Operating Instructions 

 
ALARM SILENCE pushbutton is used to silence the alarm. 
MONITOR RESET pushbutton is used to reset the RSAP UPS FAULT alarm.  The monitor will 
alarm again if the alarm condition is still present following the RESET. 
 
Monitor TEST pushbutton is used to check the operation of all LED’s and the audible alarm.  All 
LED’s that are illuminated will go off and all lights that are off will illuminate.  Horn will also 
sound. 
 
INTERNAL MONITOR BATTERY TEST button is used to test the condition of the monitor’s 
battery pack.  If the yellow LED does not illuminate, replace the batteries. 
 
Reset the RSAP as follows: 

1.

 

On the UPS, note the alarm and its fault code.  If applicable, contact 24 hour UPS field 
service at (877) 867-8773. 

2.

 

If no alarm code is present, press the monitor reset button. 

3.

 

If the monitor’s audible alarm sounds again repeat steps 1 and 2. 

4.

 

Contact TIC service if the alarm cannot be reset after a few attempts. 

 
Refer to Figure 1.0 for location of the LED’s and pushbuttons described below: 
 
1.

 

Rectifier / Charger LED

.  This green LED is illuminated as long as the UPS inverter is 

operating.  

2.

 

Battery LED

.  This yellow LED is illuminated as long as the UPS is in the battery backup 

mode.  The audible alarm will beep intermittently. 

3.

 

Inverter On LED

.  The green LED is illuminated as long as the UPS inverter is operating. 

4.

 

Output 

LED.  This green LED is illuminated as long as there is power  to the critical load.  

(Either by the Inverter or Bypass) 

5.

 

Load On Bypass LED

.  This yellow LED is illuminated as long as the critical load is 

powered by the Bypass. 

6.

 

AC Input LED

.  This green LED is illuminated as long as there is AC power supplied to 

the system.  

7.

 

UPS Fault

.  This red LED is illuminated and the audible alarm sounds when a UPS fault 

has occurred.  The RSAP must be reset after the alarm is cleared. 

8.

 

Overload LED

.  This red LED is illuminated when a UPS overload has occurred.  The 

audible alarm will also sound. 

9.

 

Input Failure LED

.  This red LED is illuminated when an input power failure condition is 

present.  The audible alarm will also sound. 

10.

 

Battery Low Voltage

.  This red LED is illuminated as soon as the DC bus voltage 

approaches its cutoff voltage.  The audible will also sound. 

11.

 

Alarm Silence LED

.  This red LED will illuminate when the ALARM SILENCE 

pushbutton has been pressed and alarm condition is still present.  If alarm condition clears, 
the ALARM SILENCE LED will automatically reset. 

12.

 

Internal Monitor Battery OK LED

.  This yellow LED will illuminate when its 

corresponding push button is pressed and the batteries are OK.  IF this light is dim or does 
not light, replace all internal batteries. 

Summary of Contents for RSAP

Page 1: ...TOSHIBA International Corp REMOTE STATUS ALARM PANEL RSAP INSTALLATION INSTRUCTION MANUAL ...

Page 2: ... Figure 1 0 5 Remote Monitor Closed Hardwire Figure 1 1 6 Terminal Block Description Figure 2 0 7 Terminal Block Description Figure 2 1 8 Remote Monitor Open Figure 3 0 9 Remote Monitor Open Hardwired Figure 3 1 10 Remote Monitor Conduit Access Figure 4 0 11 Figure G8000 12 Figure 4200FA 15 50Kva 13 Figure 4200FA 80kVA 14 ...

Page 3: ... pairs of twisted wire from the RSAP to the customer accessible alarm contact terminal bar in the UPS module Refer to UPS manual for location 6 Referring to Figure 3 0 install 6 AA batteries Batteries will provide about eight 8 hours of run time in the event of an AC power failure Replace these batteries yearly for optimum performance 7 Referring to Figure 1 0 connect the power supply adapter into...

Page 4: ...audible alarm will beep intermittently 3 Inverter On LED The green LED is illuminated as long as the UPS inverter is operating 4 Output LED This green LED is illuminated as long as there is power to the critical load Either by the Inverter or Bypass 5 Load On Bypass LED This yellow LED is illuminated as long as the critical load is powered by the Bypass 6 AC Input LED This green LED is illuminated...

Page 5: ...5 ...

Page 6: ...REEN LED 11 ALARM SILENCE RED LED 2 BATTERIES ON YELLOW LED 3 INVERTER ON GREEN LED 4 OUTPUT TO CRITICAL LOAD GREEN LED 5 LOAD ON BYPASS YELLOW LED 12 INTERNAL MONITOR BATTERY OK YELLOW LED 10 BATTERY LOW VOLTAGE RED LED 9 INPUT FAILURE RED LED 8 OVERLOAD RED LED 7 UPS FAULT RED LED 6 AC INPUT ON GREEN LED AUDIBLE ALARM MONITOR RESET PUSHBUTTON MONITOR TEST PUSHBUTTON ALARM SILENCE PUSHBUTTON INTE...

Page 7: ...7 ...

Page 8: ... COMMON 9 ON BATTERIES 10 ON BATTERY COMMON 11 RECTIFIER 12 RECTIFIER COMMON 13 UPS FAILURE 14 UPS COMMON 15 LOW BATTERY 16 LOW BATTERY COMMON 17 OVERLOAD 18 OVERLOAD COMMON TERMINAL BLOCK DESCRIPTION LOCATED INSIDE BOX FIGURE 2 1 INTERNAL POWER SUPPLY HARDWIRE OPTION TB 1 3 BYPASS 4 BYPASS ...

Page 9: ...9 ...

Page 10: ...10 ...

Page 11: ...11 ...

Page 12: ...12 ...

Page 13: ...13 ...

Page 14: ...llustration purposes only and is subject to change without notice TIC is not responsible for any errors or omissions DATE 04 06 06 Drawn by JE RSAP REMOTE ALARM STATUS PANEL 4200FA 80kVA RSAP TIC 4200FA 80 1 0 15 14 13 12 11 10 9 8 7 6 5 4 3 OUTPUT OVERLOAD COMMON LOW BATTERY COMMON UPS FAILURE COMMON RECTIFIER ON COMMON ON BATTERIES COMMON LOAD ON INVERTER COMMON LOAD ON BYPASS 16 COMMON 2 12 1 3...

Reviews: