DK40i Installation
Reserve Power Option
Strata DK I&M 6/00
3-17
D
K
40
i Installation
Reserve Power Option
A reserve power source (two customer supplied 12VDC batteries) can be connected to the DK40i
power supply to ensure uninterrupted system operation in the event of a power failure. A pre-
assembled interface cable for installation of the Reserve Power option is available from Toshiba
(PBTC-3M), see
Figure 3-12 System Power Supply Wiring
Important!
Local ordinances may dictate battery type and installation details.
The batteries require a well-ventilated location within nine feet of the system (the interface cable is
nine feet long).
WARNING!
To reduce the risk of fire or injury to persons, read and follow these
instructions:
➤
Use only 12VDC gelcell batteries.
➤
Do not dispose of the batteries in a fire. The cells may explode. Check
with local codes for possible special disposal instructions.
➤
Do not open or mutilate the batteries. Released electrolyte is corrosive
and may cause damage to the eyes or skin. It may be toxic if swallowed.
➤
Exercise care in handling batteries in order not to short the battery with
conduction materials such as rings, bracelets, and keys. The battery or
conductor may overheat and cause burns.
➤
Charge the batteries provided with or identified for use with this product
only in accordance with the instructions and limitations specified in this
manual.
➤
Observe proper polarity orientation between the batteries and battery
charger.
Actual Size
PBTC-3M
Battery Cable with
Ring Terminals
and PPSU Connector
(length - 9 feet)
Power Supply
BATT
Two-prong Male
Connector
(pre-assembled)
Black
White
In-line Fuse Holder 10 A
(Fuse Provided)
Black Jumper with
Ring Terminals
(provided)
White
Black
12 VDC
Battery
+
–
12 VDC
Battery
+
TPSU40
+
–
Ring Terminals 3/8 In.
–
16AWG
2164
Summary of Contents for Strata AirLink DK40i
Page 22: ...Introduction Related Documents Media xx Strata DK I M 6 00 ...
Page 48: ...DK14 Installation DK14 Wiring Diagrams 1 26 Strata DK I M 6 00 ...
Page 220: ...DK424 Installation Remote Cabinet Installation Instructions 5 68 Strata DK I M 6 00 ...
Page 262: ...DK424i Configuration Primary Reserve Power Cabinet Hardware 6 42 Strata DK I M 6 00 ...
Page 450: ...Universal Slot PCB Wiring Option Interface PCB Wiring Diagrams 10 42 Strata DK I M 6 00 ...
Page 592: ...Peripheral Installation Enhanced 911 Service E911 12 84 Strata DK I M 6 00 ...
Page 616: ...ACD Installation Spectrum Electronic Wall Boards 13 24 Strata DK I M 6 00 ...
Page 634: ...Fault Finding Fault Isolation Flowcharts 14 18 Strata DK I M 6 00 ...
Page 704: ...ISDN Interfaces ISDN Disconnect Cause Code 16 54 Strata DK I M 6 00 ...