Operating Instructions
ALARM SILENCE pushbutton is used to silence the alarm.
MONITOR RESET pushbutton is used to reset the RSAP UPS FAULT alarm. The monitor will
alarm again if the alarm condition is still present following the RESET.
Monitor TEST pushbutton is used to check the operation of all LED’s and the audible alarm. All
LED’s that are illuminated will go off and all lights that are off will illuminate. Horn will also
sound.
INTERNAL MONITOR BATTERY TEST button is used to test the condition of the monitor’s
battery pack. If the yellow LED does not illuminate, replace the batteries.
Reset the RSAP as follows:
1.
On the UPS, note the alarm and its fault code. If applicable, contact 24 hour UPS field
service at (877) 867-8773.
2.
If no alarm code is present, press the monitor reset button.
3.
If the monitor’s audible alarm sounds again repeat steps 1 and 2.
4.
Contact TIC service if the alarm cannot be reset after a few attempts.
Refer to Figure 1.0 for location of the LED’s and pushbuttons described below:
1.
Rectifier / Charger LED
. This green LED is illuminated as long as the UPS inverter is
operating.
2.
Battery LED
. This yellow LED is illuminated as long as the UPS is in the battery backup
mode. The audible alarm will beep intermittently.
3.
Inverter On LED
. The green LED is illuminated as long as the UPS inverter is operating.
4.
Output
LED. This green LED is illuminated as long as there is power to the critical load.
(Either by the Inverter or Bypass)
5.
Load On Bypass LED
. This yellow LED is illuminated as long as the critical load is
powered by the Bypass.
6.
AC Input LED
. This green LED is illuminated as long as there is AC power supplied to
the system.
7.
UPS Fault
. This red LED is illuminated and the audible alarm sounds when a UPS fault
has occurred. The RSAP must be reset after the alarm is cleared.
8.
Overload LED
. This red LED is illuminated when a UPS overload has occurred. The
audible alarm will also sound.
9.
Input Failure LED
. This red LED is illuminated when an input power failure condition is
present. The audible alarm will also sound.
10.
Battery Low Voltage
. This red LED is illuminated as soon as the DC bus voltage
approaches its cutoff voltage. The audible will also sound.
11.
Alarm Silence LED
. This red LED will illuminate when the ALARM SILENCE
pushbutton has been pressed and alarm condition is still present. If alarm condition clears,
the ALARM SILENCE LED will automatically reset.
12.
Internal Monitor Battery OK LED
. This yellow LED will illuminate when its
corresponding push button is pressed and the batteries are OK. IF this light is dim or does
not light, replace all internal batteries.