E6581315
31
5.1.2. Write command (06)
Computer
→
Inverter *The text size is 8 bytes fixed.
Inverter
No.
Command
Commu-
nication
No. (high)
Commu-
nication
No. (low)
Write Data
(high)
Write Data
(low)
CRC
(low)
CRC
(high)
(3.5bytes
Blank)
06
(3.5bytes
Blank)
1) Inverter No. (1 byte)
: Specify an inverter number between 0 and 247 (00H to F7H).
Command processing will be executed only broadcast communication “0” and with
those inverters that match set inverter numbers. Data will not be returned if “0”
(broadcast communication) and inverter numbers do not match.
2) Command (1 byte)
: Set the write command (06H fixed).
3) Communication No. (2 bytes) : Set in the order of high to low numbers.
4) Write data (2 bytes)
: Set in the order of high to low write data.
5) CRC (2 bytes)
: Set generation results of CRC in the order of low to high numbers. For the method to
generate CRC, see “5.2 CRC Generation.” Note that the setting sequence is rever-
sal to that of others.
Inverter
→
Computer (Normal return) *The text size is 8 bytes fixed.
Inverter
No.
Command
Commu-
nication
No. (high)
Commu-
nication
No. (low)
Write Data
(high)
Write Data
(low)
CRC
(low)
CRC
(high)
(3.5bytes
Blank)
06
(3.5bytes
Blank)
1) Command (1 byte)
: Write command (06H fixed) will be returned.
2) Write data (2 bytes)
: Returned in the order of write data (high) and (low).
Inverter
→
Computer (Abnormal return) *The text size is 5 bytes fixed.
Inverter No. Command Error Code
CRC
(low)
CRC
(high)
(3.5bytes
Blank)
86
(3.5bytes
Blank)
1) Command (1 byte)
: 86H fixed (Read command error) (C 80H)
2) Error code (1 byte)
: See “4.3 Transmission errors.”
Example: Writing in frequency command value (FA01) (60Hz)
(Computer
→
inverter)
01 06 FA 01 17 70 E6 C6
(Inverter
→
computer)
01 06 FA 01 17 70 E6 C6
Example: Communication number error
(Computer
→
inverter)
01 06 FF FF 00 00 89 EE
(Inverter
→
computer)
01 86 02 C3 A1
Note
▼
The EEPROM life is 10,000 operations.
Do not write in the same parameter that has an EEPROM more than 10,000 times.