UW283PG and UW803PG 6 screws for UW1403PG Figu...

Page 6: ...r unit Change the SET DATA when using the Super Long Life Filter Before you change the SET DATA be sure to stop the air conditioner Step Operation 1 Push and hold the button and theTEMP button simultaneously for about 4 seconds The display will start flashing Make sure that 01 is displayed If any code other than 01 is displayed push the button to cancel the procedure and start again Operation from...

Page 7: ...EH99876601 00EH99876601_00Ta book Page 79 Wednesday November 24 2010 5 06 PM ...

Reviews: